![Airwell CKD 30 DCI Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/airwell/ckd-30-dci/ckd-30-dci_service-manual_2880103049.webp)
11-1
TUBING CONNECTIONS
SM GCD030 1-A.0 GB
11. TUBING
CONNECTIONS
TUBE (Inch)
TORQUE (Nm)
¼”
⅜
”
½”
⅝
”
¾”
Flare Nuts
15-18
40-45
60-65
70-75
80-85
Valve Cap
13-20
13-20
18-25
18-25
40-50
Service Port Cap
11-13
11-13
11-13
11-13
11-13
1. Valve Protection Cap-end
2. Refrigerant Valve Port (use Allen wrench to open/close)
3. Valve Protection Cap
4. Refrigerant
Valve
5. Service Port Cap
6. Flare
Nut
7. Unit Back Side
8. Copper
Tube
When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction
line at the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is
required.
*Applicable for DLS18 only, for DLS24 – 44 oil traps are not required.
CONTENTS
Содержание CKD 30 DCI
Страница 38: ...7 2 SOUND LEVEL CHARACTERISTICS SM GCD030 1 A 0 GB SX 30 CKD 30 FAN SPEED LINE HI ME LO CONTENTS ...
Страница 41: ...9 1 WIRING DIAGRAMS SM GCD030 1 A 0 GB 9 WIRING DIAGRAMS 9 1 Indoor Unit PNX 30 DCI INDOOR UNIT CONTENTS ...
Страница 42: ...9 2 WIRING DIAGRAMS SM GCD030 1 A 0 GB 9 2 Indoor Unit SX 30 DCI CONTENTS ...
Страница 43: ...9 3 WIRING DIAGRAMS SM GCD030 1 A 0 GB 9 3 Indoor Unit CKD 30 DCI 9 4 Indoor Unit DLS 30 DCI CONTENTS ...
Страница 82: ...14 3 EXPLODED VIEWS AND SPARE PARTS LISTS SM GCD030 1 A 0 GB 14 3 Indoor Unit PNX 30 DCI CONTENTS ...
Страница 84: ...14 5 EXPLODED VIEWS AND SPARE PARTS LISTS SM GCD030 1 A 0 GB 14 5 Indoor Unit SX 30 DCI CONTENTS ...
Страница 89: ...14 10 EXPLODED VIEWS AND SPARE PARTS LISTS SM GCD030 1 A 0 GB 14 10 Outdoor Unit GCD 030 CONTENTS ...