TROUBLESHOOTING
SM HHD 1-A.1 GB
13-5
13.1.4
Checking the refrigeration system
Checking system pressures and other thermodynamic measures should be done when system
is in Test Mode (in Test mode, system operates in fixed settings). The performance curves
given in this manual are given for unit performance in test mode when high indoor fan speed is
selected.
Entering test mode please refer to section 12- Control system.
13.2
Simple procedures for checking the Main Parts
13.2.1
Checking Mains Voltage.
Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this
range, abnormal operation of the system is expected. If in range check the Power (Circuit)
Breaker and look for broken or loosed cable lugs or wiring mistake(s).
13.2.2
Checking Power Input.
If Indoor unit power LED is unlighted, power down the system and check the fuse of the Indoor
unit. If the fuse is OK replace the Indoor unit controller. If the fuse has blown, replace the fuse
and power up again.
Checking Power Input procedure for the Outdoor unit is the same as with the Indoor unit.
13.2.3
Checking the Outdoor Fan Motor.
For AC motor
Check the voltage between two pins Hi and N of connector OFAN on controller, normal
voltage is 220~240VAC.
For DC Motor
Check the voltage between any two pins of connector OFAN on controller, normal voltage is
280~380VDC
13.2.4
Checking the Compressor.
The compressor is brushless permanence magnetic DC motor. Three coil resistance is
same. Check the resistance between three poles. The normal value should be with the
almost same value. Pay attention U,V, W are respective to connect to
RED,YELLOW,BLUE
wires.
13.2.5
Checking the Reverse Valve (RV).
Running in heating mode, check the voltage between two pins of reverse valve connector,
normal voltage is 220~240VAC.
Содержание AWAU-YHD009-H11
Страница 14: ...OUTLINE DIMENSION 4 2 SM HHD 1 A 1 GB 4 2 Outdoor YHD009 YHD012 4 3 Outdoor YHD018...
Страница 15: ...OUTLINE DIMENSION SM HHD 1 A 1 GB 4 3 4 4 Outdoor YHD024...
Страница 16: ...PERFORMANCE DATA SM HHD 1 A 1 GB 5 1 5 PERFORMANCE DATA 5 1 Model HHD009 YHD009 HHD012 YHD012...
Страница 17: ...PERFORMANE DATA 5 2 SM HHD 1 A 1 GB 5 2 Model HHD018 YHD018 HHD018 YHD018...
Страница 18: ...PRESSURE CURVES SM HHD 1 A 1 GB 6 1 6 PRESSURE CURVES TBD...
Страница 19: ...SOUND LEVEL CHARACTERISTICS SM HHD 1 A 1 GB 7 1 7 SOUND LEVEL CHARACTERISTICS 7 1 Sound Pressure Level...
Страница 20: ...SOUND LEVEL CHARACTERISTICS 7 2 7 2 Soud Pressure Level Spectrum Measured as Figure 1 TBD...
Страница 22: ...WIRING DIAGRAMS SM HHD 1 A 1 GB 9 1 9 WIRING DIAGRAM 9 1 HHD009 HHD012 9 2 HHD018 HHD024...
Страница 23: ...WIRING DIAGRAM 9 2 SM HHD 1 A 1 GB 9 3 YHD009 YHD012 9 4 YHD018 YHD024...
Страница 49: ...EXPLODED VIEW SPARE PART LIST SM HHD 1 A 1 GB 15 3 15 3 Exploded view of indoor unit HHD012 EV AWSI HHD012 N11...
Страница 51: ...EXPLODED VIEW SPARE PART LIST SM HHD 1 A 1 GB 15 5 15 5 Exploded view of indoor unit HHD018 EV AWSI HHD018 N11...
Страница 53: ...EXPLODED VIEW SPARE PART LIST SM HHD 1 A 1 GB 15 7 15 7 Exploded view of indoor unit HHD024 EV AWSI HHD024 N11...
Страница 62: ...APPENDIX 16 SM HHD 1 A 1 GB APPENDIX...