Electrical Control Function
144
Electrical Control System
Low indoor room temperature protection
All protections are active and the same as that in cooling mode.
For other models:
Indoor fan speed is fixed at breeze and can’t be changed. The louver angle is the same as in cooling mode.
Low indoor room temperature protection
In drying mode, if room temperature is lower than 10
℃
, the compressor will stop and not resume until room
temperature exceeds 12
℃
.
All protections are active and the same as that in cooling mode.
1.3.6 Timer function
1.3.6.1 Timing range is 24 hours.
1.3.6.2 Timer on. The machine will turn on automatically when reaching the setting time.
1.3.6.3 Timer off. The machine will turn off automatically when reaching the setting time.
1.3.6.4 Timer on/off. The machine will turn on automatically when reaching the setting “on” time, and then
turn off automatically when reaching the setting “off” time.
1.3.6.5 Timer off/on. The machine will turn off automatically when reaching the setting “off” time, and then
turn on automatically when reaching the setting “on” time.
1.3.6.6 The timer function will not change the AC current operation mode. Suppose AC is off now, it will not
start up firstly after setting the “timer off” function. And when reaching the setting time, the timer LED will be
off and the AC running mode has not been changed.
1.3.6.7 The setting time is relative time.
1.3.7 Economy function
1.3.7.1 The sleep function is available in cooling, heating or auto mode.
1.3.7.2. Operation process in sleep mode is as follow:
When cooling, the setting temperature rises 1
℃
(be lower than 30
℃
) every one hour, 2 hours later the
setting temperature stops rising and the indoor fan is fixed at low speed.
When heating, the setting temperature decreases 1
℃
(be higher than 17
℃
) every one hour, 2 hours later
the setting temperature stops rising and indoor fan is fixed at low speed. (Anti-cold wind function has the
priority).
1.3.7.3 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode, the unit will turn off.
1.3.7.4 Timer setting is available
1.3.8 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart module. In
case of a sudden power failure, the module memorizes the setting conditions before the power failure. The
unit will resume the previous operation setting (not including Swing function) automatically after 3 minutes
when power returns.
Содержание AWAU-YCZ218-H11
Страница 24: ...Dimensions Outdoor Units 97 AWAU YCZ536 H11...
Страница 28: ...Wiring Diagrams Outdoor Units 101 4 Wiring Diagrams AWAU YCZ218 H11 7SP091166 AWAU YCZ218 H11 7SP091170...
Страница 29: ...Wiring Diagrams 102 Outdoor Units AWAU YCZ327 H11 7SP091167 AWAU YCZ327 H11 7SP091171...
Страница 30: ...Wiring Diagrams Outdoor Units 103 AWAU YCZ430 H11 7SP091168 AWAU YCZ430 H11 7SP091172...
Страница 31: ...Wiring Diagrams 104 Outdoor Units AWAU YCZ536 H11 7SP091169 AWAU YCZ542 H11 7SP091173...
Страница 37: ...Exploded View and Spare Part list 110 Outdoor Units Exploded view of model AWAU YCZ218 H11 7SP091170...
Страница 39: ...Exploded View and Spare Part list 112 Outdoor Units Exploded View of outdoor unit AWAU YCZ327 H11 7SP091167...
Страница 41: ...Exploded View and Spare Part list 114 Outdoor Units Exploded view of model AWAU YCZ327 H11 7SP091171...
Страница 43: ...Exploded View and Spare Part list 116 Outdoor Units Exploded View of outdoor unit AWAU YCZ430 H11 7SP091168...
Страница 45: ...Exploded View and Spare Part list 118 Outdoor Units Exploded View of outdoor unit AWAU YCZ430 H11 7SP091172...
Страница 47: ...Exploded View and Spare Part list 120 Outdoor Units Exploded View of outdoor unit AWAU YCZ536 H11 7SP091169...
Страница 49: ...Exploded View and Spare Part list 122 Outdoor Units Exploded View of outdoor unit AWAU YCZ542 H11 7SP091173...
Страница 107: ...SERVICE MANUAL Multi Splits Series...