Read Before Installation

Maximum Operation Pressure

Applicable Refrigerants

3.4MPa

R22, R407C

4.15MPa

R410A

Use pipes that meet the local standards.

Use pipes made of phosphorus deoxidized copper.
Since the operation pressure of the units that use R410A is higher than that of the units for use with R22, use pipes with
at least the radial thickness specified in the chart below. (Pipes with a radial thickness of 0.7mm or less may not be used.)

Although it was possible to use type-O for pipes with a size of up to   19.05(3/4") with conventional refrigerants, use type-
1/2H pipes for units that use R410A.(Type-O pipes may be used if the pipe size is  19.05 and the radial thickness is 1.2t.)
The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local standards.

The flare machining dimensions for units that use R410A is larger than those for units that use R22 in order to increase
air tightness.

If a clutch type flare tool is used to machine flares on units that use R410A, make the protruding part of the pipe between
1.0 and 1.5mm. Copper pipe gauge for adjusting the length of pipe protrusion is useful.

Size(mm)

Radial Thickness(mm)

Size(inch)

Type

Type-O pipes

Type-1/2H or Hpipes

Piping Materials

Types of Copper Pipes (Reference)

The table shows the standards in Japan. Using this table as a reference, choose pipes that meet the local standards.

Piping Materials/Radial Thickness

Flare Machining (type-O and OL only)

Flare Machining Dimension(mm)

External dimension of pipes

Size

Dimension A

R410A

R22

6.35

9.52

12.7

15.88

19.05

1/4"

3/8"

1/2"

5/8"

3/4"

9.1

13.2

16.6

19.7

24.0

9.0

13.0

16.2

19.4

23.3

Flare Nut

Type-2 flare nuts instead of type-1 nuts are used to increase the strength. The size of some of the flare nuts have also
been changed.
Flare nut dimension(mm)

R410A(Type2)

R22(Type1)

6.35

9.52
12.7

15.88

19.05

1/4"

3/8"
1/2"

5/8"

3/4"

17.0

22.0

26.0

29.0

36.0

17.0

22.0

24.0

27.0

36.0

6.35

9.52

12.7

15.88

1/4''

3/8''

1/2''

5/8''

0.8t

0.8t

0.8t

1.0t

19.05

3/4''

1.0t

External dimension of pipes

Size

Dimension B

Dimension B

Содержание AW-YSDM048-H11

Страница 1: ...before installation Keep this operation manual for future reference Contents Safety Precautions Read Before Installation Name of Parts Installation Procedure Troubleshootingve and Move and scrap the a...

Страница 2: ...ction of the use of Certain Hazardous Substances in Electrical and Electronic Equipment EU RoHS Directive WEEE In accordance with the directive 2012 19 EU of the European parliament herewith we inform...

Страница 3: ...UCTIONS These information can ensure the correct operation of the machine After a long time use of air conditioner the base should be checked for any damages If the damaged base is not repaired the un...

Страница 4: ...moke or fire Only use refrigerant R410A as indicated on the unit when installing or relocating the unit The use of any other refrigerant or an introduction of air into the unit circuit may cause the u...

Страница 5: ...e a charging cylinder The use of charging cylinder will change the composition of the refrigerant and lead to power loss Exercise special care when handling the tools An introduction of foreign object...

Страница 6: ...Tear up the plastic bags before disposing of them to prevent accidents Properly dispose of the packing materials Do not touch the refrigerant pipes with bare hands during and immediately after operati...

Страница 7: ...Refrigerant charging Vacuum Gauze Checking vacuum degree Tools Materials Use Notes Charging Cylinder Refrigerant Charging Must not be used with R410 type units CAUTION Items to Be Checked 1 Verify the...

Страница 8: ...tightness If a clutch type flare tool is used to machine flares on units that use R410A make the protruding part of the pipe between 1 0 and 1 5mm Copper pipe gauge for adjusting the length of pipe pr...

Страница 9: ...il from flowing back into the refrigerant circuit when the vacuum pump power is turned off power failure It is also possible to attach a check valve to the actual vacuum pump afterwards Standard degre...

Страница 10: ...where obstacles do not exist near the air inlet and air outlet Place where the air outlet may not be exposed to a strong wind Place surrounded at four sides are not suitable for installation A 1m or...

Страница 11: ...areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which...

Страница 12: ...ng information 2 Installation of outdoor unit Give enough room for the concrete foundation to fix by anchor bolts Place the concrete foundation deep enough Install the unit so that the angle of inclin...

Страница 13: ...not to let foreign matters such as sands enter the pipe 4 Piping connection method Forced fastening without centering may damage the threads and cause a gas leakage Model One way piping length Vertica...

Страница 14: ...kage will be found 3 Pressurize for about 24 hours at 3 0MPa 30 kg cm 2 g A small leakage will be found Air Tightness Test When pressurizing for 24 hours a variation of 1 C in the ambient temperature...

Страница 15: ...the inspection of gas leakge No gas leakage In case of gas leakage tighten parts of pipe connection If leakage stops then proceed the step 6 If it does not stop gas leakage discharge whole refrigerant...

Страница 16: ...able and connecting cable should be self provided All the cables shall have got the European authentication certificate During installation when the connecting cables break off it must be assured that...

Страница 17: ...RE TO EXECUTE OFF OPERATION BEFORE ELECTRIC POWER IS DISCONNECTED FOR SERVICING This unit has a function of automatic restart system after recovering power stoppage 1 Before starting test run for all...

Страница 18: ...Troubleshooting 18...

Страница 19: ...itioning the content of lead mercury hexavalent chromium polybrominated biphenyls and polybrominated diphenyl ethers are not more than 0 1 mass fraction and cadmium is not more than 0 01 mass fraction...

Страница 20: ......

Отзывы: