Safety Precautions

Precautions for Handling Units for Use with R410A

Do not use the existing refrigerant piping

The old refrigerant and refrigerator oil in the existing piping
contain a large amount of chlorine, which will cause the
refrigerator oil in the new unit to deteriorate.
R410A is a high-pressure refrigerant, and the use of the
existing piping may result in bursting.

Keep the inner and outer surfaces of the pipes clean and
free of contaminants such as sulfur, oxides, dust/dirt shaving
particles,oils,and moisture.

Contaminants inside the refrigerant piping will cause the
refrigerant oil to deteriorate.

Use a vacuum pump with a reverse-flow check valve.

If other types of valves are used, the vacuum pump oil will
flow back into the refrigerant cycle and cause the refrigerator
oil to deteriorate.

Do not use the following tools that have been used with the
conventional refrigerants. Prepare tools that are for exclusive
use with R410A.
(Gauge manifold, charging hose, gas leak detector,
reverse-flow check valve, refrigerant charge base,vacuum
gauge, and refrigerant recovery equipment.)

If refrigerant and/or refrigerant oil left on these tools are
mixed in with R410, or if water is mixed with R410A, it will
cause the refrigerant to deteriorate.
Since R410A does not contain chlorine, gas-leak detectors
for conventional refrigerators will not work.

Store the piping to be used during installation indoors, and
keep both ends of the piping sealed until immediately before
brazing.(keep elbows and other joints wrapped in plastic.)

If dust, dirt, or water enters the refrigerant cycle, it may
cause the oil in the unit to deteriorate or may cause the
compressor to malfunction.

A large amount of mineral oil will cause the refrigerating
machine oil to deteriorate.

Use a small amount of ester oil, ether oil, or alkylbenzene
to coat flares and flange connections.

Use liquid refrigerant to charge the system.

Charge the unit with gas refrigerant will cause the  refrigerant
in the cylinder to change its composition and will lead to
a drop in performance

Do not use a charging cylinder.

The use of charging cylinder will change the composition
of the refrigerant and lead to power loss.

Exercise special care when handling the tools.

An introduction of foreign objects such as dust, dirt or
water into the refrigerant cycle will cause the refrigerating
machine oil to deteriorate.

Only use R410A refrigerant.

The use of refrigerants containing chlorine(i.e. R22) will
cause the refrigerant to deteriorate.

Caution

Caution

In the event of a refrigerant gas leak, provide adequate
ventilation to the room.
If leaked refrigerant gas is exposed to a heat source, noxious
gases may form.

Do not touch the fins on the heat exchanger with bare hands,
for they are sharp and dangerous.

Do not try to defeat the safety features of the devices, and
do not change the settings.
Defeating the safety features on the unit such as the pressure
switch and temperature switch or using parts other than the
dealer or specialist may result in fire or explosion.

When installing the unit in a small room, safeguard against
hypoxia that results from leaked refrigerant reaching the
threshold level.
Consult the dealer for necessary measures to take.
When relocating the air conditioner, consult the dealer or
a specialist.
Improper installation may result in water leak, electric shock,
or fire.
After completing the service work, check for a refrigerant
gas leak.
If leaked gas refrigerant is exposed to a heat source such
as fan heater,stove,and electric grill, noxious gases may
form.
Only use specified parts.
Have the unit professionally installed. Improper installation
may cause water leak, electric shock,smoke, or fire.

With All-Fresh type air conditioners, outdoor air may be
directly blown into the room upon thermo off. Take this into
consideration when installing the unit.
Direct exposure to outdoor air may present a health hazard,
and it may also cause food items to deteriorate.

Children should be supervised to ensure that they do not
play with the appliance.

WARNING

This appliance is not intended for use by persons (including
children) with reducedphysical, sensory or mental capabilities,
or lack of experience and knowledge, unless they have been
given supervision or instruction concerning use of the
appliance by a person responsible for their safety.

Содержание AW-YSDM048-H11

Страница 1: ...before installation Keep this operation manual for future reference Contents Safety Precautions Read Before Installation Name of Parts Installation Procedure Troubleshootingve and Move and scrap the a...

Страница 2: ...ction of the use of Certain Hazardous Substances in Electrical and Electronic Equipment EU RoHS Directive WEEE In accordance with the directive 2012 19 EU of the European parliament herewith we inform...

Страница 3: ...UCTIONS These information can ensure the correct operation of the machine After a long time use of air conditioner the base should be checked for any damages If the damaged base is not repaired the un...

Страница 4: ...moke or fire Only use refrigerant R410A as indicated on the unit when installing or relocating the unit The use of any other refrigerant or an introduction of air into the unit circuit may cause the u...

Страница 5: ...e a charging cylinder The use of charging cylinder will change the composition of the refrigerant and lead to power loss Exercise special care when handling the tools An introduction of foreign object...

Страница 6: ...Tear up the plastic bags before disposing of them to prevent accidents Properly dispose of the packing materials Do not touch the refrigerant pipes with bare hands during and immediately after operati...

Страница 7: ...Refrigerant charging Vacuum Gauze Checking vacuum degree Tools Materials Use Notes Charging Cylinder Refrigerant Charging Must not be used with R410 type units CAUTION Items to Be Checked 1 Verify the...

Страница 8: ...tightness If a clutch type flare tool is used to machine flares on units that use R410A make the protruding part of the pipe between 1 0 and 1 5mm Copper pipe gauge for adjusting the length of pipe pr...

Страница 9: ...il from flowing back into the refrigerant circuit when the vacuum pump power is turned off power failure It is also possible to attach a check valve to the actual vacuum pump afterwards Standard degre...

Страница 10: ...where obstacles do not exist near the air inlet and air outlet Place where the air outlet may not be exposed to a strong wind Place surrounded at four sides are not suitable for installation A 1m or...

Страница 11: ...areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which...

Страница 12: ...ng information 2 Installation of outdoor unit Give enough room for the concrete foundation to fix by anchor bolts Place the concrete foundation deep enough Install the unit so that the angle of inclin...

Страница 13: ...not to let foreign matters such as sands enter the pipe 4 Piping connection method Forced fastening without centering may damage the threads and cause a gas leakage Model One way piping length Vertica...

Страница 14: ...kage will be found 3 Pressurize for about 24 hours at 3 0MPa 30 kg cm 2 g A small leakage will be found Air Tightness Test When pressurizing for 24 hours a variation of 1 C in the ambient temperature...

Страница 15: ...the inspection of gas leakge No gas leakage In case of gas leakage tighten parts of pipe connection If leakage stops then proceed the step 6 If it does not stop gas leakage discharge whole refrigerant...

Страница 16: ...able and connecting cable should be self provided All the cables shall have got the European authentication certificate During installation when the connecting cables break off it must be assured that...

Страница 17: ...RE TO EXECUTE OFF OPERATION BEFORE ELECTRIC POWER IS DISCONNECTED FOR SERVICING This unit has a function of automatic restart system after recovering power stoppage 1 Before starting test run for all...

Страница 18: ...Troubleshooting 18...

Страница 19: ...itioning the content of lead mercury hexavalent chromium polybrominated biphenyls and polybrominated diphenyl ethers are not more than 0 1 mass fraction and cadmium is not more than 0 01 mass fraction...

Страница 20: ......

Отзывы: