FWDB Low temperature floor ceiling-Technical Manual R32-50Hz
For construction convenience, before laying pipes, use insulation material to insulate the pipes to
be deal with, at the same time, at two ends of the pipe, remain some length not to be insulated, in order to be
welded and check the leakage after laying the pipes.
5.2.3. Insulate for the jointing area, expanding area and the flange area
①
Insulate for the jointing area, expanding area and the flange area should be done after checking leakage
of the pipes
②
Make sure there’s no clearance in the joining part of the accessorial insulation material and local
preparative insulation material.
5.3Drainage pipe insulation
The connection part should be insulated, or else water will be condensing at the non-insulation
part.
5.4Note
5.4.1 The jointing area, expanding area and the flange area should be heat insulated after passing
the pressure test
5.4.2 The gas and liquid pipe should be heat insulated individually, the connecting part should be
heat insulated individually.
5.4.3 Use the attached heat-insulation material to insulate the pipe connections (pipes’ tie-in ,expand nut ) of
the indoor unit
51
Содержание AW-FWDB018-N91
Страница 15: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 13 4 Service Space ...
Страница 18: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 16 6 2 AW FWDB024 N91 ...
Страница 33: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 4 2 AW YMDB024 H91 31 ...
Страница 37: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 8 Exploded Views 8 1 AW YMDB018 H91 35 ...
Страница 39: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 8 2 AW YMDB024 H91 37 ...
Страница 55: ...RFWDB Low temperature floor ceiling Technical Manual R32 50Hz Part 5 Controller 53 1 Wired Controller 54 ...
Страница 56: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz Telecommande filaire RCW23 1 Wired Controller 54 ...
Страница 57: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 55 ...