FWDB Low temperature floor ceiling-Technical Manual R32-50Hz
4.3 Upwards drainage (drain pump)
For Four-way cassette (compact)
For Round-way cassette
4.4 Convergent drainage
4.4.1. The number of indoor units should be as small as possible to prevent the traverse main pipe
overlong.
4.4.2. Indoor unit with drain pump and indoor unit without drain pump should be in different
drainage system.
4.4.3. Selecting the diameter
Number of connecting indoor units → Calculate drainage volume → Select the diameter
Calculate allowed volume =Total cooling capacity of indoor units(HP)×2 (l/ hr)
Allowed volume(lean 1/50) (l/ hr)
I.D. (mm)
Thick
Hard PVC
∽
≤14
¢
25
3.0
Hard PVC
14
<∽
≤88
¢
30
3.5
Hard PVC
88
<∽
≤334
¢
40
4.0
Hard PVC
175
<∽
≤334
¢
50
4.5
Hard PVC
334
<∽
¢
80
6.0
48
Содержание AW-FWDB018-N91
Страница 15: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 13 4 Service Space ...
Страница 18: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 16 6 2 AW FWDB024 N91 ...
Страница 33: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 4 2 AW YMDB024 H91 31 ...
Страница 37: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 8 Exploded Views 8 1 AW YMDB018 H91 35 ...
Страница 39: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 8 2 AW YMDB024 H91 37 ...
Страница 55: ...RFWDB Low temperature floor ceiling Technical Manual R32 50Hz Part 5 Controller 53 1 Wired Controller 54 ...
Страница 56: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz Telecommande filaire RCW23 1 Wired Controller 54 ...
Страница 57: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 55 ...