FWDB Low temperature floor ceiling-Technical Manual R32-50Hz
3 Additional Refrigerant Charge
Caution
● Refrigerant cannot be charged until field wiring has been completed.
● Refrigerant may only be charged after performing the leak test and the vacuum pumping.
● When charging a system, care shall be taken that its maximum permissible charge is never
exceeded, in view of the danger of liquid hammer.
● Charging with an unsuitable substance may cause explosions and accidents, so always ensure
that the appropriate refrigerant is charged.
● Refrigerant containers shall be opened slowly.
● Always use protective gloves and protect your eyes when charging refrigerant.
The outdoor unit is factory charged with refrigerant. Calculate the added refrigerant according to
the diameter and the length of the liquid side pipe of the outdoor unit/indoor unit
R(g)
D(mm)
L(m)
Φ6.4
Φ9.5
Less than 5m (One-way)
—
—
Added Refrigerant When Over 5m (One-way)
12g/m × L
24g/m × L
Remark:
R (g): Additional refrigerant to be charged
L (m): The length of the refrigerant pipe (one-way)
D (mm): Liquid side piping
46
Содержание AW-FWDB018-N91
Страница 15: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 13 4 Service Space ...
Страница 18: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 16 6 2 AW FWDB024 N91 ...
Страница 33: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 4 2 AW YMDB024 H91 31 ...
Страница 37: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 8 Exploded Views 8 1 AW YMDB018 H91 35 ...
Страница 39: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 8 2 AW YMDB024 H91 37 ...
Страница 55: ...RFWDB Low temperature floor ceiling Technical Manual R32 50Hz Part 5 Controller 53 1 Wired Controller 54 ...
Страница 56: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz Telecommande filaire RCW23 1 Wired Controller 54 ...
Страница 57: ...FWDB Low temperature floor ceiling Technical Manual R32 50Hz 55 ...