19

A zone can be marked as Disabled if the port is faulty. Then it will not be used 
by any group. The group used this zone before can choose another good zone.
Electronic balancing feature of ZoneTouch 3 offers the flexibility of balancing 
the amount of airflow to each zone electronically. Once the opening position of 
the damper is set, the damper will only open to this position. The default setting 
for each damper is 100% opening position and the adjustable range is between 
5% and 100% with 5% increment. The zone settings can be conducted on the 
touch screen as below.
a.   On ‘Installers’ screen, touch Zones menu 
b)  Touching the percentage value for the zone to bring up the value input  
 

dialog. Confirm the required value to start the balancing process. All zones  

 

will open to its balanced position. You can input proper value and check the  

 

airflow until the right value is reached. 

c)  Repeat the process for all zones which need balancing. Then touch the Stop  
 

button to stop the balancing process.

d)  Mark the zone as Disabled if the zone port is faulty.

Note: The %OPEN value on the Zoning screen can be operated by the user 

for additional air flow adjustment to the groups. The overall opening % of the 

zone is calculated as %OPEN x Balance %.

Zone Setting contd. 

Содержание ZoneTouch3

Страница 1: ...airtouch net au Installer Manual...

Страница 2: ......

Страница 3: ...1 6 Reset and Save current system settings 17 5 2 Zone Setting 18 5 3 Grouping Zones 20 5 4 Spill or Bypass 21 5 5 Enabling Disabling Service Reminder 23 5 6 System Info 24 5 7 Setting up Wi Fi Conne...

Страница 4: ...4...

Страница 5: ...and its optional extension module extra 8 zones control the position of the motorized damper of each zone 1 3 Motorized Damper Bright Green Motorized dampers drive the blade of the damper to adjust t...

Страница 6: ...le extension module WiFi router to connect to smart phones up to 16 zone dampers and up to two consoles Figure below shows the connection of devices such as the WiFi router a console and eight dampers...

Страница 7: ...cts a motorized damper to the relevant output port clearly marked on the main or extension module Figure below shows the connection of eight dampers to the extension module Main and extension modules...

Страница 8: ...ference Configuration contd Figure below shows the linking of the main module to the extension module consoles and smart phone 24V 24V Touch Screen 1 Home Router Touch Screen 2 Smart Phones Main Modul...

Страница 9: ...four zones Example There could be one or more zones going into a common area such as Kitchen Dining or Family Dining room Work out the total group number Maximum total group number in a system is 16...

Страница 10: ...t step 4 4 to connect other zone dampers to their relevant zone ports on the main and extension modules 4 1 Mount the main and or extension modules if using more than 8 zones by screwing the boxes to...

Страница 11: ...and the other to the extension module 4 7 Connect the 24V AC transformer to screw terminals on the main control module If extension module is used connect another 24 VAC transformer to the screw term...

Страница 12: ...o be opened to mount the console on the wall Follow the steps below to carefully install the console to the wall a Slide the back base to bottom side to clear the stops on the front cover b Remove the...

Страница 13: ...g four screws on the marked positions e Retrieve the console cable from main control module out of the cable hole and plug it into the console f Align the bottom edge of the back base with the bottom...

Страница 14: ...all and make sure the back of front cover is flush against the wall And then push the front cover downwards with two figures holding the top side of the front cover where there are two slots till the...

Страница 15: ...t value Polyaire but can be changed Touching Installer s tab will bring up password input page After inputting the correct password installer s setting page will come up In the user s settings which a...

Страница 16: ...l zone calculation the system needs to know the total number of groups to be installed The factory default number is 8 IMPORTANT This number must be equal to the total group number used in the system...

Страница 17: ...nsor value may be higher than the room temperature When the screen goes to sleep mode for a while its temperature value may be close to real room temperature In extremely rare cases the temperature va...

Страница 18: ...18 5 2 Zone Setting Zone Setting...

Страница 19: ...an be conducted on the touch screen as below a On Installers screen touch Zones menu b Touching the percentage value for the zone to bring up the value input dialog Confirm the required value to start...

Страница 20: ...d before or after grouping Grouping can be carried out as follows a In Installers screen touch Grouping to enter Grouping screen b Touch the edit field of the group c Then touch or button to add or mi...

Страница 21: ...oups being closed When choosing groups for spill it is strongly recommended NOT to use bedrooms as spill groups During sleep time if the air conditioner is on and spill groups are forced to open the s...

Страница 22: ...up unless there is a permanent open zone used as spill zone Otherwise there will be no spill group when all zones are closed and damage may be caused by high pressure building up inside ducts if air c...

Страница 23: ...ice Reminder is disabled by default but can be enabled as follows In the Installer settings screen touch Service to enter the Service screen a Touch the service reminder option buttons to enable or di...

Страница 24: ...w product model Device ID current hardware and software versions of the system If there is a new version there will be a red dot on the Quick menu of the homepage Following the red dot and prompts wil...

Страница 25: ...ar ZoneTouch 3 from Apple Store or Google Play Store can be run from mobile devices if the mobile is connected to the same WiFi network as the ZoneTouch console The connection will stay permanent till...

Страница 26: ...turn groups on or off to check if the dampers are correctly connected by feeling the air at the outlet d The Turbo group can be tested by selecting the relevant chosen group as Turbo mode in the Setti...

Страница 27: ...urned off Check if Spill status is displayed for the zone Opening other zones will rectify the error Check spill groups No display on the LCD Check if the cable is plugged in properly Unplug the cable...

Страница 28: ...ications and procedures are correct at time of publication but are subject to change without notice Please read the instructions before installing this Zone Control System Polyaire Pty Ltd does not ac...

Отзывы: