background image

17

5.1.2 Installer Settings Password

The password is used to prevent unauthorized changing of the installer settings.  
To reset this password, touch the password edit field in the ‘Parameter’ screen, and  
then type in the new password and touch ‘Enter’ key to confirm the password change. 

5.1.3 Damper RPM Setting

ZoneTouch 3 can work with other dampers which are not made by Polyaire.  
But the damper motors have to meet certain requirements:
Power supply: 24 VAC
Drive Open and Drive Close
Revolution per Minute (RPM): 0.1 to 2.5 

5.1.4 Damper Rotation Direction

If dampers move in the wrong direction while zones are being turned on and off, 
this setting will reverse the damper rotation direction and make sure the damper is 
closing or opening while the zone is being turned off or on respectively. 

5.1.5 Touchpad Temp

Touchpad has a temperature sensor. When the screen is on, it will generate heat  
and the temperature sensor value may be higher than the room temperature.  
When the screen goes to sleep mode for a while, its temperature value may be  
close to real room temperature. 
In extremely rare cases, the temperature value might need calibration. If necessary, 
do it when the screen is not heated up and use an accurate reference temperature 
gauge. Input the correct value to match the reference gauge.
If there are two consoles connected in the system, they will be automatically identified 
as touchpad 1 and 2 and their temperature can be displayed on its own screen.

5.1.6 Reset and Save current system settings 

To record all system settings, press Backup Settings button.  
If the main module has been replaced, the system can be recovered from this file. 
Press the Recover Saved Settings button to recover. After successful recovery, the 
system has to be powered off for at least 30 seconds and then powered back on  
to use the recovered settings.
If the system needs to be reset to factory default settings in some cases, press Reset 
to Factory. All group names and settings will be back to original factory settings.

 

Parameters contd. 

Содержание ZoneTouch3

Страница 1: ...airtouch net au Installer Manual...

Страница 2: ......

Страница 3: ...1 6 Reset and Save current system settings 17 5 2 Zone Setting 18 5 3 Grouping Zones 20 5 4 Spill or Bypass 21 5 5 Enabling Disabling Service Reminder 23 5 6 System Info 24 5 7 Setting up Wi Fi Conne...

Страница 4: ...4...

Страница 5: ...and its optional extension module extra 8 zones control the position of the motorized damper of each zone 1 3 Motorized Damper Bright Green Motorized dampers drive the blade of the damper to adjust t...

Страница 6: ...le extension module WiFi router to connect to smart phones up to 16 zone dampers and up to two consoles Figure below shows the connection of devices such as the WiFi router a console and eight dampers...

Страница 7: ...cts a motorized damper to the relevant output port clearly marked on the main or extension module Figure below shows the connection of eight dampers to the extension module Main and extension modules...

Страница 8: ...ference Configuration contd Figure below shows the linking of the main module to the extension module consoles and smart phone 24V 24V Touch Screen 1 Home Router Touch Screen 2 Smart Phones Main Modul...

Страница 9: ...four zones Example There could be one or more zones going into a common area such as Kitchen Dining or Family Dining room Work out the total group number Maximum total group number in a system is 16...

Страница 10: ...t step 4 4 to connect other zone dampers to their relevant zone ports on the main and extension modules 4 1 Mount the main and or extension modules if using more than 8 zones by screwing the boxes to...

Страница 11: ...and the other to the extension module 4 7 Connect the 24V AC transformer to screw terminals on the main control module If extension module is used connect another 24 VAC transformer to the screw term...

Страница 12: ...o be opened to mount the console on the wall Follow the steps below to carefully install the console to the wall a Slide the back base to bottom side to clear the stops on the front cover b Remove the...

Страница 13: ...g four screws on the marked positions e Retrieve the console cable from main control module out of the cable hole and plug it into the console f Align the bottom edge of the back base with the bottom...

Страница 14: ...all and make sure the back of front cover is flush against the wall And then push the front cover downwards with two figures holding the top side of the front cover where there are two slots till the...

Страница 15: ...t value Polyaire but can be changed Touching Installer s tab will bring up password input page After inputting the correct password installer s setting page will come up In the user s settings which a...

Страница 16: ...l zone calculation the system needs to know the total number of groups to be installed The factory default number is 8 IMPORTANT This number must be equal to the total group number used in the system...

Страница 17: ...nsor value may be higher than the room temperature When the screen goes to sleep mode for a while its temperature value may be close to real room temperature In extremely rare cases the temperature va...

Страница 18: ...18 5 2 Zone Setting Zone Setting...

Страница 19: ...an be conducted on the touch screen as below a On Installers screen touch Zones menu b Touching the percentage value for the zone to bring up the value input dialog Confirm the required value to start...

Страница 20: ...d before or after grouping Grouping can be carried out as follows a In Installers screen touch Grouping to enter Grouping screen b Touch the edit field of the group c Then touch or button to add or mi...

Страница 21: ...oups being closed When choosing groups for spill it is strongly recommended NOT to use bedrooms as spill groups During sleep time if the air conditioner is on and spill groups are forced to open the s...

Страница 22: ...up unless there is a permanent open zone used as spill zone Otherwise there will be no spill group when all zones are closed and damage may be caused by high pressure building up inside ducts if air c...

Страница 23: ...ice Reminder is disabled by default but can be enabled as follows In the Installer settings screen touch Service to enter the Service screen a Touch the service reminder option buttons to enable or di...

Страница 24: ...w product model Device ID current hardware and software versions of the system If there is a new version there will be a red dot on the Quick menu of the homepage Following the red dot and prompts wil...

Страница 25: ...ar ZoneTouch 3 from Apple Store or Google Play Store can be run from mobile devices if the mobile is connected to the same WiFi network as the ZoneTouch console The connection will stay permanent till...

Страница 26: ...turn groups on or off to check if the dampers are correctly connected by feeling the air at the outlet d The Turbo group can be tested by selecting the relevant chosen group as Turbo mode in the Setti...

Страница 27: ...urned off Check if Spill status is displayed for the zone Opening other zones will rectify the error Check spill groups No display on the LCD Check if the cable is plugged in properly Unplug the cable...

Страница 28: ...ications and procedures are correct at time of publication but are subject to change without notice Please read the instructions before installing this Zone Control System Polyaire Pty Ltd does not ac...

Отзывы: