4.2 POWER cable
Standard sensor cables with 5-pin circular female connector, M12 thread, A-
coded
Straight or angled connectors can be used
Diameter of each conductor strand min. 0,25mm² (AWG 24)
Cables can be shielded or not shielded. A shield is not absolutely necessary but
improves the EMC performance of the valve terminal.
When using shielded cables, both sides of the shield should be grounded. Do
not forget to connect a grounding strap to the grounding screw of the valve ter-
minal.
ATTENTION:
Current load per copper strand:
max. 2.5 A @ 0,25mm² [AWG 24]
max. 3.4 A @ 0,34mm² [AWG 22]
IP protection code: IP65 or higher
Material of cable jacket: PUR or PVC. Resistant against environmental influ-
ences and chemicals (oil, detergents, temperatures, dust etc.)
For use in drag chains use special drag chain cables only. Consider the mini-
mum bending radius also.
Example of an M12 sensor cable (M12 female connector 5-pin and open wires)
Содержание RE-46