Airstream INTER 2V4SA Скачать руководство пользователя страница 31

10

INTER 2V4SA, rev.02

INTER 2V4SA

5. 

Changing a Parameter

5.1.  Using the Display

Flashing Values: 

The display 

will  flash  in  certain  cases 
and not in others. The flash-
ing indicates that the value 
shown  can  be  adjusted.  A 
value  that  is  not  flashing 
cannot be adjusted.

Relative and Absolute Values: 

Some param-

eter  adjustments  are  displayed  both  as  a 
relative value and an absolute temperature. 
This  applies  all  heating  and  cooling  differ-
entials, the mist differential and the heater 
offset. The parameter is first displayed as a 
relative  value.  The  corresponding  absolute 
temperature is displayed after six seconds if 
no action is taken by the user. The absolute 
value is the temperature at which the stage 
turns on (except in the case of the heater and 
mist offsets where the value displayed is the 
temperature at which the stage turns off). If 
the user presses a button, the relative value 
reappears. For example, when the user se-
lects a differential menu, i.e. STAGES 3-6DIF-
FERENTIAL, the sequence is as follows:

(i)  The current differential for stage 3 flashes 
on the display, alternating with "

3 dIF

".

3dIF

2 .0

(ii)  If, after about 6 seconds, no action is 
taken by the user, the absolute temperature 
value is displayed, alternating with "

St 3 On

". 

In this case, the absolute value is:  Set Point 
+ Bandwidth 1 + Offset 2 + Bandwidth 2 
+ Differential 3.

78.0

ST3 on

2 .0

(iii)  When the user presses on an adjustment 
button to make an adjustment to differential, 
the relative value reappears on the display.

2 .3

5.2.  Locking the Parameter 

Settings

The parameter settings can be locked to pre-
vent accidentally modifying them. When the 
settings are locked, only the temperature set 
point and the Stage 1 minimum ventilation 
speed can be modified (as long as the tem-
perature ramp and the minimum ventilation 
speed ramp are deactivated respectively).

• Set internal switch # 1 to 

ON

 

to  lock  the  parameters.  The 

"Locked  Parameter"

  status  LED 

turns on.

• Set internal switch # 1 to 

OFF

 

to  unlock  the  parameters.  The 

"Locked  Parameter"

  status  LED 

turns off.

ON

OFF

1

1

ON

OFF

31

INTER 2V4SA, rev.02

INTER 2V4SA

11. 

Alarms

The controller sets off an alarm in the case 
of a power failure, a fault in the supply circuit 
or a high or low temperature.

 

11.1.  Temperature Alarms

The diagram below explains how temperature 
alarms are detected. When the average room 
temperature  exceeds  the  high  temperature 
alarm setting (Set Point + Hi  Offset), a high 
temperature alarm sets off. When the aver-
age room temperature decreases below the 
low temperature alarm limit (Set Point - Lo 
Offset), a low temperature alarm sets off. 

The 

critical temperature 

is the  absolute maxi-

mum allowable  temperature in the room.

Temperature

Alarms

Alarm

Room T°

Time

Set 

Point

Normal temperature range (no alarm)
Alarm : temperature out of range

Hi Offset

Lo Offset

11.2.  Outside Temp. Com-

pensation on Temp. 

Alarms

In situations where the outdoor temperature 
is  high,  the  room  temperature  will  rise  as 
warm  air  enters  the  building  through  ven-
tilation  inlets.  If  the  high  set  point  is  not 
adjusted  to  take  this  into  account,  a  high 
temperature  alarm  may  be  needlessly  set 
off. To avoid this situation, the system can 
compensate for high outdoor temperatures 
when monitoring temperature alarms. When 
this  feature  is  activated  and  the  outdoor 
temperature  is  close  to  the  high  set  point, 
the room temperature is monitored with re-
spect to the outdoor temperature. An alarm 
sets off only if the room temperature rises 
above the outdoor temperature by a certain 
value called the offset. In addition to this, the 
system also uses a critical high temperature 
as  an  absolute  limit  on  room  temperature.  
When room temperature reaches the critical 
high temperature, an alarm is set off.  This 
compensation  feature  is  automatically  en-
abled when an outside temperature probe is 
connected to the controller. 

Outside T° Offset:

  In general, the room tem-

perature is greater than the outdoor tempera-
ture by a certain number of degrees, called 
the offset. The offset determines when an 
alarm sets off.  It is the number of degrees the 
room temperature can rise above the outdoor 
temperature without setting off an alarm.

Содержание INTER 2V4SA

Страница 1: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Страница 2: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Страница 3: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Страница 4: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Страница 5: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Страница 6: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Страница 7: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Страница 8: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Страница 9: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Страница 10: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Страница 11: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Страница 12: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Страница 13: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Страница 14: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Страница 15: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Страница 16: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Страница 17: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Страница 18: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Страница 19: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Страница 20: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Страница 21: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Страница 22: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Страница 23: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Страница 24: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Страница 25: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Страница 26: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Страница 27: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Страница 28: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Страница 29: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Страница 30: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Страница 31: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Страница 32: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Страница 33: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Страница 34: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Страница 35: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Страница 36: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Страница 37: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Страница 38: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Страница 39: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Страница 40: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Отзывы: