•  At  Set  Point  +  Bandwidth  1  +  Stage  2 
 Bandwidth 2 + Differential 3: stage 
3 fans start running.

•  At  Set  Point  +  Bandwidth  1  +  Stage  2 
 Bandwidth 2 + Differential 3 & 4: 
stage 4 fans start.

•  At  Set  Point  +  Bandwidth  1  +  Stage  2 
 Bandwidth 2 + Differential 3, 4 & 
5: stage 5 fans start.

•  At  Set  Point  +  Bandwidth  1  +  Stage  2 
 Bandwidth 2 + Differential 3, 4 & 
5 & 6: stage 6 fans start.

If the room temp. falls:

•  At  Set  Point  +  Bandwidth  1  +  Stage  2 
 Bandwidth 2 + Differential 3, 4 & 
5: stage 6 fans return to a stop. 

•  At  Set  Point  +  Bandwidth  1  +  Stage  2 
 Bandwidth 2 + Differential 3 & 4: 
stage 5 fans return to a stop. 

•  At  Set  Point  +  Bandwidth  1  +  Stage  2 
 Bandwidth 2 + Differential 3: stage 
4 fans return to a stop. 

•  At  Set  Point  +  Bandwidth  1  +  Stage  2 
 Bandwidth 2: stage 3 fans return 
to a stop; stage 2 fans start decreasing in 
speed as the T° decreases. 

•  At  Set  Point  +  Bandwidth  1  +  Stage  2 
Offset - 0,2°C (0,4°F): Stage 2 fans return 
to a stop. 

• At Set Point + Bandwidth 1:  Stage 1 fans 
start decreasing in speed as the temperature 
decreases.

• 

At Set Point:  

Stage 1 fans reach minimum 

speed.

• 

0,2°C (0,4°F)  Below the Set Point

: Stage 1 

fans stop operating continuously and operate 
according to the minimum ventilation cycle 
at min speed.

25

INTER 2V4SA, rev.02

INTER 2V4SA

I.  Specifying Ramp Steps

Ramp steps can only be modified while the 
ramp is disabled (see section iv. to disable 
the ramp). 

• Select the 

STAGE 1 MIN SPEED / RAMP-

menu.  The  current  temperature  set  point 
flashes on the display – the value does not 
flash if the ramp is enabled.

Repeat the following steps for each ramp 
step (steps 0-9).

•  Press  the  Other  Functions  button.  The 
day number of the first ramp step (step 0) 
is displayed "

d0 x

" ("x" is the day number). 

• Use the adjustment buttons to set the day 
number of the first ramp step.

•  Press  the  Other  Functions  button  once 
again. The minimum ventilation speed associ-
ated with the first step of the ramp (step 0) is 
displayed alternating with letters 

"P0 x"

("x" 

represents the speed). Adjust the minimum 
speed with the adjustment buttons

• Press the Other Functions button again to 
select the following ramp step. 

• Proceed in similar fashion to set all ramp 
steps and then, enable the ramp as explained 
below.

II.  Activating  the  Min.  Ventilation 

Speed Ramp

• If you have just finished specifying ramp 
steps,  press  the  Other  Functions  button 
once  again.  The  word 

OFF 

flashes  on  the 

display.

•  Press  the  up-arrow  adjustment  button.  
The word 

ON 

flashes on the display and the 

Minimum Speed Ramp Status LED flashes, 
indicating that the minimum speed ramp is 
now activated.

or

• If you have previously defined ramp steps, 
select the 

STAGE 1 MIN SPEED/RAMP menu

 

and then press the Other Functions button 
to scroll down all ramp steps, until the word 

OFF 

appears (twenty-one clicks).

•  Press  the  up-arrow  adjustment  button.  
The  word 

ON 

flashes  on  the  display  and 

the  Min  Speed  Ramp  status  LED  flashes, 
indicating that the minimum speed ramp is 
now activated.

III.  Adjusting the Day Number

The  day  number  can  be  adjusted  in  order 
to move forward or backward on the ramps 
(temperature and min. ventilation ramp).

• Select the 

CURRENT RAMPING DAY

 menu. 

The current day number is displayed, alternat-
ing with the letters "

day

". 

• Use the adjustment buttons to set it to the 
desired value.

IV.  Deactivating the Minimum Ven-

tilation Speed Ramp

•  Select  the 

STAGE  1  MIN  SPEED/RAMP 

menu  and  then  press  the  Other  Functions 
button to scroll down all ramp steps, until the 
word 

ON 

appears (twenty-one clicks).

• Press the down-arrow adjustment button 
once. The word 

OFF 

flashes on the display 

and the Min Speed Ramp status LED turns 
off. 

Содержание INTER 2V4SA

Страница 1: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Страница 2: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Страница 3: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Страница 4: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Страница 5: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Страница 6: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Страница 7: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Страница 8: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Страница 9: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Страница 10: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Страница 11: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Страница 12: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Страница 13: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Страница 14: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Страница 15: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Страница 16: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Страница 17: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Страница 18: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Страница 19: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Страница 20: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Страница 21: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Страница 22: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Страница 23: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Страница 24: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Страница 25: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Страница 26: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Страница 27: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Страница 28: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Страница 29: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Страница 30: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Страница 31: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Страница 32: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Страница 33: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Страница 34: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Страница 35: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Страница 36: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Страница 37: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Страница 38: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Страница 39: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Страница 40: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Отзывы: