Airstream INTER 2V4SA Скачать руководство пользователя страница 21

20

INTER 2V4SA, rev.02

INTER 2V4SA

7.2.  Fan Stage Settings

Refer to previous section of this manual to 
get  more  information  about  the  following 
parameters. 

I.  Adjusting  Stage  1-2  Minimum 

Speed

The minimum speed can be adjusted between 
10 and 100%.

• Select 

STAGE 1 MIN SPEED/RAMP 

menu

 

to 

set the minimum speed of stage 1 or select 

STAGE  2  MIN  SPEED 

to  set  the  minimum 

speed  of  stage  2.  The  minimum  speed  of 
the  selected  stage  flashes  on  the  display, 
alternating with the letters 

"SPEEd"

.

•  Use  the  adjustment  buttons  to  set  the 
minimum speed of the selected stage to the 
desired value. 

 

Note that the minimum speed of stage 1 
can only be modified if the speed ramp 
is disabled (see section 8.4 on page 24).

II.  Adjusting  the  Override  Minimum 

Speed of Stage 1

The Override Minimum Speed of stage 1 is 
the  speed  reached  by  stage  1  fans  at  the 
startup  of  stage  2.  This  parameter  ranges 
from 10 to 100%.

• Select the 

STAGE 1 OVERRIDE MIN.SPEED 

menu. The override speed of stage 1 flashes 
on  the  display,  alternating  with  the  letters 

"SPEEd"

.

•  Use  the  adjustment  buttons  to  set  this 
parameter to the desired value. 

III.  Adjusting Stage 1 Bandwidth 

The bandwidth of stage 1 is the temperature 
interval over which variable fans of stage 1 in-
crease or decrease in speed proportionally to 
the temperature. It can be adjusted between 
0,3°C and 10,0°C (0,5°F and 18,0°F).

• Select the 

STAGE 1 BANDWIDTH/TIMER 

menu. The bandwidth of stage 1 flashes on 
the display, alternating with letters 

"BAnd"

.

• Use the adjustment buttons to set it to the 
desired value. 

IV.  Adjusting Stage 2 Offset 

Stage 2 Offset signals the beginning of stage 
2. Stage 2 starts when the room tempera-
ture reaches: Set Point + S1 Ban 
S2 Offset. If you want stage 2 to start prior 
to  the  end  of  stage  1,  give  the  Offset  a 
negative value (see previous graph). Stage 2 
Offset ranges from negative S1 bandwidth 
to 10,0°C (18,0°F).

• Select the 

STAGE 2 OFFSET/BANDWIDTH 

menu.  The  offset  of  stage  2  flashes  on  the 
display, alternating with the letters "

OFSET

".

• Use the adjustment buttons to set it to the 
desired value. 

V.  Adjusting Stage 2 Bandwidth 

The bandwidth of stage 2 is the temperature 
interval  over  which  stage  2  increases  or 
decreases in speed proportionally to the tem-
perature. It can be adjusted between 0,3°C 
and 10,0°C (0,5°F and 18,0°F).

• Select the 

STAGE 2 OFFSET/BANDWIDTH 

menu. 

•  Press  the  Other  Functions  button.  The 
bandwidth of stage 2 is displayed, alternating 
with the letters "

BAnd

". 

• Use the adjustment buttons to set it to the 
desired value. 

21

INTER 2V4SA, rev.02

INTER 2V4SA

VI.  Adjusting Stages 3-6 Differentials

Differentials tell the controller when to start 
stages 3-6. If the controller does not use a 
fix hysteresis to stop these stages, it then 
uses differential values to stop them when 
the remperature decreases (Refer to the "Fan 
Stage" graph). Differentials can be adjusted 
from 0,3°C and 10,0°C (0,5°F and 18,0°F).

•  Select  the 

STAGES  3-6  DIFFERENTIAL 

menu. The differential of stage 3 flashes on 
the display, alternating with "

3 diF

".

• Use the adjustment buttons to set it to the 
desired value. 

• Press the Other Functions button to select 
the differential of the next fan stage. 

• Proceed in similar fashion to set the differ-
ential of stages 4 to 6 (if applicable). 

VII. Adjusting the De-icing Timer 

The de-icing cycle time is the period of time 
separating  de-icing  cycles.  It  ranges  from 
1 to 720 minutes and must be greater than 
the De-icing On Time. The de-icing On Time 
ranges from 0 to 900 seconds.

• Select the 

STAGE 2  DE-ICING

 menu . The 

de-icing cycle time is displayed, alternating 
with the letters "

CYCLE

".

• Use the adjustment buttons to set it to the 
desired value. 

• Press the Other Functions button. The de-
icing On Time is displayed, alternating with 
the letters "

t On

".

• Use the adjustment buttons to set it to the 
desired value.

Содержание INTER 2V4SA

Страница 1: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Страница 2: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Страница 3: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Страница 4: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Страница 5: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Страница 6: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Страница 7: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Страница 8: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Страница 9: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Страница 10: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Страница 11: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Страница 12: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Страница 13: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Страница 14: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Страница 15: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Страница 16: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Страница 17: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Страница 18: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Страница 19: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Страница 20: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Страница 21: ...ious graph Stage 2 Offset ranges from negative S1 bandwidth to 10 0 C 18 0 F Select the STAGE 2 OFFSET BANDWIDTH menu The offset of stage 2 flashes on the display alternating with the letters OFSET Us...

Страница 22: ...onds in increments of 15 seconds To run the fans continuously at minimum speed set the Off Time to zero and On Time to any value other than zero To stop the fans set the On Time to zero and Off Time t...

Страница 23: ...midity exceeds the humidity set point the minimum ventilation fans are operated continu ously rather than cycled RH Comp on the Min Ventilation Speed RH Level 10 RH Set Point Compensat ed speed Regula...

Страница 24: ...tion speed associated with that day Speed 10 Speed 9 Speed 8 Speed 7 Speed 6 Speed 5 Speed 4 Speed 3 Speed 2 Speed 1 Min Ventilation Ramp 1 2 3 4 5 6 7 8 10 11 12 DAYS Min Vent Speed stage 1 Notes Cer...

Страница 25: ...x x is the day number Use the adjustment buttons to set the day number of the first ramp step Press the Other Functions button once again The minimum ventilation speed associ ated with the first step...

Страница 26: ...seconds the Off Time can be adjusted from 0 to 60 minutes To disable mist cooling set the On Time to zero Select the MIST TIMER menu The current On Time for the mist cycle is displayed al ternating w...

Страница 27: ...uttons to set it to the desired value IV Deactivating the Temperature Ramp Select the SET POINT TEMP RAMP menu and then press the Other Functions button to scroll down all ramp steps until the word ON...

Страница 28: ...ion between consecutive steps of the ramp When the last step is reached the controller keeps using the tem perature set point associated to that day Temperature 90 0 87 2 84 4 81 6 78 8 76 0 73 2 70 4...

Страница 29: ...ts function independently dif ferent probes are assigned to each output Probes 1 and 2 are assigned to Heater 1 and Probes 3 and 4 are assigned to Heater 2 In dividual probes can be turned on or off u...

Страница 30: ...peratures I Viewing the Room Temperature The room temperature is the average value of all temperatures measured by activated probes in proper operating condition Select the ROOM TEMP MIN MAX menu The...

Страница 31: ...the parameters The Locked Parameter status LED turns off ON OFF 1 1 ON OFF 31 INTER 2V4SA rev 02 INTER 2V4SA 11 Alarms The controller sets off an alarm in the case of a power failure a fault in the su...

Страница 32: ...rev 02 INTER 2V4SA 4 4 Temperature Probes The controller is supplied with one tempera ture probe connected to input 1 Up to three additional probes can be connected to the controller in order to obtai...

Страница 33: ...caps located on each of the four mounting holes Mount the enclosure on the wall using four screws Be sure the electrical knockouts are at the bottom of the enclosure in order to prevent water from ent...

Страница 34: ...controller should be combined with another line N for 115V or L2 for 230V to activate the motor Also be sure the Stage 1 and 2 COMM is sup plied by line L1 The Stage s fuse is open Replace the fuse T...

Страница 35: ...RM C F SEC MIN LOCKED STAGE 1 STAGE 2 MIST FUNCTIONS ADJUSTMENTS OTHER FUNCTIONS INTER 2V4SA Main menu LED Display Status LEDs Units Adjustment but tons Menu selectors 35 INTER 2V4SA rev 02 INTER 2V4S...

Страница 36: ...ity As humidity increases the minimum speed of stage 1 fans increases proportionally to compensate for the change Full speed fan start up In order to overcome the inertia of the ven tilation system co...

Страница 37: ...ithout having to enter the building Minimum ventilation cycles When ventilation is not required for cooling the first stage fans can be operated either continuously or intermittently to reduce the lev...

Страница 38: ...sfer is incorrect the letters COPY and Error will flash on screen In this case press the up or down adjustment button to exit the error menu and then refer to the table below to see possible error cau...

Страница 39: ...mory card is write protected If you want to copy the controller s configuration on the memory card make sure the switch at the bottom of the card is at the unlocked position The controller is write pr...

Страница 40: ...MOTOR TYPE STAGE 1 OVERRIDE MIN SPEED STAGE 2 MIN SPEED STAGE 2 OFFSET BANDWITH STAGE 2 DE ICING STAGE 2 MOTOR TYPE STAGE 3 6 DIFFERENTIAL MIST OFFSET DIFFERENTIAL MIST TIMER MIST RH COMPENSATION HEAT...

Отзывы: