En-5

Pipe outside

diameter [mm (in.)]

Width across flats

of Flare nut [mm]

6.35 (1/4)

17

9.52 (3/8)

22

12.70 (1/2)

26

15.88 (5/8)

29

19.05 (3/4)

36

4.3.2. Bending pipes

• The pipes are shaped by your hands or pipe bender. Be careful not to collapse them.
• Do not bend the pipes in an angle more than 90°.
•  When pipes are repeatedly bend or stretched, the material will harden, making it dif

fi

 cult 

to bend or stretch them any more. Do not bend or stretch the pipes more than 3 times.

 

CAUTION

To prevent breaking of the pipe, avoid sharp bends. 

If the pipe is bent repeatedly at the same place, it will break.

4.3.3. Pipe connection

When the 

fl

 are nut is tightened properly by your hand, hold the body side coupling with a 

separate spanner, then tighten with a torque wrench.

 

CAUTION

Be sure to install the pipe against the port on the indoor unit and the outdoor unit 
correctly. If the centering is improper, the 

fl

 are nut cannot tightened smoothly. If the 

fl

 are nut is forced to turn, the threads will be damaged.

Do not remove the flare nut from the indoor unit pipe until immediately before 
connecting the connection pipe.

Do not use mineral oil on 

fl

 ared part. Prevent mineral oil from getting into the system 

as this would reduce the lifetime of the units.

Hold the torque wrench at its grip, keeping it at a right angle with the pipe, in order to 
tighten the 

fl

 are nut correctly.

Connection pipe

Torque wrench

Indoor unit pipe 
(Body side)

Tighten with 2 wrenches.

Holding wrench

Flare nut

Flare nut [mm (in.)]

Tightening torque [N·m (kgf·cm)]

6.35 (1/4) dia.

16 to 18 (160 to 180)

9.52 (3/8) dia.

32 to 42 (320 to 420)

12.70 (1/2) dia.

49 to 61 (490 to 610)

15.88 (5/8) dia.

63 to 75 (630 to 750)

19.05 (3/4) dia.

90 to 110 (900 to 1,100)

5.  FORMING THE DRAIN HOSE AND PIPE

 

CAUTION

Do not remove the flare nut from the indoor unit pipe until immediately before 
connecting the connection pipe.

To prevent breaking of the pipe, avoid sharp bends.

If the pipe is bent repeatedly at the same place, it will break.

[For 

1

 Rear piping, 

2

 Right piping and 

3

 Bottom piping]

•  Install the indoor unit piping in the direction of the wall hole and bind the drain hose and 

pipe together with vinyl tape. 

•  Install the piping so that the drain hose is at the bottom.
•  Wrap the pipes of the indoor unit that are visible from the outside with decorative tape.

Pipe (Top)

Cloth tape
  (Accessories)

2

 Right piping

3

 Bottom piping

Bind with vinyl tape

Drain hose (Bottom)

1

 Rear piping

 

CAUTION

Do not wrap the tape too tightly on drain hose. If the tape is too tight (as shown in the 
Figure below) the insulation effect will be lost and the moisture from condensation 
may accumulate.

Bad Example

 

Vinyl tape too tight

•  Perform “6. ELECTRICAL WIRING” before performing this piping.
•  Wrap the pipes of the indoor unit that are visible from the outside with cloth tape.
•  After passing the indoor piping and drain hose through the wall hole, hang the indoor 

unit on the hooks at the top of the wall hook bracket.

[For 

4

 

Left bottom piping, 

5

 Left piping and 

6

 Center piping, 

7

 

Left rear piping]

•  Preset the end of the pipe.
•  For 

6

 Center piping and, 

7

 Left rear piping route the connection pipes through the wall.

•  Bend the connection piping to a bend radius not less than 100 mm and position the piping no 

more than 35 mm from the wall. 

•  After passing the indoor unit piping and drain hose through the wall hole, hang the 

indoor unit on the hooks at the top and bottom of the wall hook bracket.

Wall 
hook 
bracket

Small piping (Liquid pipe)

Large piping  (Gas pipe)

Connection piping

Alignment marks

[

Hang the indoor unit

]

•  Hang the indoor unit from the hooks at the top of the wall hook bracket.
•  Insert the spacer, etc. between the indoor unit and the wall hook bracket and separate 

the bottom of the indoor unit from the wall.

Bottom hook

Indoor unit

Top hooks

Wall hook bracket

Indoor unit

Spacer

Width across

fl

 ats

9373370147-02_IM.indb   5

9373370147-02_IM.indb   5

1/21/2013   4:10:13 PM

1/21/2013   4:10:13 PM

Содержание ASHA18GACH

Страница 1: ...APPAREIL INT RIEUR Type montage mural UNIDAD INTERIOR Tipo montado en pared Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTE...

Страница 2: ...rvice person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 1 2 1 Precautions for using R410A refrigerant WARNING Do no...

Страница 3: ...ates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Are...

Страница 4: ...y strong so that the wall can support the weight Fig A UNIT mm UNIT centre UNIT size UNIT size hole hole hole for tapping screw 80 hole 80 hole Piping inlet Piping inlet hole hole hole hole hole hole...

Страница 5: ...flare R410A pipes the dimension A should be approximately 0 5 mm more than indicated in the table for flaring with R410A flare tools to achieve the specified flaring Use a thickness gauge to measure...

Страница 6: ...breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break For 1 Rear piping 2 Right piping and 3 Bottom piping Install the indoor unit piping in the direct...

Страница 7: ...ly making sure that there are no external forces of the cables applied to the terminal connections Improperly connected or secured cables can cause serious accidents such as overheating the terminals...

Страница 8: ...1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cabl...

Страница 9: ...ld be separate from the power cable line 6 3 3 Remote controller cable Remote controller cable modification 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remo...

Страница 10: ...d at the input device you want to connect use the Apply voltage terminal CNA01 CNA03 Input device 1 Input device 2 Input device 3 Load resistance Load resistance Load resistance 1 DC power supply 12 t...

Страница 11: ...operation 3 Connection methods Wire modification Remove insulation from wire attached to wire kit connector Remove insulation from field supplied cable Use crimp type insulated butt connector to join...

Страница 12: ...frigerant system set the address at IU AD SW as shown in the Table A 2 Refrigerant circuit address Rotary switch REF AD 1 Factory setting 0 Rotary switch REF AD 10 Factory setting 0 In the case of mul...

Страница 13: ...oling temperature setting range OFF Factory setting Standard 18 to 30 C ON Extension 18 to 32 C NOTE Please do not make a standard setup and an extension setup intermingled in remote controller group...

Страница 14: ...lamp Green FILTER indicator lamp Red TIMER indicator lamp Orange 7 4 2 Checking the function settings Press and hold the MANUAL AUTO button on the indoor unit for 3 seconds to check the function sett...

Страница 15: ...6 Center piping and 7 Left rear piping butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with vinyl tape so that there is no gap 1 Rear 2 Right and...

Страница 16: ...ge Are the wires and pipes all connected completely No operation heat or burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat...

Страница 17: ...n manual of the remote controller 2 digit numbers are corresponding to the error code in the preceding table Touch the Next Page or previous page to switch to other indoor unit information UTY RNKY UT...

Отзывы: