AirStage ASHA18GACH Скачать руководство пользователя страница 13

En-12

Setting

Setting range

Type of switch

Remote control-

ler address

0 to 15

Setting 

example 

0

RC AD

 

Example

  If 4 indoor units are connected.

Remote 
controller 

Indoor unit

Indoor unit

Indoor unit

Indoor unit

RC AD SW

0

RC AD SW

1

RC AD SW

2

RC AD SW

3

RC AD SW

0

1

2

3

4

5

6

7

Address

0

1

2

3

4

5

6

7

RC AD SW

8

9

A

B

C

D

E

F

Address

8

9

10

11

12

13

14

15

ii) 2-wire type

 

Rotary switch (RC AD SW)...Factory setting “0”

 

Since the remote controller address settings are automatically con

fi

 gured, you do not 

need to con

fi

 gure them.

 If 

con

fi

 guring manually, it is necessary to con

fi

 gure both the indoor unit and the 

remote controller. For details, please refer to the remote controller manual.

]1

7.2. Custom code setting

Selecting the custom code prevents the indoor unit mix-up. (Fig. B)
(Up to 4 codes can be set.)
Perform the setting for both the indoor unit and the remote controller.

Fig. B

Code change

Indoor unit

Remote 
controller

Confusion

A            B              C           D

A           B            C             D

• Custom code setting for indoor unit

Set the DIP switch SET 3 SW1, 2, referring to the Table B.

DIP switch “SET3”

SW

1

SW

2

SW

3

SW

4

ON

OFF

Table B

Custom code

A (Factory setting)

B

C

D

DIP switch SET 3

 SW1

OFF

ON

OFF

ON

DIP switch SET 3

 SW2

OFF

OFF

ON

ON

7.3. Switching the upper limit of cooling 

temperature

This setting can be raised the upper limit of the cooling temperature setting range.
This setting can be used when connecting to the following controllers.
•  Wired remote controller (2-wire type)
•  Central remote controller
•  Touch panel controller
•  System controller
•  Service tool
•  Web monitoring tool

DIP switch setting

Set the DIP switch SET 4  SW3 referring to the Table C.

DIP switch “SET4”

SW

1

SW

2

SW

3

SW

4

ON

OFF

Table C

DIP switch SET 4 SW3

Cooling temperature setting range

OFF (Factory setting)

Standard (18 to 30 °C)

ON

Extension (18 to 32 °C)

NOTE:

Please do not make a standard setup and an extension setup intermingled in remote 
controller group.

]1

7.4. Function setting

 

WARNING

Please make this setting after completing all construction works.

•  FUNCTION SETTING can be performed with the wired or wireless remote controller.
  (The remote controller is optional equipment)
•  Refer to the wired or wireless remote controller manual for detailed setting information. 

(Set IU AD, REF AD SW to 0)

•  Refer to “7.1. Setting the address” for indoor unit address and refrigerant circuit address 

settings.

•  Turn the power of the indoor unit ON before starting the setting.

*  Turning on the power to the indoor units initializes EEV, so make sure the piping air 

tight test and vacuuming have been conducted before turning on the power.

*  Also check again to make sure no wiring mistakes were made before turning on the 

power.

Function details

Function

Function 

number

Setting number

Default

Details

Filter 

indicator 

interval

11

00

Default

Adjust the 

fi

 lter cleaning interval noti-

fi

 cation. If the noti

fi

 cation is too early, 

change to setting 01. If the noti

fi

 cation 

is too late, change to setting 02.

01

Longer

02

Shorter

Filter indi-

cator action

13

00

Enable

Enable or disable the 

fi

 lter indicator. 

Setting 02 is for use with a central 
remote controller.

01

Disable

02

Display 
only on 

central 

remote 

controller

Horizontal 

swing 

air

fl

 ow 

direction

24

00

Default

Adjust the horizontal swing air

fl

 ow 

direction.
(For horizontal swing equipped mod-
els)

01

Left half

02 Right half

Cool air 

tempera-

ture trigger

30

00

Default

Adjust the cool air trigger tempera-
ture. To lower the trigger temperature, 
use setting 01. To raise the trigger 
temperature, use setting 02.

01 Adjust (1)

02 Adjust (2)

9373370147-02_IM.indb   12

9373370147-02_IM.indb   12

1/21/2013   4:10:22 PM

1/21/2013   4:10:22 PM

Содержание ASHA18GACH

Страница 1: ...APPAREIL INT RIEUR Type montage mural UNIDAD INTERIOR Tipo montado en pared Pour le personnel agr uniquement nicamente para personal de servicio autorizado Italiano MANUALE DI INSTALLAZIONE UNIT INTE...

Страница 2: ...rvice person nel to repairs When moving consult authorized service personnel for disconnection and installation of the unit 2 ABOUT THE UNIT 1 2 1 Precautions for using R410A refrigerant WARNING Do no...

Страница 3: ...ates substances that adversely affect the equipment such as sulfuric gas chlorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Are...

Страница 4: ...y strong so that the wall can support the weight Fig A UNIT mm UNIT centre UNIT size UNIT size hole hole hole for tapping screw 80 hole 80 hole Piping inlet Piping inlet hole hole hole hole hole hole...

Страница 5: ...flare R410A pipes the dimension A should be approximately 0 5 mm more than indicated in the table for flaring with R410A flare tools to achieve the specified flaring Use a thickness gauge to measure...

Страница 6: ...breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break For 1 Rear piping 2 Right piping and 3 Bottom piping Install the indoor unit piping in the direct...

Страница 7: ...ly making sure that there are no external forces of the cables applied to the terminal connections Improperly connected or secured cables can cause serious accidents such as overheating the terminals...

Страница 8: ...1 Use ring terminals with insulating sleeves as shown in the figure below to connect to the terminal block 2 Securely clamp the ring terminals to the cables using an appropriate tool so that the cabl...

Страница 9: ...ld be separate from the power cable line 6 3 3 Remote controller cable Remote controller cable modification 1 Use a tool to cut off the terminal on the end of the remote controller cable and then remo...

Страница 10: ...d at the input device you want to connect use the Apply voltage terminal CNA01 CNA03 Input device 1 Input device 2 Input device 3 Load resistance Load resistance Load resistance 1 DC power supply 12 t...

Страница 11: ...operation 3 Connection methods Wire modification Remove insulation from wire attached to wire kit connector Remove insulation from field supplied cable Use crimp type insulated butt connector to join...

Страница 12: ...frigerant system set the address at IU AD SW as shown in the Table A 2 Refrigerant circuit address Rotary switch REF AD 1 Factory setting 0 Rotary switch REF AD 10 Factory setting 0 In the case of mul...

Страница 13: ...oling temperature setting range OFF Factory setting Standard 18 to 30 C ON Extension 18 to 32 C NOTE Please do not make a standard setup and an extension setup intermingled in remote controller group...

Страница 14: ...lamp Green FILTER indicator lamp Red TIMER indicator lamp Orange 7 4 2 Checking the function settings Press and hold the MANUAL AUTO button on the indoor unit for 3 seconds to check the function sett...

Страница 15: ...6 Center piping and 7 Left rear piping butt the connection pipe heat insulation and indoor unit pipe heat insulation together and bind them with vinyl tape so that there is no gap 1 Rear 2 Right and...

Страница 16: ...ge Are the wires and pipes all connected completely No operation heat or burn damage Is the indoor unit earthed grounded Short circuit Is the connection cable the specified thickness No operation heat...

Страница 17: ...n manual of the remote controller 2 digit numbers are corresponding to the error code in the preceding table Touch the Next Page or previous page to switch to other indoor unit information UTY RNKY UT...

Отзывы: