3.3B.1. UNIT INSTALLATION EXAMPLE 

(Wall mounted type/Floor standing concealed type)

Connect the locally purchased duct.

(1) Inlet side
•  Connect the duct to the locally purchased inlet 

fl

 ange.

• Connect the 

fl

 ange to the body with the locally purchased tapping screws.

•  Wind the inlet 

fl

 ange connecting to the duct with the aluminum tape etc. to avoid the 

air leakage.

 

CAUTION

When the duct is connected to inlet side, remove contained 

fi

 lter and surely attach 

locally purchased 

fi

 lter at inlet opening.

(2) Outlet side
•  Connect the duct with adjusting inside of outlet 

fl

 ange.

•  Wind the outlet 

fl

 ange connecting to the duct with the aluminum tape etc. to avoid the 

air leakage.

•  Insulate the duct to avoid the dew condensation.

 

CAUTION

Check that duct work does not exceed the range of external static pressure of 
equipment.

Make sure to insulate ducts to avoid the dew condensation.

Make sure to insulate between ducts and walls if metal ducts are used.

Please explain handling and washing methods of locally purchased materials to the 
customer.

To prevent people from touching the parts inside the unit, be sure to install grilles on 
the inlet and outlet ports. The grilles must be designed in such a way that cannot be 
removed without tools.

When connecting the duct to the outlet port of the indoor unit, be sure to insulate the 
outlet port and the installation screws to prevent water from leaking around the port.

AR04/07/09/12/14/18 Model

Set the static pressure outside the unit to 90 Pa or less (the allowable range is 
between 0 and 90 Pa).

AR24 Model

Set the static pressure outside the unit to 50 Pa or less (the allowable range is 
between 0 and 50 Pa).

•  Remove the screws, and then remove cover and fan guard.
•  Install the cover with the screws as shown in the illustration below.

Model

Screw

AR04/07/09/12/14

9

AR18

11

AR24

13

Cover

Fan guard

screw

3.3B.2. INSTALL THE FILTER

• Install 

the 

fi

 lters (Accessories) to the unit.

Filter

AR04/07/09/12/14/18: 2 

fi

 lters

AR24: 3 

fi

 lters

Unit

Filter

3.3B.3. FIX THE UNIT

(1) Fixing method of the unit
•  To prevent overturning, 

fi

 x the unit to the 

fl

 oor or the wall.

•  To avoid the vibration of the unit, insert the spacer between the unit and the 

fl

 oor or the 

wall, and 

fi

 x it.

(2) Leveling
Base horizontal direction leveling on top of the unit.

Level

10 mm or less

PROHIBITED

GOOD

Level

PROHIBITED

GOOD

10 mm or less

 

CAUTION

Fasten the unit securely with Special nuts A and B.

9374342341-01_IM.indb   Sec1:6

9374342341-01_IM.indb   Sec1:6

30/01/2013   17:05:14

30/01/2013   17:05:14

Содержание ARXD04GALH

Страница 1: ...Espa ol MANUEL D INSTALLATION MANUAL DE INSTALACI N APPAREIL INT RIEUR type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Itali...

Страница 2: ...may occur After turning off the power always wait 5 minutes before touching electrical components This unit contains no user serviceable parts Always consult authorized service personnel to repairs W...

Страница 3: ...mpleted Do not discard any accessories needed for installation until the installation work has been completed Name and Shape Q ty Application Operating Manual 1 Installation Manual 1 This book Install...

Страница 4: ...sufficient strength so that it withstands against the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space...

Страница 5: ...must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installation screws to pr...

Страница 6: ...ion which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall...

Страница 7: ...sure to install grilles on the inlet and outlet ports The grilles must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be...

Страница 8: ...the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use special flare tool excl...

Страница 9: ...parts Check for proper drainage after the construction by using the visible portion of transparent drain port and the drain piping final outlet on the body CAUTION Do not apply adhesive agent on the...

Страница 10: ...ories Hard PVC side Hose band 4 mm or less 20 mm 2 Hose band 1 Drain hose Fasten the Hose band 2 at the position where horizontal against earth ground The Hose band 2 must be positioned at the right s...

Страница 11: ...insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoor unit or RB unit Erroneous wiring m...

Страница 12: ...ssion Transmission Power supply Breaker Power supply Remote controller Master Remote controller Slave Remote controller Breaker Breaker Indoor unit Remote control 2 2 2 3 3 3 Indoor unit Indoor unit 1...

Страница 13: ...orque M3 screw Transmission X1 X2 Remote controller Y1 Y2 Y3 0 5 to 0 6 N m 5 to 6 kgf cm CAUTION To peel the film from the lead cable use a dedicated tool that will not damage the conductor cable Whe...

Страница 14: ...he current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage t...

Страница 15: ...Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input and output cable with appropriate external dimension depending on the number of...

Страница 16: ...Set the Setting Number to 02 Refer to 7 7 Function setting for details about Function Number and Setting Number 1 6 7 IR receiver unit Optional parts For the installation method please refer to the IN...

Страница 17: ...AD SW as shown in the Table A 2 Refrigerant circuit address Rotary switch REF AD 1 Factory setting 0 Rotary switch REF AD 10 Factory setting 0 In the case of multiple refrigerant systems set REF AD S...

Страница 18: ...ing information Function Number Setting Number Setting Static Pressure 26 00 0 Pa 01 10 Pa 02 20 Pa 03 30 Pa 04 40 Pa 05 50 Pa 06 60 Pa 50 Pa 07 70 Pa 50 Pa 08 80 Pa 50 Pa 09 90 Pa 50 Pa 31 25 Pa Fact...

Страница 19: ...temperature use setting 02 01 Adjust 1 02 Adjust 2 Heat air temperature trigger 31 00 Default Adjust the heat air trigger tempera ture To lower the trigger temperature by 6 degrees C use setting 01 T...

Страница 20: ...s Touch the Error Information 2 digit numbers are corresponding to the error code in the preceding table For more information refer to the installation manual of the remote controller UTY RNKY UTY RNK...

Отзывы: