En-12

(5)  Do not tighten the terminal screws too much, otherwise, the screws may break.

(6)  See the table for the terminal screw tightening torques.

(7)  Please do not 

fi

 x 2 power supply cables with 1 screw.

 Sleeve

Strip 10 mm

Screw with 
special washer

Screw with spe-
cial washer

Ring terminal

Cable

Terminal block

Cable

Ring terminal

Ring 
terminal

 

WARNING

Use ring terminals and tighten the terminal screws to the speci

fi

 ed torques, otherwise, 

abnormal overheating may be produced and possibly cause heavy damage inside the 
unit.

Tightening torque

M4 screw 

(Power supply/L, N, GND)

1.2 to 1.8 N·m 

(12 to 18 kgf·cm)

6.3.2  Transmission and Remote controller cable

Transmission cable

25 mm

40 mm

Shielded cable (no 

fi

 lm)

Remote controller cable

20 mm

For 3-wire type

20 mm

For 2-wire type

•  Connect remote controller and transmission cables as shown in Fig. A.

Fig. A

Different diameter

Connect to 1 side

GOOD

PROHIBITED

 

WARNING

Tighten the terminal screws to the speci

fi

 ed torques, otherwise, abnormal overheating 

may be produced and possibly cause heavy damage inside the unit.

Terminal number

Tightening torque

M3 screw 

(Transmission/X1, X2) 

(Remote controller/ Y1, Y2, Y3)

0.5 to 0.6 N·m 

(5 to 6 kgf·cm)

 

CAUTION

To peel the 

fi

 lm from the lead cable, use a dedicated tool that will not damage the 

conductor cable.

When installing a screw on the terminal block, do not cut the cable by overtightening 
the screw. On the other hand, an undertightened screw can cause faulty contact, which 
will lead to a communication failure.

6.4. Connection of wiring

(1)  Remove the cover.
(2)  Connect the connection cable.

Cover

Screw

 

CAUTION

When switching the DIP switch (SW1), be sure to turn off the power supply to the 
indoor unit. Otherwise, the PC board of the indoor unit may be damaged.

GND

L, N: Power supply cable

DIP switch 

(SW1)

X1, X2: Transmission cable

Remote controller cable

Y1: Red
Y2: White
Y3: Black

Cable clamp

For 2-wire type

For 3-wire type

Connect the remote 

controller cable

Y1:Non-poler
Y2:Non-poler
Y3:Do not connect *1

Y1:Red
Y2:White
Y3:Black

Set the DIP switch 
(SW1)

2WIRE

(Factory setting)

3WIRE

*1:  If you connect the remote controller cable to the terminal 

Y3, 2-wire type remote controller does not work.

Cable tie (Medium) 
(Accessories)

Avoid covering the air 
inlet with the wiring.

Avoid touching the ceiling with the wiring

Ceiling

Power supply 
cable

Do not bind the power supply cable and other cables together.

9374342341-01_IM.indb   Sec1:12

9374342341-01_IM.indb   Sec1:12

30/01/2013   17:05:42

30/01/2013   17:05:42

Содержание ARXD04GALH

Страница 1: ...Espa ol MANUEL D INSTALLATION MANUAL DE INSTALACI N APPAREIL INT RIEUR type conduit UNIDAD INTERIOR Tipo conducto Pour le personnel agr uniquement nicamente para personal de servicio autorizado Itali...

Страница 2: ...may occur After turning off the power always wait 5 minutes before touching electrical components This unit contains no user serviceable parts Always consult authorized service personnel to repairs W...

Страница 3: ...mpleted Do not discard any accessories needed for installation until the installation work has been completed Name and Shape Q ty Application Operating Manual 1 Installation Manual 1 This book Install...

Страница 4: ...sufficient strength so that it withstands against the weight of the indoor unit 2 The inlet and outlet ports should not be obstructed the air should be able to blow all over the room 3 Leave the space...

Страница 5: ...must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be sure to insulate the outlet port and the installation screws to pr...

Страница 6: ...ion which can withstand a load do at least 5 times the weight of the main unit and which will not amplify sound or vibration If the installation location is not strong enough the indoor unit may fall...

Страница 7: ...sure to install grilles on the inlet and outlet ports The grilles must be designed in such a way that cannot be removed without tools When connecting the duct to the outlet port of the indoor unit be...

Страница 8: ...the flare nuts could break after a prolonged period causing refrigerant to leak and generate hazardous gas if the refrigerant comes into contact with a flame 4 3 1 Flaring Use special flare tool excl...

Страница 9: ...parts Check for proper drainage after the construction by using the visible portion of transparent drain port and the drain piping final outlet on the body CAUTION Do not apply adhesive agent on the...

Страница 10: ...ories Hard PVC side Hose band 4 mm or less 20 mm 2 Hose band 1 Drain hose Fasten the Hose band 2 at the position where horizontal against earth ground The Hose band 2 must be positioned at the right s...

Страница 11: ...insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoor unit or RB unit Erroneous wiring m...

Страница 12: ...ssion Transmission Power supply Breaker Power supply Remote controller Master Remote controller Slave Remote controller Breaker Breaker Indoor unit Remote control 2 2 2 3 3 3 Indoor unit Indoor unit 1...

Страница 13: ...orque M3 screw Transmission X1 X2 Remote controller Y1 Y2 Y3 0 5 to 0 6 N m 5 to 6 kgf cm CAUTION To peel the film from the lead cable use a dedicated tool that will not damage the conductor cable Whe...

Страница 14: ...he current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage t...

Страница 15: ...Normal 2 External output A twisted pair cable 22AWG should be used Maximum length of cable is 25m Use an external input and output cable with appropriate external dimension depending on the number of...

Страница 16: ...Set the Setting Number to 02 Refer to 7 7 Function setting for details about Function Number and Setting Number 1 6 7 IR receiver unit Optional parts For the installation method please refer to the IN...

Страница 17: ...AD SW as shown in the Table A 2 Refrigerant circuit address Rotary switch REF AD 1 Factory setting 0 Rotary switch REF AD 10 Factory setting 0 In the case of multiple refrigerant systems set REF AD S...

Страница 18: ...ing information Function Number Setting Number Setting Static Pressure 26 00 0 Pa 01 10 Pa 02 20 Pa 03 30 Pa 04 40 Pa 05 50 Pa 06 60 Pa 50 Pa 07 70 Pa 50 Pa 08 80 Pa 50 Pa 09 90 Pa 50 Pa 31 25 Pa Fact...

Страница 19: ...temperature use setting 02 01 Adjust 1 02 Adjust 2 Heat air temperature trigger 31 00 Default Adjust the heat air trigger tempera ture To lower the trigger temperature by 6 degrees C use setting 01 T...

Страница 20: ...s Touch the Error Information 2 digit numbers are corresponding to the error code in the preceding table For more information refer to the installation manual of the remote controller UTY RNKY UTY RNK...

Отзывы: