11
Technical data
PRESSURE DEW POINT MONITORING DEVICE TPK 20
Measuring range
-20 ... +40 °C tpd
Sensor element
Capacitive Polymer sensor
Application temperature
-10 ... +50 °C
Accuracy
(at 23 °C)
≤
±1 K (tpd -10.0 ... +40.0 °C)
≤
±2 K (tpd -20.0 ... -10.0 °C)
≤
±3 K (tpd -30.0 ... -20.0 °C)
Operating pressure
0 Pa ... 1.7 MPa (17 bar)
Media compatibility
Clean, oil free compressed air
(filtered and dried, ISO 8573-Class 2-4-2)
Display
Red LED-Display, 14 mm
Measured value
4-digits with units °C / °F, Resolution 0.1 °C tpd
Operation
4 Keys (Soft touch keyboard)
Functions
2 adjustable alarm-limits with Hysteresis, display switchable
between °C or °F
Relay output
2 potential isolated Normally open 36 V DC, 24 V AC, max. 2 A
surge suppression with Varistor 39 V
Analog output
4 ... 20 mA / -20 ... +40 °C tpd
Serial interface
RS232 / RS485, 4800 Bd, 8N1
Ext. Signal generator
15 V / 50 mA
Electrical connection
15-pin SUB-D socket
Sensor protection filter
Stainless steel sinter filter 40
µ
m
Measuring chamber
Attached, with diverting throttle, pre-adjusted at 60 Nl / h
Compressed air connection
3/8“ internal threads
Power supply
24 V DC, max. 300 mA, reverse polarity protected, DC-plug 2.1
mm
Plug-in power supply unit
90 - 240 V / 7 VA max., output voltage 24 V DC
EMV Noise emission
EN 61000-6-3:2001
EMV Noise immunity
EN 61000-6-2:2001
Housing
Electronics:Plastic, IP 20
Measuring chamber: Aluminium
Guarantee
24 Months
Scope of supply
Instrument with attached measuring chamber/Diverting throttle,
plug connection NW 7.2 mm, plug-in power supply unit, Operating
manual, Test certificate
Rights reserved for change in technical data due to technological advancements!