Page 24
1-stage Wiring: Single stage
operation can still be achieved by wiring only W1
from the thermostat to W1 of the DCC7235 for
LOW
airflow, or W2 from the
thermostat to W2 of the DCC7235 for
HIGH
airflow. W1 and W2 can also be
connected (jumpered) for HIGH Airflow in 1-stage systems.
For convenience, when a single stage system is applied, an on-board
SHUNT
connects
Y1
to
Y2
for operation at the
Y2
airflow whenever any Y is active.
NOTE: THE SHUNT MUST BE REMOVED WHEN A TWO STAGE COMPRESSOR SYSTEM IS
APPLIED FOR HEATING OR COOLING.
2.
OPERATING with a HEAT PUMP ("Y" MUST BE Active for COMPRESSOR
Heating)
D & W1 active
: When "1&2-Stg HT" and
D
AND
W1
are active, the selected
output PWM % shown under
W1
in the selected TABLE A and B, above, occurs
after a 15 sec delay after any
W
first becomes active. A prior flow value (PWM%)
selected by either
Y
will be replaced by the value selected by either
W
.
D & W2 active
: When "1&2-Stg HT" and
D
AND
W2
are active, the selected
output PWM % shown under
W2
in the selected TABLE A and B occurs after a
15 sec time delay after the first occurrence of
W1
or
W2
. A prior flow value
(PWM%) selected by either
Y
will be replaced by the value selected by either
W
.
NOTE: WHEN EITHER OR BOTH W1 AND W2 ARE ACTIVE AND D IS NOT ACTIVE, THE OUTPUT
WILL BE PER THE COLUMN (W1 OR W2) & NOT D IN TABLES A AND B.
2.
“TIMED 2-STAGE HEAT” SWITCH (SW1-1) "ON"
1st stage -- D & W1 or D & W2 active
: When the switch is in this position and either
W1 &
D
or
W2 & D
are active, the volume command (PWM %) shown under
D & W1
in the
selected TABLE A or B occurs after a 15 sec time delay from when W1 or W2 became
active.
TIMED STAGING
: When either
D & W1
or
D & W2
remain active for 5 minutes, the
volume command (PWM %) transitions to the selected values shown under
D & W2
in the
selected TABLE A or B, above, to give the high volume output.
When W1 or W2 is active and D is NOT active, the Output will be per the column
(W1
or W2) & NOT D
in Tables A and B.
TIMED STAGING WIRING
: Either an energized W1 or W2 alone, or W1 and W2 together
(for example, by connecting them together with an external shunt) will activate the timed 2-
stage output
.
NOTE: POWER TO THE CONTROLLER MUST BE CYCLED FOR THE 1&2-STG HT AND TIMED 2-
STG HT SWITCH STATE TO BE RECOGNIZED. THE SELECTED STATE WILL BECOME
EFFECTIVE AFTER POWER IS RESTORED.
C.
PUMP TIMER RELAY ON-OFF (ENABLE/DISABLE)
a.
“PUMP TMR ON”:
The Pump RELAY Timer functions normally and will activate per
paragraph
B. a.,
above.
b.
“PUMP TMR OFF”:
The Pump RELAY Timer is disabled and will not activate.
D.
NORMAL &TEST MODE TIMING (SW3-2 "TEST"):
NOTE: THIS SWITCH SELECTS NORMAL OPERATION OR THE TEST MODE
Содержание MaxAir 100 LV
Страница 31: ...Page 31 WIRING DIAGRAM STANDARD UNITS...
Страница 32: ...Page 32 WIRING DIAGRAM MAXe UNITS...
Страница 33: ...Page 33 FAN COIL DIMENSIONS AND RETURN AIR SIZE LOCATION...
Страница 34: ...Page 34...
Страница 35: ...Page 35...
Страница 36: ...Page 36...
Страница 41: ...Page 41 2 AND 2 5 TON EVAPORATOR COIL SIZES 70 IPCE 24 30A...
Страница 42: ...Page 42 SAMPLE PIPING SCHEMATICS...
Страница 43: ...Page 43...
Страница 44: ...Page 44...
Страница 45: ...Page 45...