Page 22
TABLE A (SW2-
1) SWITCH “OFF” POSITION:
TABLE B (SW2-
1) SWITCH “ON” POSITION:
NOTE: TABLE A OR B AND SELECTIONS WITHIN TABLES A AND B BECOME EFFECTIVE
WITHOUT CYCLING 24VAC POWER 2 TO 4 SECONDS AFTER CHANGING SWITCH POSITIONS.
2.
SW3-
1 IN “0-10V IN” SWITCH POSITION:
Selects
CONTINUOUSLY VARIABLE
outputs per table 3, below and the command (volume) level is input via the “0-10V IN”
connector:
SET MAX
AIRFLOW
SEL 1&2
"L1,L2" SELECTIONS WITH DISCRETE INPUT TABLE A SELECTED
G
(ONLY)
Y2 &
G & /O
Y1 &
G & /O
Y2 &
G & O
Y1 &
G & O
W1 &
D
W2 &
D
(W1 or
W2) & /D
L1, L2=0
20%
100%
60%
100%
60%
50%
100%
20%
L1=1,L2=0
20%
100%
60%
100%
60%
35%
83%
20%
L1=0,L2=1
20%
83%
50%
83%
50%
35%
83%
20%
L1,L2=
1
20%
83%
50%
83%
50%
25%
50%
20%
SET MAX
AIRFLOW
(Dip-SW2)
"L1,L2" SELECTIONS WITH DISCRETE INPUT TABLE B SELECTED
G
(ONLY)
Y2 &
G &/O
Y1 &
G & /O
Y2 &
G & O
Y1 &
G & O
W1 &
D
W2 &
D
(W1 or
W2) & /D
L1, L2=0
20%
66%
35%
66%
35%
35%
66%
20%
L1=1,L2=0
20%
50%
25%
50%
25%
25%
50%
20%
L1=0,L2=1
20%
35%
20%
35%
20%
20%
35%
20%
L1=1,L2=0
20%
25%
20%
25%
20%
20%
25%
20%
Содержание MaxAir 100 LV
Страница 31: ...Page 31 WIRING DIAGRAM STANDARD UNITS...
Страница 32: ...Page 32 WIRING DIAGRAM MAXe UNITS...
Страница 33: ...Page 33 FAN COIL DIMENSIONS AND RETURN AIR SIZE LOCATION...
Страница 34: ...Page 34...
Страница 35: ...Page 35...
Страница 36: ...Page 36...
Страница 41: ...Page 41 2 AND 2 5 TON EVAPORATOR COIL SIZES 70 IPCE 24 30A...
Страница 42: ...Page 42 SAMPLE PIPING SCHEMATICS...
Страница 43: ...Page 43...
Страница 44: ...Page 44...
Страница 45: ...Page 45...