Page 18
DCC7235 LAYOUT
FIG 1
FIG 1
1.
POWER:
24VAC (nominal) supplied by a Class II transformer between terminals "R" (“24VAC LINE”) and "C"
(“24VAC RET”). The
RED “POWER”
LED
illuminates when the control is powered.
Transformer rating: 20VA minimum
Voltage: 22.5Vac Minimum, 30Vac Maximum
Current: <100ma (All outputs and relays active)
NOTE: SUPPLY 24VAC POWER FROM THE SECONDARY OF AN NEC CLASS-2
TRANSFORMER ONLY.
2.
CONTROL SYSTEM INPUTS
a.) 0-10vdc Command
— When SW3-1 “TEST” is
ON,
a 0-10 VDC input to J2 between Vin+ and
Vin
– produces a variable PWM output of 0% through 100%.
The polarity of the input signal
must be observed
. See Figs 1 & 2:
Differential Input Voltage: 0 V to 10 VDC represents 0 to 100% PWM
Maximum Input V dc: +10.2 Vdc
Common Mode Voltage: - 0.2 V max negative, +5 V max positive
Signal (differential) Input impedance: >150K Ohm (Vin+ to Vin-)
Common mode impedance: > 150K Ohm to COM