background image

 

 

 

IO-123090-GFW-020113 

- 9 - 

©2013 AirMark 

7)  Check the pump to ensure proper operation. 

The water inlet of the unit should be hot if the 
water temperature in the water heater has 
reached the set point. If water is not being 
circulated through the coil but the pump is 
running, then open the air bleed valve in the 
unit and purge any air left in the system. 

8)  Adjust the water heater thermostat so that the 

water temperature entering the hot water coils 
is 120 – 180ºF depending on the amount of 
heat required by the structure. This is done 
with the unit energized and operating long 
enough for all temperatures to stabalize. 

 

After all connections are made, start-up and check-
up must be performed before proper evaluation of 
the entire system can be made. Make sure that 
heat anticipator is properly set as noted on 
thermostat instructions. 

 

Load requirements can vary in each residence and 
it may be necessary for the installer or homeowner 
to make slight adjustments to the heat anticipator 
setting for longer or shorter cycles. It is 
recommended to change the setting no more than 
plus or minus 0.05 amps at a time. Greater 
changes can cause the unit to rapid cycle or 
remain on excessively. To properly check the unit's 
operation, the installer should have an electrical 
current measuring device (0-10 amp Amprobe, 
Fluke), air pressure measuring device (0-1.0 in 
slope gauge), and a temperature-measuring 
device (0-200ºF thermometer). 
 
Install the Amprobe to measure blower current, the 
slope gauge to measure static air pressure at the 
units and the temperature device to measure unit 
supply and return air temperature. Before taking 
measurements, be sure that all registers, grilles 
and dampers are open or are set to their proper 
positions. Be sure that clean filters are in place. 
Temperature measuring device must be installed 
to obtain average temperature at both inlet and 
outlet. For outlet, measure temperature of each 
main trunk at a location far enough away to avoid 
heater radiation and read the average 
temperatures. Table 2 below shows the CFM that 
should be achieved at various external static 
pressures 
 

 

 

Fig.9. Schematic of hydronic unit set up 

 

 

0.10 0.20 0.30 0.40 0.50

Tap 5

900 851 800 742 682

Tap 4

652 630 591 556 530

Tap 3

500 476 452 421 400

Tap 2

900 851 800 742 682

Tap 1

400 381 360 339 312

Tap 5

1150 1087 1030 975 910

Tap 4

1080 1048 1010 960 895

Tap 3

900 862 825 796 745

Tap 2

700 663 632 600 552

Tap 1

500 473 449 421 395

AFW18-24

AFW30-36

SPEED 

TAP

MODEL

CFM V. External Static 

Pressure 

 

 

Table 2. CFM delivered at various external statics  

 

 
 
 

GFW18-24

GFW30-36

Содержание GFW SERIES

Страница 1: ..._________________________ SERIAL ____________________________________________________ INSTALLER __________________________________________________ INSTALLATION DATE ___________________________________...

Страница 2: ...dification of the unit to operate with alternative power sources Inspection On receiving the product visually inspect it for any major shipping related damages Shipping damages are the carrier s respo...

Страница 3: ...he drain access panel in the bottom of the unit if this is a bottom return application In case of a front return application the front access panel should be removed and discarded If an accessory gril...

Страница 4: ...ton is stamped on the piston body Instruction for piston change 1 Turn the 13 16 nut once to release any residual pressure in the coil 2 After ensuring that the coil is free of any residual pressure d...

Страница 5: ...ilure to eliminate gaps will impair the proper functioning of the TXV valve It is recommended that the TXV bulb be installed parallel to the ground in a horizontal plane The bulb position should be ab...

Страница 6: ...inlet side threaded male port and the outlet side female swivel nut port 6 After ensuring that the white Teflon seal is still in place inside the flowrator body screw the female swivel nut onto the f...

Страница 7: ...Note Terminals T and N located on the top right side of the board are not intended for field use and should be left un connected CAUTION The aquastat AQ jumper must be in the OFF position at all times...

Страница 8: ...9 Use flexible piping and insulate all pipes Plumbing must be in compliance with state or local codes Code CMR248 in Massachusetts The units for hydronic heat have different top and heater box config...

Страница 9: ...To properly check the unit s operation the installer should have an electrical current measuring device 0 10 amp Amprobe Fluke air pressure measuring device 0 1 0 in slope gauge and a temperature mea...

Страница 10: ...he equipment The filter s removes dust and debris from the air thus helping to keep your air conditioned space clean More important the filter keeps dust and debris from collecting on the heat transfe...

Страница 11: ...er heater BTU INPUT assumes a water heater recovery efficiency of 76 For mild climates BTU INPUT structure s heat loss x 1 51 For colder climates BTU INPUT structure s heat loss x 1 58 3 Pump Replacem...

Страница 12: ...ndler is undersized for space being heated h Water heater is undersized Note All units installed in Massachusetts are required to be in compliance with CMR 248 Massachusetts State Plumbing Code and or...

Страница 13: ...IO 123090 GFW 020113 2013 AirMark HIGH VOLTAGE disconnect all power sources prior to servicing Failure might lea d to safety hazard Wiring diagram for GFW models...

Отзывы: