background image

 

 

 

IO-123090-GFW-020113 

- 8 - 

©2013 AirMark 

The freeze protection sensor is connected to the 
FP and R terminals. These are normally open and 
will close when the sensor sees 40ºF. The pump 
stays ON for a minimum of 30 secs.  

 

The board has a built-in timer which circulates hot 
water 6 times a day for 60 secs each time to 
prevent the coil from freezing.  

 

 

Fig.8. Micro-processor control board 

 
Start up  

Ensure that motor is pre-loaded with program from 
factory. 

 

WARNING

  The hot water (hydronic) coil and 

all water lines 

MUST

 be purged of air prior to 

starting the pump. Failure to do so could result in 
pump damage. Airmark will not be responsible for 

any property or personnel damage caused by 
failure to follow this instruction. 

 

 

WARNING

  Hot water flowing to the coil 

should be in the range of 120º - 180º F. Water at 
these temperatures can cause first-degree burns. 
Use of proper safety gear while installing or 
servicing the equipment is strongly recommended 
as is installation of a water-tempering valve (for 
water temperatures of above 140ºF) to supply 
lower temperature water to fixtures in the house. 
N170L series or equivalent should be used.  

 

Connect the hydronic coil to the water heater 
system as shown in Fig 9. Use flexible piping and 
insulate all pipes. Plumbing must be in compliance 
with state or local codes (Code CMR248 in 
Massachusetts). The units for hydronic heat have 
different top and heater box configurations. This 
configuration is not suitable for electric heat. 

DO 

NOT 

try to install hydronic heater in a unit not 

equipped for it. Verify connections: hot water to “in” 
and cold water to “out”. 7/8” ODstubs are provided 
for plumbing connections. Bleed the air flow 
system through the bleeder port or optional valve.  

 

Purging The System 

 

1)  Open air vent and allow water heater to fill with 

water. Close air vent when water heater is full 
and all air has been purged. 

2)  Ignite water heater. Set thermostat on water 

heater to 140 degrees. 

3)  Close the valve on the hot water supply from 

the   water heater ("A") and open the valve on 
the cold-water return to the water heater ("B"). 
Then open the air vent in the fan coil. Use 
bucket or hose to discard water during purging 
process at air bleed valve. Purge air 
completely from line.  

4)  Once air is purged, close return valve ("B") and 

open supply valve ("A"). Purge the coil and 
lines of air completely. 

5)  After air is purged from the system and filled 

with water, open the return valve ("B") and the 
supply valve ("A"). Then close the air vent in 
the fan coil. 

6)  Apply power to the fan coil and set the room 

thermostat on heat. Raise the temperature 
setting to activate the circulating pump 

Содержание GFW SERIES

Страница 1: ..._________________________ SERIAL ____________________________________________________ INSTALLER __________________________________________________ INSTALLATION DATE ___________________________________...

Страница 2: ...dification of the unit to operate with alternative power sources Inspection On receiving the product visually inspect it for any major shipping related damages Shipping damages are the carrier s respo...

Страница 3: ...he drain access panel in the bottom of the unit if this is a bottom return application In case of a front return application the front access panel should be removed and discarded If an accessory gril...

Страница 4: ...ton is stamped on the piston body Instruction for piston change 1 Turn the 13 16 nut once to release any residual pressure in the coil 2 After ensuring that the coil is free of any residual pressure d...

Страница 5: ...ilure to eliminate gaps will impair the proper functioning of the TXV valve It is recommended that the TXV bulb be installed parallel to the ground in a horizontal plane The bulb position should be ab...

Страница 6: ...inlet side threaded male port and the outlet side female swivel nut port 6 After ensuring that the white Teflon seal is still in place inside the flowrator body screw the female swivel nut onto the f...

Страница 7: ...Note Terminals T and N located on the top right side of the board are not intended for field use and should be left un connected CAUTION The aquastat AQ jumper must be in the OFF position at all times...

Страница 8: ...9 Use flexible piping and insulate all pipes Plumbing must be in compliance with state or local codes Code CMR248 in Massachusetts The units for hydronic heat have different top and heater box config...

Страница 9: ...To properly check the unit s operation the installer should have an electrical current measuring device 0 10 amp Amprobe Fluke air pressure measuring device 0 1 0 in slope gauge and a temperature mea...

Страница 10: ...he equipment The filter s removes dust and debris from the air thus helping to keep your air conditioned space clean More important the filter keeps dust and debris from collecting on the heat transfe...

Страница 11: ...er heater BTU INPUT assumes a water heater recovery efficiency of 76 For mild climates BTU INPUT structure s heat loss x 1 51 For colder climates BTU INPUT structure s heat loss x 1 58 3 Pump Replacem...

Страница 12: ...ndler is undersized for space being heated h Water heater is undersized Note All units installed in Massachusetts are required to be in compliance with CMR 248 Massachusetts State Plumbing Code and or...

Страница 13: ...IO 123090 GFW 020113 2013 AirMark HIGH VOLTAGE disconnect all power sources prior to servicing Failure might lea d to safety hazard Wiring diagram for GFW models...

Отзывы: