4. Operation
2. Operating procedure
CD Start the generator unit under the procedure of manual operation anq. adjust the frequency and
voltage.
®Turn the starter switch to "STOP" position and stop the engine.
@Turn the circuit breaker of output terminal
"ON'
after the generator unit stopped when you use
the circuit breaker and single phase receptacle on the control panel.
©Turn the operating selector switch to "AUTO" position on the control panel, switch "ENGINE
SPEED"switch to "HIGH" position.
@The unit will be under stand by and start once the start signal is sensed.
3. Function
4.
When start signal activates in stand-by conditions, it starts the generator engine after preheating.
When stop signal activates, it continues 70 seconds cooling down operation to stop engine and the
machine is placed again in stand-by conditions.
Voltage
Time
starting
confirmed
2seconds 2seconds
70seconds
cii
-0
�
"O "O
-0
C:
Q)
Q)
Q)
cii cii
a.
>,
C:
cu
-Bl
Q)
....
E
0
..c
Ol
E
a.
:::J
C:
C:
"iii
"'
....
u5
I
E
o,U>
"'
c:.E
.Ql .Ql
-0
Q)
.!:: 3:
cu
U)
"'
0
C:
o-
cu
cu
tJ
.C)
t,Q
Q)
:g·5
a. a.
u5
u5
Cl
0
0
t
C:
Q)
.fl
Q)
e
u5 u5
cu
w
co
cn3
w
Q
�
Starting action
Even when the engine will not start even after cranking operation for 10 seconds, stop it 8 seconds
and then try cranking operation again. In case the engine will not start even after cranking
operation is repeated three times, trouble signal goes on showing difficulty in starting.
In case that the lamp "OVERCRANK" goes on, switch off power supply once, pressing the button
"EMERGENCY STOP ". Then after releasing the button "EMERGENCY STOP", get rid of the
cause of trouble whv encine would not start.
Start signal
ON
Indication of
malfunctions
IMPORTANT
Perform periodical inspection and maintenance of the generator
•For maintenance of the generator, try operation 5 to 10 minutes once a week.