3. Operation
3-16
A170103E
Be sure to check at times to see if gauges or each component of
the machine are properly working, or if there is any air-leak,
oil-leak, water-leak or fuel-leak etc.
The table above gives standard values. They may vary slightly
depending on the operating conditions and other factors.
In single-phase load operation, check the current of U, V, and
W phase with the ammeter, by turning the current selection
switch.
When each current is unbalanced, change load connections so
that the current of U, V, and W, can be equally balanced. Also
make sure that the current of each phase does not exceed the
rated one.
※
Keep the operation log to record constant inspection of each
component, so that trouble of the machine can be easily
discovered and preventive measures can be taken.
PK0028
Do not under any circumstance, open the portions below during
operation.
Coolant drain valve
Engine oil drain valve
H990432
Never work nearby hot portions of the machine while it is running.
Do not touch hot portions of the machine while inspecting the
machine when running.
Parts such as the engine, exhaust manifold, exhaust pipe, muffler
and radiator are especially hot. Never touch those parts, because
it could cause scalding.
Coolant water and engine oil are also very hot and dangerous to
touch. Avoid checking or refilling them while the machine is
running.
When the breaker functions often during operation, reduce the load.
When using 1-phase load, check the current of each phase and try to keep the load of each phase
constantly average.
If you continue to operate the generator while ignoring or neglecting these cautions, it could cause
overheating and result in fire. Furthermore, should operation continue at a lower level than the standard
rated frequency, it could burn the generator and any motors of the attached load.