2. Transportation and Installation
2-2
2.2 Conditions of Installation
SG0110
The machine has to be installed on a dry, firm, and
level area.
The machine should be operated in the following
conditions:
Ambient temp: -5°F to 104°F (-15°C to 40°C)
Humidity: Less than 85%
Altitude: Lower than 1,000m above sea level.
※
Using the machine outside the above conditions may
cause serious failure.
If more than two units are placed parallel in
operation, keep enough distance so that exhaust air
from the one does not affect the other one.
Keep enough space around the unit for inspection
and maintenance access.
PC002
Exhaust gas from the engine is poisonous, and it could cause
casualties if inhaled.
Avoid using the machine in an insufficiently ventilated building or
a tunnel.
Do not position the exhaust gas outlet in the direction of a person
or a house.
A050506-1
In case that the unit is installed inside any tunnel, make sure to
provide fresh air and ventilate it.
In this case, make sure to extend the exhaust fume pipe
outdoors, and also make sure to prevent any leak from any
connection pipes.
1,000mm or more
1,000
mm or
mor
e
Exhaust pipe
Using Blower
○
×
1,000
mm or
mor
e
Exhausted
gas
Go
to