PART III – ALARM (Failure)
1.
Fault Info (Fault out) [FLT]
The device displays a warning in case of a malfunction in any of its components
.
The control card
decides
whether to continue operating according to the severity of the fault. Fault information is transmitted to
the user
as a fault code on the controller's display (Digital Controller, Touch Panel, etc.) and warning led in
the Basic
Controller. In addition, the device mechanically (dry contact) exports the fault information from the
"Fault out"
output.
2.
Fault Code List
S
cr
een
C
o
d
e
Description
R
eg
ist
er
Va
lu
e
B
asi
c
P
an
el
1
U
n
it
S
ta
tu
s
2
R
eset
5
F
a
n
BY
P
/
RT
R
PH
H
T / C
C
W
/
CHW
D
X
/ FW
V
---
Unit run normaly
0
---
-
-
√
√
√
√
√
ERR 1
Fire alarm[FRE]
1
0001
√
3
√
√
X
X
X
X
ERR 2
Elecrtric heater failure [HTI]
2
0010
√
-
√
√
X
X
X
ERR 3
Fresh air fan failure (FAN_OA)
3
0011
X
√
X
X
X
X
X
ERR 4
Exhaust air fan failure
(FAN_RA)
4
0100
X
√
X
X
X
X
X
ERR 5
Outdoor air temperature sensor
failure (T_OA)
5
0101
X
-
X
X
X
X
X
ERR 6
Return air temperature sensor
failure (T_RA)
6
0110
√
-
√
X
7
√
X
7
X
7
ERR 7
Panel temperature sensor
failure (T_PA)
7
0111
√
-
√
X
8
√
X
8
X
8
ERR 8
Supply air temperature sensor
failure (T_SA)
8
1000
√
-
√
X
9
√
X
9
X
ERR 9
Sensor-1 failure [SE1]
9
1001
√
4
-
√
√
√
√
√
ERR 10
Sensor-2 failure [SE2]
10
1010
√
4
-
√
√
√
√
√
ERR 11
Freon pressure failure [DXH]
[DXL]
11
1011
√
√
6
√
√
√
√
X
ERR 12
Filter dirty alarm [FIL]
12
1100
√
-
√
√
√
√
√
ERR 13
Clock malfunction
13
1101
√
-
√
√
√
√
√
ERR 14
RF communication failure
14
1110
√
-
√
√
√
√
√
ERR 15
Digital Controller
communication failure
15
1111
√
-
√
√
√
√
√
ERR 16
Constatnt flow maximum limit
failure
16
---
√
-
√
√
√
√
√
1
Basic Controller
warning led fault indicator: Led flash time 0 short, 1 long. For example: for 0010
short - short - long - short / break /
short -
short - long - short / break /…
2
Equipment to be stopped is indicated on the right columns.
3
Depending on the fire scenario
4
Fans continue to run at normal speed
5
In case of marked faults, reset is required.
6
No reset is possible in the 3rd failure, it is necessary to contact the service.
7
If the return air temperature sensor is set for room temperature measurement and the equipment is operated with this sensor
8
If the panel temperature sensor is set for room temperature measurement and the equipment is operated with this sensor
9
If the equipment is operated with this sensor