9.4. Modbus Register List
ID
Description
M
ul
ti
pl
ie
r
A
cces
U
n
it
L
im
it
D
ef
au
lt
Explanation
0
Version of program
1
r
-
-
-
Versiyon of installed program [MMYY]
1
Unit ON / Off
1
rw
-
[0,1]
0
0-Stop / 1-Start
2
Alarm Code
1
r
-
-
0
Failure code
3
Fresh air fan speed
1
r
rpm
-
-
-
4
Exhaust air fan speed
1
r
rpm
-
-
-
5
PWM value of fresh air fan
1
r
%
[0,100]
-
-
6
PWM value of exhaust air fan
1
r
%
[0,100]
-
-
20
Outdoor air temperature
0,1
r
°C
[-40,80]
-
T_OA
21
Return ait temperature
0,1
r
°C
[-40,80]
-
T_RA
22
Supply air temperature
0,1
r
°C
[-40,80]
-
T_SA
23
Panel temperature
0,1
rw
°C
[-40,80]
-
T_PA
24
1.Sensor value
0,01
r
V
-
-
Voltage value of SE1
25
2.Sensor value
0,01
r
V
-
-
Voltage value of SE2
26
RF 1.Sensor value
0,01
r
V
-
-
Voltage value of SR1
27
RF 2.Sensor value
0,01
r
V
-
-
Voltage value of SR1
29
Relative Humidity value (RH)
0,1
r
%
-
-
Processed data of the value from the sensor
30
CO
2
value
0,1
r
ppm
-
-
Processed data of the value from the sensor
31
Pressure value
0,1
r
hPa
-
-
Processed data of the value from the sensor
60
DO1 Output info [RUN]
1
r
-
[0,1]
-
0-Closed / 1-Run
61
DO2 Output info [FLT]
1
r
-
[0,1]
-
0-Closed / 1-Run
62
LP0 Output info [BYP]
1
r
-
[0,1]
-
0-Closed / 1-Run
63
LP1 Output info [HT1]
1
r
-
[0,1]
-
0-Closed / 1-Run
64
LP2 Output info [HT2]
1
r
-
[0,1]
-
0-Closed / 1-Run
65
LP3 Output info [PH1]
1
r
-
[0,1]
-
0-Closed / 1-Run
66
LP4 Output info [PH2]
1
r
-
[0,1]
-
0-Closed / 1-Run
80
DI1 Input info [BST]
1
r
-
[0,1]
-
0-Closed / 1-Run
81
DI2 Input info [BMS]
1
r
-
[0,1]
-
0-Closed / 1-Run
82
DI3 Input info [FRE]
1
r
-
[0,1]
-
0-Closed / 1-Run
83
DI4 Input info [HTI]
1
r
-
[0,1]
-
0-Closed / 1-Run
84
DI5 Input info [FIL]
1
r
-
[0,1]
-
0-Closed / 1-Run
100 Mode selection
1
rw
-
[0,1]
0
0- Standard fan speed / 1- VOD
101 Fresh air fan speed stage
1
rw
-
[0,3]
0
0-Low / 1-Mid / 2-High / 3-Stop
102 Exhaust air fan speed stage
1
rw
-
[0,3]
0
0-Low / 1-Mid / 2-High / 3-Stop
128 Set temperature
1
rw
°C
[18,28]
22
-
10. Timer Function
It is the function where the work program of the device is made weekly
for
certain
days
. 4 different operating
modes can be selected for each day of the week. The device regulates the operation according to the set
mode at the specified day and time and continues to work in this mode until the next set time.
11. Fire Scenario [FRE]
I/O
[FRE]
Default values
Fire scenario selection
1