background image

8000

10

2

2

 

 Issue 

1

  

0

8

/

20

Entro-V 

Controls

Part No: 90001

308/90001299

BASIC

 CONTROLLER

, DIGITAL CONTROLLER AND

 

OTHER

 CONTROL

 OPTIONS

User manual

Содержание 90001299

Страница 1: ...80001022 Issue 1 08 20 Entro V Controls Part No 90001308 90001299 BASIC CONTROLLER DIGITAL CONTROLLER AND OTHER CONTROL OPTIONS User manual ...

Страница 2: ...agram PWM 9 3 Controller Options 10 3 1 Basic Controller 10 3 1 1 Buttons 10 3 1 2 Leds 11 3 2 Digital Controller 12 3 2 1 Buttons 12 3 2 2 Screenshots 13 PART II WORKING SCENARIO 18 1 Fan Speed Control 18 2 Boost Function 18 3 Filter Control 18 4 By Pass Rotor Control 19 4 1 By Pass Control 19 4 2 Rotor Control 19 5 Heating Cooling Control 19 5 1 Electric Heater or Water Heater Control 19 5 2 Wat...

Страница 3: ...n 21 9 3 Modbus Function 21 9 4 Modbus Register List 23 10 Timer Function 23 11 Fire Scenario FRE 23 12 Child Proof Protection Function 24 13 Unit Status When Power On 24 PART III ALARM Failure 25 1 Fault Info Fault out FLT 25 2 Fault Code List 25 Annex A SERVICE OPERATIONS 26 1 Basic Controller 26 2 Digital Controller 26 3 Register List 28 ...

Страница 4: ...s that the ventilation units have two fans to control supply and extract fans Both fans must be controlled separately in various operating conditions For instance in some cases it may be requested to keep the ventilated environment to a positive pressure supply only or a negative pressure extraction only In this case it is required to set both fans at different speeds or one fan on and the other f...

Страница 5: ...tive 2 Fan speed control Alternative 3 Electric Preheater steps control Preheater Function Electric preheater steps control for frost protection Room Temperature Function Enables selection of return air temperature or control panel temperature as room temperature BMS Function It allows simple control of the unit from a central control system and monitoring of the situation BMS Unit can be on off v...

Страница 6: ...r duct type installation 1 3 4 Humidity CO2 Sensor This sensor is used for air humididty and amount of CO2 measurement in air It is formed by the combination of 2 sensors 1 3 2 and 1 3 3 The control card has been calibrated according to this sensor It is suitable for duct type installation 1 3 5 Pressure transmitter It is the sensor used to measure the air pressure difference It can be used for co...

Страница 7: ...User Manual 6 33 2 2 Control Board Input Output ...

Страница 8: ...User Manual 7 33 ...

Страница 9: ...User Manual 8 33 ...

Страница 10: ...User Manual 9 33 2 3 Control Board Connection Diagram PWM ...

Страница 11: ...e fan speed Press To activate boost function 2 Press To reset the unit 3 Press for 3 seconds To reset the duration of filter replacement depending on time 4 Press for 3 seconds To activate VOD mode 5 or Press for 3 seconds Child lock Press for 3 seconds 1 Cannot open or close if BMS 8 1 is active 2 Cannot change the fan speed if Boost function is active 3 Reset works if the unit is off 4 Cannot wo...

Страница 12: ...ription Unit off Fan speed is high Fan speed is mid Fan speed is low Fan speed is boost VOD mode is active Fire function is active Failure warning see Part III Led is off Led is on Blink Cable connection Cable type Flat 6x Maximum lenght 20m ...

Страница 13: ...screen If select something on screen Press To increase existing value Press To decrease existing value Press To exit existing menu Press To activate boost function 2 Press for 3 seconds To reset the unit 3 Press for 3 seconds To reset the duration of filter replacement depending on time 4 Press for 3 seconds To adjust screen brightness and contrast Press for 3 seconds Child lock Press for 3 second...

Страница 14: ...nshots 1 Screen Main Screen 4 Screen Adjust 2 Screen Timer 5 Screen Company Logo 3 Screen Information 1 Screen Symbols Main Screen 1 Screen Symbols Main Screen for DX Unit 1 2 3 6 8 11 9 12 10 7 5 4 13 Info Input 7 14 15 Info Input ...

Страница 15: ...ger Plate type By Pass Available Closed Unit Off Exchanger Plate type By Pass not available Unit Working Exchanger Plate type By Pass Available Closed Unit Working Exchanger Rotor type By Pass not available Unit Off Exchanger Plate type By Pass Available Open Unit Working Exchanger Rotor type By Pass not available Unit Working 4 Symbol Air temprerature on Panel T_PA Temperature set value when sele...

Страница 16: ...r cooling coil Status Open 10 Symbol Sensor CO2 sensor is available 1 3 3 Humidity sensor is available 1 3 2 Sensor supplied by the user 11 Symbol Timer The day of the week BMS is active 12 Symbol Fault code 13 Symbol Defrost Frost protection is active Frost protection is active for DX system 14 Symbol DX System 15 Symbol DX Coil DX system is working in cooling mode DX coil DX system is closed DX ...

Страница 17: ...mode selection 3 Field Clock selection 4 Field System time information 3 Screen Symbols Information 1 Field Temperature sensor values C 2 Field Sensor values mV 3 Field Fan speed values rpm if fan tacho connection is available 4 Field Fan speed values 1 2 3 4 Info Input 1 2 3 4 Info Input ...

Страница 18: ...the entry value should be 3 if the 1st day of the week is Sunday and today is Wednesday the entry value should be 4 4 Field Screen contrast value 5 Field Screen brightness value 1 3 2 4 5 Info Input The Digital Controller will be wired into the PCB board in the MODBUS connector as per the following wiring diagram Cable type Cat6 Maximum lenght 50m 12V blue blue white GND brown Brown white A orange...

Страница 19: ...on I O BST Control Panels Default values Boost speed value for control panel Boost duration value for control panel Boost speed value for control board Boost duration value for control board 100 15 min 80 1 min If necessary the fan speed of the device is set to the fastest position temporarily Manual By pressing the button on the panel The fans of the device operate at the highest speed boost spee...

Страница 20: ...he interior Depending on the outside temperature set temperature and indoor temperature the control card decides whether the rotor will operate or not 5 Heating Cooling Control It provides control of the additional heater and or cooler used to ensure that the fresh air supplied from the heat recovery device is in the requested parameters These heaters coolers can be controlled depending on room or...

Страница 21: ... duct it will be activated There is a fault input for the electric heater dry contact NC If this connection is made A malfunction in the electric heater will be shown on the control panel and will disable the electric heater 7 Room Temperature Function Control board it needs to measure the room temperature to operate many functions The following alternatives can be used for this measurement Altern...

Страница 22: ... bit 1 9 2 Physical Connection Communication network is showed below Control board can be connected to RS485 on which is connected more than one unit Address conflicts on this line should be removed and necessary software settings should be done for data communication If the line is too long or if any communication problem occurs 120 Ohm resistance should be added at the beginning and end of the l...

Страница 23: ...ata was written Function 03 Transfer Package Example Master Transfer Address Information Function Code Register ID Data Lenght Failure Control 0x01 0x03 0x00 0x02 0x00 0x01 0x25 0xCA Response of Control Board Address Information Function Code Register ID Data Lenght Failure Control 0x01 0x03 0x00 0x07 0xFF 0xFA 0x34 Function 03 Transfer Package Example Master Transfer Address Information Function ...

Страница 24: ...or 60 DO1 Output info RUN 1 r 0 1 0 Closed 1 Run 61 DO2 Output info FLT 1 r 0 1 0 Closed 1 Run 62 LP0 Output info BYP 1 r 0 1 0 Closed 1 Run 63 LP1 Output info HT1 1 r 0 1 0 Closed 1 Run 64 LP2 Output info HT2 1 r 0 1 0 Closed 1 Run 65 LP3 Output info PH1 1 r 0 1 0 Closed 1 Run 66 LP4 Output info PH2 1 r 0 1 0 Closed 1 Run 80 DI1 Input info BST 1 r 0 1 0 Closed 1 Run 81 DI2 Input info BMS 1 r 0 1 ...

Страница 25: ...ion Manual It is the function that prevents the control panel from being accessed especially by children When the function is activated the keys are locked and not functional Alternative 1 Manual Optionally the function can be activated and deactivated by pressing the key combination on the control panel Alternative 2 Time dependent When this function is activated The function is activated when th...

Страница 26: ...7 X7 X7 ERR 7 Panel temperature sensor failure T_PA 7 0111 X8 X8 X8 ERR 8 Supply air temperature sensor failure T_SA 8 1000 X9 X9 X ERR 9 Sensor 1 failure SE1 9 1001 4 ERR 10 Sensor 2 failure SE2 10 1010 4 ERR 11 Freon pressure failure DXH DXL 11 1011 6 X ERR 12 Filter dirty alarm FIL 12 1100 ERR 13 Clock malfunction 13 1101 ERR 14 RF communication failure 14 1110 ERR 15 Digital Controller communi...

Страница 27: ... 3 seconds BMS function on off BMS Press for 3 seconds Exit Press for 3 seconds or Wait 10 seconds LEDS Led Status Status Function H On Off By Pass function BYP M On Off Equipments function Heater preheater HTI L On Off BMS function BMS Led is off Led is on Blink 2 Digital Controller BUTTONS Service operation input Press for 3 seconds SCREENSHOTS 6 Screen Password screen 8 Screen Service screen 7 ...

Страница 28: ...act DI 4 Field Inputs selection sensor AI Inputs Code List DI Code Description Code Description Not connected HTI Heater failure info Part II 5 1 and 6 BST Boost function Part II 2 FIL Filter mechanical info Part II 3 BMS BMS unit on off BMS in Part II 8 1 DXH Freon system pressure failure info Part III FRE Fire info Part II 11 DXL Freon system pressure failure info Part III 1 4 1 3 2 Info Input I...

Страница 29: ...eater 3 stage Part II 5 1 FRZ Frost protection info Part II 6 PH1 Electric preheater 1 stage Part II 6 PH2 Electric preheater 2 stage Part II 6 8 Screen Symbol Service operation 1 Field Register number 2 Field Register value 3 Register List Modbus Service Log ID Description Multiplier Access Unit Limit Default Explanation X X 0 Version of program 1 r Versiyon of installed program MMYY X X 1 Unit O...

Страница 30: ...e value from the sensor X X 31 Pressure value 0 1 r hPa Processed data of the value from the sensor X 33 Countdown for By Pass position change 1 r s Time is expected to be 0 for By Pass position change X 35 Filtre Sensor 1 r 0 1 Indicates whether the mechanical filter sensor is connected X 36 Countdown for electric heater cooling time 1 r s Countdown starts when the algorithm is activated otherwis...

Страница 31: ...0 Closed 1 Run X 77 Tacho info for fresh air fan TI1 1 r 0 1 X 78 Tacho info for exhaust air fan TI1 1 r 0 1 X X 80 DI1 Input info BST 1 r 0 1 0 Closed 1 Run X X 81 DI2 Input info BMS 1 r 0 1 0 Closed 1 Run X X 82 DI3 Input info FRE 1 r 0 1 0 Closed 1 Run X X 83 DI4 Input info HTI 1 r 0 1 0 Closed 1 Run X X 84 DI5 Input info FIL 1 r 0 1 0 Closed 1 Run X 90 Panel Child proof protection 1 rw X 91 Ba...

Страница 32: ...re X 137 Heater status 1 rw 0 1 0 0 Passive 1 Active X 138 Prehater status 1 rw 0 1 0 0 Passive 1 Active X 139 Electric heater cooling time reference 1 rw s 20 600 30 X 140 Temperature sensor selection for eelectric heater 1 rw 0 1 0 0 Room temperature Register 130 1 Supply air temperature T_SA X 145 Frost protection status 1 rw 0 1 0 0 Passive 1 Active X 146 Frost temperature 1 rw C 10 10 0 X 147...

Страница 33: ... 1 BST 2 BMS 3 FRE 4 HTI 5 FIL 6 DXH 7 DXL X 180 BMS in status 1 rw 0 1 0 0 Passive 1 Active X 182 Fire scenario selection 1 rw 0 3 0 185 SE1 Sensor selection 1 rw 0 4 0 0 1 RH 2 CO2 3 PRE 4 SEN kullanıcı sensörü 186 SE1 Sensor selection 1 rw 0 4 0 0 1 RH 2 CO2 3 PRE 4 SEN kullanıcı sensörü X 187 SR1 RF Sensor selection 1 rw 0 2 0 0 1 RH 2 CO2 X 188 SR2 RF Sensor selection 1 rw 0 2 0 0 1 RH 2 CO2 ...

Страница 34: ......

Страница 35: ......

Страница 36: ......