Chillers
ULTIMA FREECOOL
Chillers
Installation & Maintenance Manual : 903-125 IM E 05/04/A
7
General Description
STANDARD FEATURES
Each refrigeration circuit is supplied with the following:
•
Full operating charge of R407C
•
Liquid injection oil cooling circuit fitted to each compressor as standard with filter,
sight glass, strainer and non-return valve
•
Electronic expansion valve
•
Liquid line ball valve
•
Discharge line ball valve
•
Discharge line mufflers (DSQ MODELS ONLY)
•
Large capacity filter drier with replaceable cores
•
Liquid line sight glass
•
Low pressure switch with manual reset via microprocessor controller
•
High pressure switch with manual reset
•
Suction and liquid pressure transducers
•
Dual Pressure relief valve with integral rupture disc and indicator gauge offering
easy maintenance complying with Pressure Regulations
Refrigeration
•
Valves for refrigeration head pressure control in simultaneous Free Cooling and
Mechanical cooling mode
Each water glycol circuit is supplied with the following:
•
Water Flow switch
•
3 way modulating valve to control free-cooling operation
•
Strategically placed automatic air vents
•
Strategically placed drain valves
•
Butterfly shut off valves for Free-cooling coil isolation to allow for maintenance
•
Pressure transducers across evaporator to monitor water pressure drop
Water / Glycol
•
Inlet water filter 1/16” mesh
Controls
microprocessor controlled providing 6-8 stages of mechanical cooling
(Depending on model size), modulating condenser fans and valve to offer 0-100% free-
cooling when ambients permit. The controller incorporates full Building Management
System capabilities, full details can be found in the
section.
Weatherproof electrical power and control panels are situated at the end of the unit
and contain:
•
Individual mains power compartments for each refrigeration circuit
•
Separate door locking electrical isolation for each mains compartment
•
Dedicated control panel and isolator for fans and integral pumps (when fitted)
Electrical
•
Emergency Stop fitted to controls compartment door
CAUTION
The Emergency Stop MUST NOT be used to stop the chiller other than in the event
of an emergency.
•
Separate, fully accessible, controls compartment, allowing safe adjustment of
microprocessor set points whilst the unit is operational
•
Dedicated bus-bar chamber for connection of incoming 3-phase and earth mains
power supply
•
Circuit breakers for protection of all major unit components
•
Phase Rotation Relay also incorporating loss of phase protection
The electrical power and control panel is wired to the latest European standards and
codes of practice
Mains supply is 3 phase and a neutral is not required.
Содержание UFC200D-8
Страница 1: ...INSTALLATION OPERATING MAINTENANCE MANUAL Ultima FreeCool Free Cooling Chiller 200 750 kW ...
Страница 40: ...Chillers ULTIMA FREECOOL Chillers Installation Maintenance Manual 903 125 IM E 05 04 A 39 Notes ...
Страница 43: ...ULTIMA FREECOOL Chillers Chillers 42 Installation Maintenance Manual 903 125 IM E 05 04 A Notes ...
Страница 44: ...Chillers ULTIMA FREECOOL Chillers Installation Maintenance Manual 903 125 IM E 05 04 A 43 Notes ...