ULTIMA FREECOOL
Chillers
Chillers
30
Installation & Maintenance Manual : 903-125 IM E 05/04/A
Commissioning Data
WATERSIDE PRESSURE DROPS
(20% Ethylene Glycol Concentration)
Super Quiet– DSQ Models
WATERSIDE PRESSURE DROP (kPa)
0
50
100
150
200
250
0
10
20
30
40
50
60
200-250 275 300
400
350
450-500
575 & 700
650 750
WATERFLOW (l/s)
1
For glycol solutions, please refer to