Date: 18/10/05
Airedale International Air Conditioning Ltd
Leeds Road, Rawdon, Leeds. LS19 6JY England
Tel: + 44 (0) 113 239 1000 Fax: + 44 (0) 113 250 7219
TECHNICAL
UPDATE
MANUAL AFFECTED: TECHNICAL & INSTALLATION
ULTIMA:
UCC/UCCU
30-450
UCFC/URAC/UWC75-450
UFC/USC200-750
MANUAL PART NO:
901-108 TM E 02/05/A
CHANGE:
ANTI-VIBRATION MOUNT (SPRING TYPE) SPECIFICATION &
INSTALLATION INSTRUCTIONS:
COMPONENTS:
1
Locating Screw
2
Retaining Nut & Washer
3 Levelling
Screw
4
Levelling Lock Nut
5 Retaining
Studs
6a Upper
Retaining
Nuts
6b Lower
Retaining
Nuts
7 Spring
assembly
8 Pressure
Plate
9 Top
Plate
10 Bolting-down
holes
2
1
6a
5
6b
10
9
8
7
3
4
DIMENSIONS:
A
(1)
B
C
D
E
FØ
UCC30-70
UCC75, 80, 100, 125 & 150
UCCU30-70
UCCU75, 80, 100, 125 & 150
UCFC75-150
2 SPRING
136
110
180 148 16
11
UCC110, 130, 160-450
UCCU110, 130, 160-450
UCFC160-450
UFC200-750
URAC75-450
USC200-750
UWC75-450
4 SPRING
180
130
225 186 20
16
B
A
C
D
E
F
E
(1) Unloaded
dimension
(2) Refer
to
relevant
Loose Parts Instructions
sheet for positioning of each mount.
INSTALLATION
1
Locate and secure mount using bolting down holes (10) in base plate.
2
Ensure mounts are located in line with the unit base.
3
If applicable, remove compressor enclosure covers to allow access to mount fixing holes in
the unit base.
4
Lock the upper retaining nuts (6a) to the underside of the top plate (9) before a load is
applied.
5
Remove retaining nut and washer (2), lower the unit onto the mounts and replace retaining
nut and washer.
6
Beginning with the mount with the largest deflection, adjust the height of each mount using
the levelling screw (3).
CAUTION
Mountings must be adjusted incrementally in turn. Do not fully adjust 1 mount at a time as
this may overload and damage springs.
7
When all mounts are level, lock each into place using the levelling lock nut (4).
8
Lock all retaining nuts (6a and 6b) to the extreme ends of the retaining studs (5).
CAUTION
Do not connect any services until all anti vibration mounts have been fully adjusted.
Содержание UFC200D-8
Страница 1: ...INSTALLATION OPERATING MAINTENANCE MANUAL Ultima FreeCool Free Cooling Chiller 200 750 kW ...
Страница 40: ...Chillers ULTIMA FREECOOL Chillers Installation Maintenance Manual 903 125 IM E 05 04 A 39 Notes ...
Страница 43: ...ULTIMA FREECOOL Chillers Chillers 42 Installation Maintenance Manual 903 125 IM E 05 04 A Notes ...
Страница 44: ...Chillers ULTIMA FREECOOL Chillers Installation Maintenance Manual 903 125 IM E 05 04 A 43 Notes ...