51
Technical, Installation and Maintenance Manual :6912497 V1.8.0 _08_2014
Rack Pressure Management
7KHIDQVZLOORSHUDWHWRPDLQWDLQWKH³DLURII´WHPSHUDWXUHDVORQJDVWKHSUHVVXUHUHPDLQVZLWKLQWKHQRUPDORSHUDWLQJ
range. However, if the pressure within the server space changes beyond the high or low differential set-points, the fans
prioritise pressure control to bring the server pressure back within limits, at which point normal temperature control
resumes.
The diagram shows the normal operating area between the dotted lines (B) of the low and high set-point differentials.
The red zones (A and C) indicate areas where the fans prioritise pressure control to bring it back within limits.
-100%
Fan Minimum
Speed
Low Set-point
(-40Pa)
Low Set-point
Differential
(-30Pa)
High Set-point
Differential
(0Pa)
High Set-point
(10Pa)
Fan
Speed
Fan Maximum
Speed
Temperature control is
affected as the fan speed is
increased to control pressure
0%
0%
Normal operating
range which is not
influenced by
pressure control
Temperature control is
affected as the fan speed is
reduced to control pressure
A
B
C
Содержание LogiCool OnRak
Страница 1: ...LogiCool OnRak IT Cooling Technical Installation Operational and Maintenance Manual ...
Страница 57: ...IT Cooling LogiCool OnRak IT Cooling 57 Technical Installation and Maintenance Manual 6912497 V1 8 0 _08_2014 ...
Страница 58: ...LogiCool OnRak IT Cooling 58 IT Cooling Technical Installation and Maintenance Manual 6912497 V1 8 0_08_2014 ...
Страница 59: ...IT Cooling LogiCool OnRak IT Cooling 59 Technical Installation and Maintenance Manual 6912497 V1 8 0 _08_2014 ...