![AIREDALE LogiCool OnRak Скачать руководство пользователя страница 50](http://html.mh-extra.com/html/airedale/logicool-onrak/logicool-onrak_technical-installation-operational-and-maintenance-manual_2876533050.webp)
LogiCool
OnRak
IT Cooling
50
IT Cooling
Technical, Installation and Maintenance Manual :6912497 V1.8.0_08_2014
Load Neutral Mode
:KHQRSHUDWLQJLQORDGQHXWUDOPRGHWKHXQLWHQVXUHVWKH³$LU2Q´URRPWHPSHUDWXUH
is modulated to maintain the valve
temperature setpoint. In this condition the air temperature leaving the OnRak is less than the air temperature entering the
server cabinet.
This mode of temperature control considers the impact of case heat radiation as well as the effect of other equipment on
the surrounding environment. Using the OnRak in load neutral mode reduces the cooling capacity as the OnRak tries to
maintain a room setpoint and operates in a similar manner to a CRAC unit.
Server Air Off Temperature Sensors
regulate the fan speed to maintain a
constant cabinet temperature of 40°C
Remote Room Air
Temperature
Sensor
Air Off Temperature is used
to maintain the Room Air
Temperature by modulating
the 3-way valve to adjust the
flow of water through the coil
Heat lost to air
AIR OFF
Û&
ROOM
AIR TEMP
Û&
Server
Air Off
Sensor
No. 1
Server
Air Off
Sensor
No. 2
Server
Air Off
Sensor
No. 3
Server
Air Off
Sensor
No. 4
Содержание LogiCool OnRak
Страница 1: ...LogiCool OnRak IT Cooling Technical Installation Operational and Maintenance Manual ...
Страница 57: ...IT Cooling LogiCool OnRak IT Cooling 57 Technical Installation and Maintenance Manual 6912497 V1 8 0 _08_2014 ...
Страница 58: ...LogiCool OnRak IT Cooling 58 IT Cooling Technical Installation and Maintenance Manual 6912497 V1 8 0_08_2014 ...
Страница 59: ...IT Cooling LogiCool OnRak IT Cooling 59 Technical Installation and Maintenance Manual 6912497 V1 8 0 _08_2014 ...