The SLIMLINE PERFORMER Ceiling Cassette – Ductless Mini-Split

Technical Manual : AIR 8-105.5 

 

Ceiling Cassette 

Table 6.1 – Cooling Performance – DX Cooling Only and Heat Pump Units 

 

Entering Air 

DB ºF @ 

50% RH

 

Fan Speed 

 High 

Medium 

Low 

 

TC SC TC SC TC SC 

Model 

BTU/h BTU/h BTU/h BTU/h BTU/h BTU/h 

 

72 

16500 14400 16300 13900 15800 13100 

CSD/CSH 18 

75 

17500 14900 17200 14400 16800 13500 

 

80 

19200 15600 18900 15100 18500 14200 

 

72 

20000 16800 19600 16100 19300 15600 

CSD/CSH 24 

75 

21000 17300 20600 16500 20400 16000 

 

80 

23000 18000 22600 17200 22200 16700 

 

72 

27600 25000 27000 23600 26400 22200 

CSD/CSH 30 

75 

29000 25800 27600 25000 27800 22800 

 

80 

31400 27000 31000 25400 30200 23800 

 

72 

33400 28400 33000 27600 32200 26200 

CSD/CSH 36 

75 

35000 29200 34600 28200 34000 26800 

 

80 

38200 30400 37800 29400 37000 27800 

 

72 

37800 31600 37200 30200 36800 29400 

CSD/CSH 42 

75 

39500 32400 39000 31000 38500 30000 

 

80 

42500 33400 42000 32000 41500 31000 

 
 

Table 6.2 – Heating Performance – Heat Pump Units 

 

Entering Air 

DB ºF

 

Fan Speed 

 

High Medium  Low 

Model 

TC BTU/h 

TC BTU/h 

TC BTU/h 

 

50 19100 18900 18600 

CSH 18 

60 17800 17600 17200 

 

70 16400 16200 16000 

 

50 24400 24000 23800 

CSH 24 

60 22800 22600 22200 

 

70 21400 21000 20800 

 

50 30400 30200 29800 

CSH 30 

60 29000 28800 28200 

 

70 27400 27200 26800 

 

50 35800 35600 35000 

CSH 36 

60 34200 33800 33400 

 

70 32400 32000 31600 

 

50 39500 39000 39000 

CSH 42 

60 38200 37800 37800 

 

70 37200 36800 36600 

Notes: 

1. 

TC = Total Cooling Capacity 

2. 

SC = Sensible Cooling Capacity 

3. 

Cooling capacities are based on 95/75ºF DB/WB Outdoor ambient. 

4. 

Heating capacities are based on 47/43ºF DB/WB Outdoor ambient. 

 

Содержание CCW 18

Страница 1: ...AIR 8 105 5 September 2012 The SLIMLINE PERFORMER Ceiling Cassette Ductless Mini Split Models CSD CSH and CCW T E C H N I C A L M A N U A L 3087217 ...

Страница 2: ... individual comfort Airedale Cassettes are available with electro mechanical or micro processor based controls The micro processor controller includes an infrared transmitter which enables room conditions to be maintained at a user defined set point Airedale Cassettes are also available with Carel microprocessor controls and network cards to allow units to be connected to a Building Management Sys...

Страница 3: ...headers to ensure low water pressure drops Fan All units utilizing backward curved centrifugal fans are staticly and dynamically balanced for quiet operation Fan impellers are made from either aluminum or fire retardant plastic UL94 VO for light weight and corrosion resistant operation Fans are driven by an enclosed multi speed external rotor motor allowing good heat dissipation and an increased m...

Страница 4: ...iver displays ON OFF cool or heat and timer alarm status Controls Option 3 Carel Controller The unit shall be fitted with a programmable microprocessor controller designed to operate the unit according to pre engineered control strategies The Carel controller requires a wall sensor wall stat or network interface card LonWorks Card for Carel Controller The Carel microprocessor controller shall come...

Страница 5: ...o cover the unit housing when the unit is not mounted in a drop ceiling Painted Sky White with hammertone finish Two Position Spring Return Control Valves For control of chilled water or hot water flow a three way three port diverting type valve or a two way two port control valve is supplied loose for on site installation Actuation is via a 24V signal from the unit s electrical panel On a four pi...

Страница 6: ... 32200 26200 CSD CSH 36 75 35000 29200 34600 28200 34000 26800 80 38200 30400 37800 29400 37000 27800 72 37800 31600 37200 30200 36800 29400 CSD CSH 42 75 39500 32400 39000 31000 38500 30000 80 42500 33400 42000 32000 41500 31000 Table 6 2 Heating Performance Heat Pump Units Entering Air DB ºF Fan Speed High Medium Low Model TC BTU h TC BTU h TC BTU h 50 19100 18900 18600 CSH 18 60 17800 17600 172...

Страница 7: ...ow Pr Drop TC SC Flow Pr Drop Model BTU h BTU h gpm PSI BTU h BTU h gpm PSI 72 5 236 5 156 1 1 2 4 3 999 3 999 0 8 1 5 CCW2 8 75 6 528 5 989 1 3 3 5 4 729 4 729 1 0 2 0 80 10 037 7 529 2 0 7 6 7 026 6 107 1 4 4 0 72 8 723 7 261 1 8 1 9 5 623 5 623 1 1 0 9 CCW2 12 75 10 831 8 173 2 2 2 7 7 502 6 604 1 5 1 4 80 14 435 9 644 2 9 4 6 11 236 8 200 2 3 2 9 72 13 728 12 126 2 8 1 9 9 295 9 295 1 9 0 9 CC...

Страница 8: ...CCW 33 60 51 120 5 3 3 5 70 46 555 4 9 3 0 50 62 005 6 5 4 8 CCW 36 60 56 762 5 9 4 1 70 51 600 5 4 3 5 Table 8 2 Heating Performance DX Cooling Only and Heat Pump Units with Optional Hot Water Coil Hot Water 180ºF Inlet 160ºF Outlet Entering Air Heating Capacity Flowrate Pressure Drop Model DB ºF 50 RH BTU h GPM PSI 50 46 389 4 8 1 3 CSD CSH 18 60 42 598 4 4 1 1 70 38 746 4 0 0 9 50 50 279 5 3 1 ...

Страница 9: ...H BTU h GPM PSI 50 28 389 3 0 11 0 CCW2 8 60 25 903 2 7 9 4 70 23 605 2 5 8 0 50 33 471 3 5 4 6 CCW2 12 60 30 715 3 2 4 0 70 27 995 2 9 3 4 50 60 388 6 3 5 7 CCW 18 60 55 127 5 8 4 8 70 49 706 5 2 4 0 50 65 350 6 8 6 5 CCW 20 60 59 887 6 3 5 6 70 54 118 5 7 4 7 50 99 476 10 4 10 1 CCW 33 60 91 494 9 6 8 8 70 82 986 8 7 7 4 50 114 225 11 9 13 0 CCW 36 60 105 132 11 0 11 2 70 95 896 10 0 9 5 Notes 1...

Страница 10: ... 2 3 4 10 11 16 19 9 16 19 1 2 12 9 16 1 7 16 22 15 16 7 8 22 1 2 8 13 16 11 5 16 4 11 16 3 11 16 2 5 8 O 5 3 16 6 1 2 5 1 8 3 3 4 2 1 16 2 5 8 A A VIEW A A 9 13 16 1 1 8 2 3 4 5 7 8 9 5 10 6 1 CW Inlet 2 CW Outlet 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Branch Duct Opening x3 6 Fresh Air Intake x2 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 Mounting Bracket 1 2 3 4 3...

Страница 11: ...6 31 3 8 28 9 16 12 9 16 1 13 16 4 5 8 6 8 5 8 1 5 8 5 5 16 7 3 4 2 3 4 2 3 4 4 7 8 4 15 16 32 5 16 5 3 8 3 3 16 1 5 16 3 8 13 16 8 11 16 11 13 16 3 1 8 7 13 16 2 3 4 VIEW A A A A 2 5 1 4 10 5 6 7 8 9 3 5 3 8 1 CW Coil Inlet 2 CW Coil Outlet 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh Air Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10...

Страница 12: ...1 1 2 2 5 8 28 11 16 12 9 16 28 9 16 1 7 8 43 1 2 7 8 8 13 16 19 5 8 12 7 16 6 3 8 3 5 8 3 3 8 3 6 4 5 8 7 3 16 2 3 16 4 3 4 7 9 16 9 13 16 1 5 8 4 7 8 2 3 4 2 3 4 3 1 8 9 13 16 2 3 4 5 10 2 5 4 3 1 6 7 9 8 1 CW Coil Inlet 2 CW Coil Outlet 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh Air Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 M...

Страница 13: ...3 4 1 5 8 2 3 4 4 7 8 3 7 16 A A VIEW A A 6 7 8 9 5 5 1 2 4 3 10 1 DX Suction Line 2 DX Liquid Line 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh AIr Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 Mounting Bracket 31 3 8 1 7 8 28 9 16 12 9 16 28 11 16 32 3 8 4 3 4 11 5 8 2 5 8 37 37 11 16 Figure 13 1 Dimensions Medium Chassis Model CSD ...

Страница 14: ...15 15 3 1 8 2 3 4 9 13 16 VIEW A A A A 8 13 16 2 7 8 2 7 8 4 7 8 6 5 16 4 7 16 2 7 8 3 1 2 4 7 8 6 7 16 1 2 3 4 9 7 8 6 10 5 5 43 1 2 44 7 16 1 DX Suction Line 2 DX Liquid Line 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh AIr Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 Mounting Bracket Figure 14 1 Dimensions Large Chassis Model CSD ...

Страница 15: ...n in 3 4 3 4 3 4 3 4 3 4 Liquid in 3 8 3 8 3 8 3 8 3 8 Condensate ID in 3 8 3 8 3 8 3 8 3 8 Filtration Type Wire Framed Periframe Quantity 2 2 3 3 3 Arrestance 80 80 80 80 80 Condensate Pump Maximum Head in 30 30 30 30 30 Nominal Flowrate gpm 0 1 0 1 0 1 0 1 0 1 Options Electric Heating Capacity kW 3 0 3 0 5 0 5 0 5 0 HW Heating Capacity 5 BTU h 38 746 41 993 56 609 59 600 64 268 HW Coil Connectio...

Страница 16: ...8 7 8 7 8 7 8 7 8 Chilled Water Outlet in 5 8 5 8 7 8 7 8 7 8 7 8 Condensate ID in 3 8 3 8 3 8 3 8 3 8 3 8 Filtration Type Wire Framed Periframe Quantity 1 1 2 2 3 3 Arrestance 80 80 80 80 80 80 Condensate Pump Maximum Head in 30 30 30 30 30 30 Nominal Flowrate gpm 0 1 0 1 0 1 0 1 0 1 0 1 Options Electric Heating Capacity kW 1 5 1 5 3 0 3 0 5 0 5 0 HW Heating Capacity 2 BTU h 13 799 N A 29 258 30 ...

Страница 17: ...Color Champagne Dimensions Weights Height includes Fan Guard in 28 28 28 28 30 Width in 23 23 23 29 29 Depth in 23 23 23 29 29 Weight lb 97 129 131 145 173 Compressor Type Rotary Recip Recip Recip Recip Crankcase Heater Fitted No No No No No Condenser Coil Construction Plate Fin Microchannel Plate Fin Microchannel Plate Fin Microchannel Plate Fin Microchannel Plate Fin Microchannel Connections 1 S...

Страница 18: ... Champagne Dimensions Weights Height includes Fan Guard in 28 32 36 40 40 Width in 34 34 34 34 34 Depth in 34 34 34 34 34 Weight lb 172 184 196 208 208 Compressor Type Scroll Recip Recip Recip Scroll Crankcase Heater Fitted No Yes Yes Yes No Condenser Coil Construction Round Tube Plate Fin Round Tube Plate Fin Round Tube Plate Fin Round Tube Plate Fin Round Tube Plate Fin Connections 1 Suction in ...

Страница 19: ...MCA A 1 5 2 0 2 8 Recommended Fuse A 10 10 10 1 Standard Unit fitted with optional electric heating elements Available with 230V model units only 2 Standard unit fitted with optional booster transformer for connection to a 115V electrical supply Electric heat not available in conjunction with this option Table 19 2 Electrical Data Condensers for DX Cooling Only Units Cassette Unit CSD 18 CSD 24 CS...

Страница 20: ... Minimum recommended overcurrent protection Table 20 2 Sound Data Ceiling Cassette Units MERCER TABLE Models Fan Speed SPL dBA 1 Sound Pressure Frequency Spectrum dB 1 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz High 29 37 37 33 29 21 14 10 CCW2 8 Med 26 34 34 30 24 15 12 10 Low 22 31 29 25 17 8 10 8 High 35 42 41 38 35 28 21 12 CCW2 12 Med 32 38 39 36 32 24 16 10 Low 29 37 37 33 29 21 14...

Страница 21: ... 21 1 Sound Data Condensers for DX Cooling Only and Heat Pump Units Model Units Cooling Heating YCJD18 dBA 75 YCJD24 dBA 76 YCJD30 dBA 76 YCJD36 dBA 76 YCJD42 dBA 76 YHJD18 dBA 70 1 70 9 YHJD24 dBA 75 8 75 0 YHJD30 dBA 74 7 74 8 YHJD36 dBA 76 5 76 5 YHJD42 dBA 72 0 76 0 Rated in accordance with ARI 270 95 standards ...

Страница 22: ...nly The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping The small base dimension means less space is required on the ground or roof Top Discharge The warm air from the top mounted fan is blown up and away from the structure and any landscaping This allows compact location on multi unit applications Low Operating Sound Level The upward air flow carri...

Страница 23: ...wiring connections Available in sweat connect models only The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping The small base dimension means less space is required on the ground or roof Top Discharge The warm air from the top mounted fan is blown up and away from the structure and any landscaping This allows compact location on multi unit applicatio...

Страница 24: ...it Technical Manual AIR 8 105 5 Ceiling Cassette Commercial Products Group Modine Manufacturing Company 1500 DeKoven Avenue Racine WI 53403 2552 Phone 1 866 823 1631 toll free Fax 1 800 204 6011 www airedaleusa com Modine Manufacturing Company 2012 Litho in USA ...

Отзывы: