The SLIMLINE PERFORMER Ceiling Cassette – Ductless Mini-Split

Technical Manual : AIR 8-105.5 

 

Ceiling Cassette 

General Description 

 

FACTORY INSTALLED OPTIONS  

Controls Option 1: 
Electro-Mechanical 

The unit shall be factory wired with an electo-mechanical control system that includes the necessry 
relays and safety switches for proper unit operation.  Terminal strip provide at the unit for the wiring of a 
24V wall mounted thermostat required for unit operation. 

Controls Option 2: 
Microprocessor 

A custom designed microprocessor is fitted to the Airedale Cassette to enable room conditions to be 
maintained at a user defined set point. Communication to the controller is by a hand held infrared 
transmitter or a wall mounted ‘pendant’ transmitter. Each type of transmitter includes a wall mounting 
bracket as standard. 
 

Note: 

Units with Microprocessor controls can not be connected to a BMS.  Select the Electro-Mechanical 

controls option, for field installed BMS interface, or the Carel controller version with optional 
Lonworks and BACnet network cards. 

The microprocessor allows five operating modes: fan only, dry cooling, cooling only, heating only, and 
heating/cooling with auto changeover for maximum versatility. A temperature set point between 58ºF and 
90ºF can be selected. 

The microprocessor monitors indoor coil temperature and return air temperature. The receiver contains a 
self diagnostic feature. When a low indoor coil temperature is detected the cooling action is stopped. If a 
sensor fails then an alarm is displayed on the fascia mounted receiver. The microprocessor also limits 
the number of compressor starts per hour to reduce wear on the compressor. 

The infrared/pendant transmitter is used to switch the unit ON/OFF, change temperature settings, fan 
speed, operating mode, and to toggle the motorized air sweep (where fitted). The microprocessor also 
has a built-in clock which can be activated to enable the unit to be programmed with up to two separate 
operating periods on weekdays (Mon-Fri).  
 
The clock provides ON/OFF unit operation and is 

not

 a night set back or occupied/unoccupied control 

function. Mon-Fri will operate as a ‘block’ of days and cannot be programmed independently of one 
another. Saturdays and Sundays can each be programmed with up to two separate operating periods 
and are programmed independently of the weekdays and each other.  

A fascia mounted receiver displays ON/OFF, cool or heat, and timer/alarm status. 

Controls Option 3: 
Carel Controller 

The unit shall be fitted with a programmable microprocessor controller designed to operate the unit 
according to pre-engineered control strategies.  The Carel controller requires a wall sensor, wall stat or 
network interface card. 

LonWorks Card for 
Carel Controller 

The Carel microprocessor controller shall come equipped with a plug-in card allowing for complete 
compatibility with FT-10 LonWorks control system. 

BACnet Card for Carel 
Controller 

The Carel microprocessor controller shall come equipped with a plug-in card allowing for complete 
compatibility with an MS/TP BACnet control system. 

Time Clock Card for 
Carel Controller 

A time clock (card) shall be provided for “stand-alone” units where time functions, night and weekend 
setback, etc. are not transmitted from a building management system or remote central time clock.  The 
time clock shall have a full 7 day schedule and calendar function incorporated.  The 7 day schedule shall 
have two adjustable occupied/unoccupied periods per day.  The calendar function shall allow 20 
calendar periods (start date / stop date = 1 period). 

Electric Heat 

Electric heating elements will be factory fitted to the unit. Elements are manufactured for maximum 
surface area and lower working temperature for improved reliability. Thermal cut out protection switches 
are fitted to the electric heat circuit to protect against overheating. 

Hot Water Coil 

A hot water heating coil will be factory fitted (depending on unit size) in addition to the standard DX or 
chilled water coil to provide heating. The coil is manufactured from refrigeration quality copper tubes with 
mechanically bonded aluminum fins. 

Hot Water Coil Freeze 
Protection 

The unit shall be fitted with a freeze protection sensor to prevent freezing of the hot water coil assembly.  
When the sensor detects a freeze up condition it will force the flow control valve open and prevent the 
unit fan(s) from running. 

Disconnect Switch 

The unit shall be fitted with a power disconnect switch located on the control panel, sized for the full load 
amperage of the unit to enable the unit to be disconnected from the power supply prior to any 
maintenance. 

Step Up Transformer 

The unit shall be fitted with a 115V to 230V step up transformer for 115V supply power.  Note: This 
option is not available for units with Electric Heat. 

Wall Mounted Pendant 

The unit shall include a wall mounted pendant for communication to the microprocessor controller.  The 
pendant replaces the standard infrared remote control. 

Содержание CCW 18

Страница 1: ...AIR 8 105 5 September 2012 The SLIMLINE PERFORMER Ceiling Cassette Ductless Mini Split Models CSD CSH and CCW T E C H N I C A L M A N U A L 3087217 ...

Страница 2: ... individual comfort Airedale Cassettes are available with electro mechanical or micro processor based controls The micro processor controller includes an infrared transmitter which enables room conditions to be maintained at a user defined set point Airedale Cassettes are also available with Carel microprocessor controls and network cards to allow units to be connected to a Building Management Sys...

Страница 3: ...headers to ensure low water pressure drops Fan All units utilizing backward curved centrifugal fans are staticly and dynamically balanced for quiet operation Fan impellers are made from either aluminum or fire retardant plastic UL94 VO for light weight and corrosion resistant operation Fans are driven by an enclosed multi speed external rotor motor allowing good heat dissipation and an increased m...

Страница 4: ...iver displays ON OFF cool or heat and timer alarm status Controls Option 3 Carel Controller The unit shall be fitted with a programmable microprocessor controller designed to operate the unit according to pre engineered control strategies The Carel controller requires a wall sensor wall stat or network interface card LonWorks Card for Carel Controller The Carel microprocessor controller shall come...

Страница 5: ...o cover the unit housing when the unit is not mounted in a drop ceiling Painted Sky White with hammertone finish Two Position Spring Return Control Valves For control of chilled water or hot water flow a three way three port diverting type valve or a two way two port control valve is supplied loose for on site installation Actuation is via a 24V signal from the unit s electrical panel On a four pi...

Страница 6: ... 32200 26200 CSD CSH 36 75 35000 29200 34600 28200 34000 26800 80 38200 30400 37800 29400 37000 27800 72 37800 31600 37200 30200 36800 29400 CSD CSH 42 75 39500 32400 39000 31000 38500 30000 80 42500 33400 42000 32000 41500 31000 Table 6 2 Heating Performance Heat Pump Units Entering Air DB ºF Fan Speed High Medium Low Model TC BTU h TC BTU h TC BTU h 50 19100 18900 18600 CSH 18 60 17800 17600 172...

Страница 7: ...ow Pr Drop TC SC Flow Pr Drop Model BTU h BTU h gpm PSI BTU h BTU h gpm PSI 72 5 236 5 156 1 1 2 4 3 999 3 999 0 8 1 5 CCW2 8 75 6 528 5 989 1 3 3 5 4 729 4 729 1 0 2 0 80 10 037 7 529 2 0 7 6 7 026 6 107 1 4 4 0 72 8 723 7 261 1 8 1 9 5 623 5 623 1 1 0 9 CCW2 12 75 10 831 8 173 2 2 2 7 7 502 6 604 1 5 1 4 80 14 435 9 644 2 9 4 6 11 236 8 200 2 3 2 9 72 13 728 12 126 2 8 1 9 9 295 9 295 1 9 0 9 CC...

Страница 8: ...CCW 33 60 51 120 5 3 3 5 70 46 555 4 9 3 0 50 62 005 6 5 4 8 CCW 36 60 56 762 5 9 4 1 70 51 600 5 4 3 5 Table 8 2 Heating Performance DX Cooling Only and Heat Pump Units with Optional Hot Water Coil Hot Water 180ºF Inlet 160ºF Outlet Entering Air Heating Capacity Flowrate Pressure Drop Model DB ºF 50 RH BTU h GPM PSI 50 46 389 4 8 1 3 CSD CSH 18 60 42 598 4 4 1 1 70 38 746 4 0 0 9 50 50 279 5 3 1 ...

Страница 9: ...H BTU h GPM PSI 50 28 389 3 0 11 0 CCW2 8 60 25 903 2 7 9 4 70 23 605 2 5 8 0 50 33 471 3 5 4 6 CCW2 12 60 30 715 3 2 4 0 70 27 995 2 9 3 4 50 60 388 6 3 5 7 CCW 18 60 55 127 5 8 4 8 70 49 706 5 2 4 0 50 65 350 6 8 6 5 CCW 20 60 59 887 6 3 5 6 70 54 118 5 7 4 7 50 99 476 10 4 10 1 CCW 33 60 91 494 9 6 8 8 70 82 986 8 7 7 4 50 114 225 11 9 13 0 CCW 36 60 105 132 11 0 11 2 70 95 896 10 0 9 5 Notes 1...

Страница 10: ... 2 3 4 10 11 16 19 9 16 19 1 2 12 9 16 1 7 16 22 15 16 7 8 22 1 2 8 13 16 11 5 16 4 11 16 3 11 16 2 5 8 O 5 3 16 6 1 2 5 1 8 3 3 4 2 1 16 2 5 8 A A VIEW A A 9 13 16 1 1 8 2 3 4 5 7 8 9 5 10 6 1 CW Inlet 2 CW Outlet 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Branch Duct Opening x3 6 Fresh Air Intake x2 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 Mounting Bracket 1 2 3 4 3...

Страница 11: ...6 31 3 8 28 9 16 12 9 16 1 13 16 4 5 8 6 8 5 8 1 5 8 5 5 16 7 3 4 2 3 4 2 3 4 4 7 8 4 15 16 32 5 16 5 3 8 3 3 16 1 5 16 3 8 13 16 8 11 16 11 13 16 3 1 8 7 13 16 2 3 4 VIEW A A A A 2 5 1 4 10 5 6 7 8 9 3 5 3 8 1 CW Coil Inlet 2 CW Coil Outlet 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh Air Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10...

Страница 12: ...1 1 2 2 5 8 28 11 16 12 9 16 28 9 16 1 7 8 43 1 2 7 8 8 13 16 19 5 8 12 7 16 6 3 8 3 5 8 3 3 8 3 6 4 5 8 7 3 16 2 3 16 4 3 4 7 9 16 9 13 16 1 5 8 4 7 8 2 3 4 2 3 4 3 1 8 9 13 16 2 3 4 5 10 2 5 4 3 1 6 7 9 8 1 CW Coil Inlet 2 CW Coil Outlet 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh Air Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 M...

Страница 13: ...3 4 1 5 8 2 3 4 4 7 8 3 7 16 A A VIEW A A 6 7 8 9 5 5 1 2 4 3 10 1 DX Suction Line 2 DX Liquid Line 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh AIr Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 Mounting Bracket 31 3 8 1 7 8 28 9 16 12 9 16 28 11 16 32 3 8 4 3 4 11 5 8 2 5 8 37 37 11 16 Figure 13 1 Dimensions Medium Chassis Model CSD ...

Страница 14: ...15 15 3 1 8 2 3 4 9 13 16 VIEW A A A A 8 13 16 2 7 8 2 7 8 4 7 8 6 5 16 4 7 16 2 7 8 3 1 2 4 7 8 6 7 16 1 2 3 4 9 7 8 6 10 5 5 43 1 2 44 7 16 1 DX Suction Line 2 DX Liquid Line 3 HW Coil Inlet Optional 4 HW Coil Outlet Optional 5 Fresh AIr Intake x3 6 Branch Duct Opening x4 7 Pump Inspection Port 8 Condensate Drain 9 Control Panel 10 Mounting Bracket Figure 14 1 Dimensions Large Chassis Model CSD ...

Страница 15: ...n in 3 4 3 4 3 4 3 4 3 4 Liquid in 3 8 3 8 3 8 3 8 3 8 Condensate ID in 3 8 3 8 3 8 3 8 3 8 Filtration Type Wire Framed Periframe Quantity 2 2 3 3 3 Arrestance 80 80 80 80 80 Condensate Pump Maximum Head in 30 30 30 30 30 Nominal Flowrate gpm 0 1 0 1 0 1 0 1 0 1 Options Electric Heating Capacity kW 3 0 3 0 5 0 5 0 5 0 HW Heating Capacity 5 BTU h 38 746 41 993 56 609 59 600 64 268 HW Coil Connectio...

Страница 16: ...8 7 8 7 8 7 8 7 8 Chilled Water Outlet in 5 8 5 8 7 8 7 8 7 8 7 8 Condensate ID in 3 8 3 8 3 8 3 8 3 8 3 8 Filtration Type Wire Framed Periframe Quantity 1 1 2 2 3 3 Arrestance 80 80 80 80 80 80 Condensate Pump Maximum Head in 30 30 30 30 30 30 Nominal Flowrate gpm 0 1 0 1 0 1 0 1 0 1 0 1 Options Electric Heating Capacity kW 1 5 1 5 3 0 3 0 5 0 5 0 HW Heating Capacity 2 BTU h 13 799 N A 29 258 30 ...

Страница 17: ...Color Champagne Dimensions Weights Height includes Fan Guard in 28 28 28 28 30 Width in 23 23 23 29 29 Depth in 23 23 23 29 29 Weight lb 97 129 131 145 173 Compressor Type Rotary Recip Recip Recip Recip Crankcase Heater Fitted No No No No No Condenser Coil Construction Plate Fin Microchannel Plate Fin Microchannel Plate Fin Microchannel Plate Fin Microchannel Plate Fin Microchannel Connections 1 S...

Страница 18: ... Champagne Dimensions Weights Height includes Fan Guard in 28 32 36 40 40 Width in 34 34 34 34 34 Depth in 34 34 34 34 34 Weight lb 172 184 196 208 208 Compressor Type Scroll Recip Recip Recip Scroll Crankcase Heater Fitted No Yes Yes Yes No Condenser Coil Construction Round Tube Plate Fin Round Tube Plate Fin Round Tube Plate Fin Round Tube Plate Fin Round Tube Plate Fin Connections 1 Suction in ...

Страница 19: ...MCA A 1 5 2 0 2 8 Recommended Fuse A 10 10 10 1 Standard Unit fitted with optional electric heating elements Available with 230V model units only 2 Standard unit fitted with optional booster transformer for connection to a 115V electrical supply Electric heat not available in conjunction with this option Table 19 2 Electrical Data Condensers for DX Cooling Only Units Cassette Unit CSD 18 CSD 24 CS...

Страница 20: ... Minimum recommended overcurrent protection Table 20 2 Sound Data Ceiling Cassette Units MERCER TABLE Models Fan Speed SPL dBA 1 Sound Pressure Frequency Spectrum dB 1 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz High 29 37 37 33 29 21 14 10 CCW2 8 Med 26 34 34 30 24 15 12 10 Low 22 31 29 25 17 8 10 8 High 35 42 41 38 35 28 21 12 CCW2 12 Med 32 38 39 36 32 24 16 10 Low 29 37 37 33 29 21 14...

Страница 21: ... 21 1 Sound Data Condensers for DX Cooling Only and Heat Pump Units Model Units Cooling Heating YCJD18 dBA 75 YCJD24 dBA 76 YCJD30 dBA 76 YCJD36 dBA 76 YCJD42 dBA 76 YHJD18 dBA 70 1 70 9 YHJD24 dBA 75 8 75 0 YHJD30 dBA 74 7 74 8 YHJD36 dBA 76 5 76 5 YHJD42 dBA 72 0 76 0 Rated in accordance with ARI 270 95 standards ...

Страница 22: ...nly The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping The small base dimension means less space is required on the ground or roof Top Discharge The warm air from the top mounted fan is blown up and away from the structure and any landscaping This allows compact location on multi unit applications Low Operating Sound Level The upward air flow carri...

Страница 23: ...wiring connections Available in sweat connect models only The unit contains enough refrigerant for matching indoor coils and 15 feet of interconnecting piping The small base dimension means less space is required on the ground or roof Top Discharge The warm air from the top mounted fan is blown up and away from the structure and any landscaping This allows compact location on multi unit applicatio...

Страница 24: ...it Technical Manual AIR 8 105 5 Ceiling Cassette Commercial Products Group Modine Manufacturing Company 1500 DeKoven Avenue Racine WI 53403 2552 Phone 1 866 823 1631 toll free Fax 1 800 204 6011 www airedaleusa com Modine Manufacturing Company 2012 Litho in USA ...

Отзывы: