9.4.
TOUCHSCREEN CONTROLLER INSTALLATION
Before starting the unit the controller must be wired to the unit.
To wire the controller:
1.
Grab the controller from the box.
2.
Loosen the back of the controller with the help of a
flathead screwdriver.
3.
Carefully pull the back cover of the controller.
4.
Open the back of the controller.
5.
Wire connectors
CANH
,
CANL,+12V
And
GND
terminals on the back of the controller .
6.
Wire the terminals on point 5 to connectors
27 to 30
on
control panel A as portrayed on the illustration below.
PLEASE NOTE:
Controller is supplied loose
for installation and wiring on site by others.
Cabling not included. CAT5 Unshielded
Twisted Pair cable as minimum is
recommended. Cable length should not
exceed 50 meters (0.5 mm
2
) to avoid loss of
communication.
The controller is not suitable for external
installation.
PLEASE NOTE:
When replacing the original controller the firmware must be updated to match the firmware of