Air Flow Balancing 

12

Pitot Tube Airflow Balancing 

The following is a method of field balancing an HRV/ERV using 
a Pitot tube advantageous in situations when flow stations are not 
installed in the ductwork. Procedure should be performed with the 
HRV/ERV on normal speed.

The first step is to operate all mechanical systems on most desire 
speed, which have an influence on the ventilation system, i.e.the 
forced air furnace or air handler if applicable. This will provide the 
maximum pressure that the HRV/ERV  will need to overcome, and 
allow for a more accurate balancing of the unit.

Drill a small hole in the duct (about 3/16"), three feet downstream 
of any elbows or bends, and one foot upstream of any elbows or bends. 
These are recommended distances but the actual installation may limit 
the amount of straight duct. 

The Pitot tube should be connected to a magnehelic gauge capable 
of reading from 0 to 0.25 in. (0-62 Pa) or other digital airflow meter. 
The tube coming out of the top of the pitot is connected to the 
high pressure side of the gauge/meter and the tube coming out of the 
side of the pitot is connected to the low pressure or reference side 
of the gauge/meter.

Insert the pitot tube into the duct; pointing the tip into the airflow. For general balancing it is sufficient to move the 
pitot tube around in the duct and take an average or typical reading. Repeat this procedure in the other duct. 
Determine which duct has the highest airflow (highest reading on the gauge). Then slower down that motor speed 
by adjusting dial/speed controller on control board to match the lower reading from the other duct. The flows 
should now be balanced. Actual airflow can be determined from the gauge/metre reading. The value read on the 
gauge is called the velocity pressure and on the flow meter is called air velocity(FPM). The Pitot tube comes with 
a chart that will give the air flow velocity based on the velocity pressure indicated by the gauge. This velocity will 
be in either feet per minute or metres per second. To determine the actual airflow, the velocity is multiplied by the 
cross sectional area of the duct being measured.

MAGNEHELIC

0

.1

.2

.3

.4

.5

Duct

AIR

FLOW

Pitot
tube

High
Pressure
Tap

Low
Pressure Tap

Magnehelic 

gauge

Pitot tube and gauge

NOTE:

 

Place the magnehelic gauge on a 
level surface and adjust it to zero.

Balancing Procedure

All the HRV/ERV’s components are in place and functioning properly.
All sealing of the ductwork system has been completed. 
Set the unit to normal speed. 
Air flows in branch to specific areas of the house should be adjusted first prior to balancing  the unit. 
After taking reading of both the stale air to the HRV/ERV duct and fresh air to the house duct, the duct with 
the lowerCFM reading should be left alone while the duct with the higher airflow should be slower down to 
match the lower 
reading by adjusting dial/speed controller on control board(see board layout on page-6). 
Return unit to appropriate fan speed for normal operation.

Prior to balancing, ensure that:

1.
2.
3.
4.
5.

6.

It is required to have balanced air flows in an HRV/ERV. The volume of air brought in from the outside 
must equal the volume of air exhausted by the unit while running at normal speed. If the air flows are 
not properly balanced, then:

• The HRV/ERV may not function at its maximum efficiency
• A negative or positive air pressure may occur in the house or condo
• The unit may not defrost properly

Содержание Softaire Compact RHRV-C100A

Страница 1: ...ini Series Model Polypropylene Core Enthalpy Core RHRV 120P ES Polypropylene Core RHRV 130P ES Polypropylene Core C US 2100 CERTIFIED Model RHRV C100A Aluminum Core RHRV C100P Polypropylene Core RERV...

Страница 2: ...When performing installation servicing or cleaning these unit it is suggested to wear safety glasses and gloves 9 Do not use this unit for commercial purpose 10 For residential use on ly The unit must...

Страница 3: ...s Chains Springs Brackets Drain Pipe 1 1 2 2 n a 1 n a 1 1 2 2 2 2 1 1 2 2 1 1 1 1 1 1 1 1 2 2 1 Set 1 Set 4 4 1 1 2 Sets 2 Sets 1 Set 1 Set 1 1 16 18 17 20 12 13 14 15 10 11 9 8 7 6 5 4 3 2 1 Filter...

Страница 4: ...Brackets Ladder Locks Chains Springs Brackets Drain Pipe 9315 014043C 9312 9313 9314 9326 014043 9319 9320 9321 014016 9322 9355 9328 011135 9330 9332 9354 9331 1 1 1 2 2 2 1 n a n a n a 1 n a n a n...

Страница 5: ...Chains Springs Brackets Drain Pipe 9315 014043C 9313 9314 9326 014043 9319 9320 9321 014016 9322 9355 9328 011135 9330 9332 9354 9331 1 1 2 2 1 n a n a 1 1 1 2 2 2 2 1 1 2 2 1 1 1 1 1 1 1 1 2 2 1 Set...

Страница 6: ...Mounting Brackets T Connector Webbing Brackets Ladder Locks Chains Springs Brackets Drain Pipe 1 2 1 1 2 2 1 2 1 1 1 1 2 1 Set 4 1 2 Sets 1 Set 1 16 18 17 20 12 13 14 15 10 11 9 8 7 6 5 4 3 2 1 Filte...

Страница 7: ...4 9395 2 2 2 4 Temperature Sensor 9326 1 1 1 5 6 Polypropylene Backdraft Damper PBD6 2 2 2 6 Blower Supply Exhaust 013070 2 2 2 7 Adjustable Door Latch 9319 1 1 1 8 Drain Spout Assembly 9320 2 2 2 9...

Страница 8: ...0 RED BLACK WHITE Ground 120 Vac 1 60Hz Power Supply TC100 5V Important Note When installing timers or time delay switches make sure that they are for appropriate HRV ERV models Damper Singlewinding O...

Страница 9: ...correctly RED YEL RED YEL GND C 5 DAT RED YEL GND RED YEL GND Note Same power source can be used for wall switch Time delay switch TC100 120 TC100 120P and HRV ERV TC100 120P TC100 120 RED BLACK WHIT...

Страница 10: ...ace connected to a cooling system Wiring Diagram cont d 8 Furnace Fan Coil Heat Pump Interlock Standard Interlock Wiring W R G Y W R G Y C TWO WIRE heating only Cooling System THERMOSTAT TERMINALS TWO...

Страница 11: ...in the exhaust air duct to prevent outdoor air from entering the unit when the Furnace Air handler is running and the unit is in Standby OFF or in Recirculation Note Typical Installations for House I...

Страница 12: ...re no screw will interfere the function of the backdraft damper aps while installing the duct work to the HRV ERV STRAPPING SYSTEM optional Allows one person installation for vertical and horizontal i...

Страница 13: ...LLBOX CAULK WALLBOX TO STRUCTURE ON ALL 4 SIDES Distance X Single Vents Only Metal Clamp Insulation Duct Backdraft Damper Grille Insulation Wallbox Access Door Fresh air intake and supply duct must be...

Страница 14: ...ther duct The ows should now be balanced Actual air ow can be determined from the gauge metre reading The value read on the gauge is called the velocity pressure and on the ow meter is called air velo...

Страница 15: ...vided with 3 holes on supply side and 3 holes on exhaust side Do not use pitot tube to open holes in the insulation as it may block damage the pitot tube Take 3 readings on each hole and average all 9...

Страница 16: ...120 57 0 27 67 44 20 129 61 0 36 89 64 30 0 42 104 69 33 0 48 119 77 36 0 55 136 86 41 Across 112 Model RHRV C100P Compact Di eren al Pressure the Core Supply Air Exhaust Air In W C Pa CFM L s CFM L s...

Страница 17: ...Drain Tube and Drain Pipe Inspect drain tube drain pipe and P trap for blockage mold or kinks Flush with warm soapy water and replace if worn bent or unable to clean 4 Clean Duct Work if Required Wipe...

Страница 18: ...er switch blinks Control board reports error lost communication with main control board refer to problem 4 check all wire connections on timer switch and main control board 7 LED s on the Main Control...

Страница 19: ...17 Notes...

Страница 20: ...18 4 Pine Street Toronto ON Canada M9N 2Y8 Tel 416 247 0045 Fax 416 247 2012 www ontarioheatingltd com info ontarioheatingltd com...

Отзывы: