6. Secure the NIND with four self tapping 3/4” screws being careful not to over-

tighten.

7. Secure the power adapter with included self tapping 1/2” screws.
8. Adhere the two included warning labels in close proximity to the NIND device. 

Plug the included power adapter into the nano Induct.  Connect the power adapter 

to a 110 or 240 VAC electrical outlet. The unit will start, with the green lights and 

blue lights illuminating.

It’s designed for continuous operation. For maximum effectiveness, operate the 

unit 24 hours a day, 7 days a week. 

Optional 24 VAC Internal HVAC Power Source Wiring

When  wiring  direct  to  24V  we  strongly  recommend  installing  a  separate  40  VA 

transformer to ensure optimal performance.

SAFETY CONSIDERATIONS

Read and follow manufacturer instructions carefully. Follow all local electrical codes 

during installation. All wiring, must conform to local and national electrical codes. 

Improper wiring, or installation may damage unit and/or cause serious injury.

WARNING

Before beginning any modification, be certain that the main line electrical discon-

nect switch is in the OFF position. Electric shock could result. Tag disconnect 

switch with suitable warning labels.

Installation and servicing of air-conditioning equipment can be hazardous due to 

system  pressure  and  electrical  components.  Only  trained  and  qualified  service 

personnel should install, repair, or service air-conditioning equipment. Air Oasis 

and its affiliates are not responsible for any damage to the HVAC system, NIND or 

injury to yourself or others if you elect to install the NIND without utilizing qualified 

technicians. 

WARNING

The NIND is designed to operate at 24 VAC. Damage or physical injury could result 

if wired to higher voltages.

1.  Wire electrical power plug to the 24 VAC internal  power source. Before wiring 

the NIND to the power source, check with a voltmeter that the source does not 

exceed 30 VAC.

2.  Insert the power plug into the port on the NIND.  If it is necessary to pass the 

cord through a hole in the wall of the air handler or through an access door, 

a rubber grommet should be inserted in the hole or electrical tape should be 

wrapped around the cord at the point of entry for protection.

24 VAC 

Power 

Source

Solid Black (-) Outside

White Stripe (+) Inside

Note: If one terminal of power source 

is  grounded,  hook  the  black  wire  to 

this terminal.

Initial Start Up

7

Содержание NANO INDUCT Sanifier

Страница 1: ...For use with models NIND14 NIND9 NIND6 For safety and to ensure proper use carefully read the contents of this manual before operating or installing the unit NANO INDUCT Owner s Manual...

Страница 2: ...ensure you get the most benefits from your Sanifier For additional information please contact us mail Air Oasis LLP Attn Customer Service 3401 Airway Blvd Amarillo TX 79118 web www airoasis com e mail...

Страница 3: ...port 4 F 180 F humidity 10 90 Non Condensing Do not operate unit in ambient temperatures above 150 F KEEP OUT OF REACH OF CHILDREN Only use the power adapters included with the purification system WAR...

Страница 4: ...Flashing The UVC lamp is outside its two year life span output has decreased and it should be replaced No Lights Illuminated There are two possibilities 1 The unit is not properly connected to the po...

Страница 5: ...in the closed position The shields should only be opened for specialized applications The nano Induct should not be installed in extremely close proximity to heat strips or other heat sources Polymer...

Страница 6: ...injury to yourself or others if you elect to install the device without utilizing qualified technicians Use the suggestions on page 3 to determine the optimal mounting location s To complete the insta...

Страница 7: ...help secure the unit 5 Firmly press the Ballast Assembly onto the four pins protruding from the AHPCO Cell The Ballast Assembly should be orientated with the air flow label running parallel with the l...

Страница 8: ...warning labels in close proximity to the NIND device 6 CAUTION DONOTLOOK ATUVLIGHT CAUTION WARNING Eye damage may result from directly viewing the light produced by these lamps To reduce the risk of e...

Страница 9: ...tion and servicing of air conditioning equipment can be hazardous due to system pressure and electrical components Only trained and qualified service personnel should install repair or service air con...

Страница 10: ...ll and pull the AHPCO Cell out from the Re tainer Ring Properly dispose of the AHPCO Cell 4 Insert the new AHPCO Cell and secure with four 1 4 hex head screws Do not overtighten the screws 5 Using a s...

Страница 11: ...rranty Card If you purchase this product from any source other than Air Oasis or an Air Oasis dealer your purchase is AS IS which means Air Oasis grants you no warranty and that you not Air Oasis assu...

Страница 12: ...purchase a new AHPCO Cell If the above does not repair the symptom please contact an Air Oasis Customer Service Representative Phone 1 800 936 1764 E mail feedback airoasis com Web www airoasis com M...

Отзывы: