5.14 – ENHANCED DISPLAY CONFIGURATION
Operator can select display parameter, for lines 2, 3, 4, and 5. Also, each line can have a level of filtering, 0
through 4 (4 is maximum) selected by Operator.
SECTION 5 – OPERATION
- K-Factor Configuration
Enhanced Display Config.
- Analog Output Configuration
- LINE 1
- LINE 2
- LINE 3
- LINE 4
- LINE 5
- Return to MAIN MENU
LINE 2
-PARAMETER
-DIFF. PRES UNITS 1
-SET CUSTOMTEXT2
-FILTER 3
-EXIT
LINE 1
- FILTER
- EXIT
LINE 4
same as LINE 2
LINE 2
Parameter
DIFF. PRESSURE
LINE 2
FILTER
0 (None)
see Parameter
List for selection
for lines 2, 3 & 4
0 (None) to
4 (Maximum)
Default selection shown.
Available selections:
Enhanced Display Config.
LINE 2
EXIT
Return to MAIN
MENU
LINE 1
FILTER
0 (None)
0 (None) to
4 (Maximum)
LINE 1
EXIT
LINE 3
same as LINE 2
3 Not avail if Parameter is
CUSTOM TEXT.
2 Available only if Parameter is
CUSTOM TEXT.
1 Available only if Parameter is
DIFF. PRESSURE.
LINE 2
DIFF. PRES. UNITS
in.WC
in.WC, in.Hg,
psig, Pa, kPa, bars,
mbars, mm WC,
mm Hg, kg/m 2
LINE 2
SET CUSTOM TEXT
see ASCII
Character Chart for
selection
Operator Setup Main Menu
LINE 5
same as LINE 2
1. While in Main Menu, use
UP
or
DN
to scroll to:
Enhanced Display
Configuration
2. Press
ENT
to enter Enhanced Display Configuration menu.
Display will indicate
: LINE 1
3. Press
ENT
to enter Setup menu. Display will indicate:
LINE 1
FILTER