CAMM - IO&M Manual
6
4.4
–
PROCESS CONNECTIONS
The CAMM comes standard with brass 1/8" FPT connections (or special fittings if ordered). To these connections the
customer can install fittings required for the type of tube/pipe used to connect to process sensor (i.e. flow station, flow
probe, static pressure sensors).
When connecting the CAMM to an airflow measuring device, connections must be completed as follows:
– High Port on CAMM connects to Total Pressure from airflow measuring device.
– Low Port on CAMM connects to Static Pressure from airflow measuring devices.
Although any size of tube/pipe can be used, the response time of the CAMM to process change can increase if there
is a increase in tube/pipe size or an increase in tube/pipe length.
CAUTION
– Selected fittings should be compatible with the brass 1/8" FPT bulkhead connection, and installed using an
appropriate thread lubricant/sealant.
– When signal fittings are added or removed, use a 9/16 wrench to prevent the 1/8" FPT bulkhead fitting from
turning.
– It is extremely important that no pressure be present in signal tubing at the time of installation, and the
orientation of high and low pressure signal lines is maintained between the source and the CAMM.
If process being measured contains humidity or moisture, it is recommended a drip leg with drain on each tube/pipe
be installed to preclude the migration of water into the CAMM.. See Figure 4.2. for typical drip leg installation.
Figure 4.2
SECTION 4 – INSTALLATION
CAUTION
Migration of water into
the CAMM will
void warranty.