![Air Monitor CAMM Скачать руководство пользователя страница 30](http://html.mh-extra.com/html/air-monitor/camm/camm_installation-operation-and-maintenance-manual_2875323030.webp)
CAMM
Air Monitor Corporation
116-044-91.P65 (8/31/10)
CAMM - IO&M Manual
5.8 – TRANSMITTER SCALING & CONFIGURATION (con't)
12. Use
UP
or
DN
to change setting. Once desired setting is displayed, press
ENT
, new setting will be stored in
memory and display will return to the Temperature Configuration sub-menu as in Step 10.
Note: If Operator desires not to change the setting and return to the Temperature Configuration sub-menu,
press
ESC
. Unit will remain programmed as it was originally.
13. Use
UP
or
DN
to select remaining parameters to be changed within the Temperature Configuration sub-menu.
14. Follow Step 12 to make any changes to parameters.
15. To return to the Transmitter Scaling & Configuration menu, select EXIT in the Temperature Configuration sub-
menu and press
ENT
.
25
SECTION 5 – OPERATION
16. While in Transmitter Scaling & Configuration menu, use
UP
or
DN
to scroll to: Absolute Pressure
Configuration
17. Press
ENT
to enter the Absolute Pressure Configuration sub-menu.
If Density Compensation is ON (see Process Configuration above), display will indicate: Min Abs. Pressure
Selection
If Density Compensation is OFF (see Process Configuration above), display will indicate: Abs. Pressure Off/On
Selection
18. Press
ENT
and display will indicate current selection of applicable menu from Step 17.
Min. Abs Pres.
Selection
Min. Abs. Pres.
24.00" Hg
Max. Abs. Pres.
Selection
Max. Abs. Pres.
32.00" Hg
Exit
Absolute Pressure Confguration
Available selections:
Default selection shown.
Absolute Pres Off/On
Selection
5
Absolute Pres Off/On
ON
5 Available only if Density Compensation
is OFF.
ON or OFF
Exits to Trans.
Scaling &
Configuration Menu
8.00 to 50.00" Hg
4.00 to 25.00 psia
28.00 to 170.00 kPa
280.0 to 1700.0 mbars
204.0 to 1300.0 mm Hg
Min. + 8.00 to 80.00" Hg
Min. + 4.00 to 39.00 psia
Min. + 28.00 to 270.00 kPa
Min. + 280.0 to 2700.00 mbars
Min. + 204.0 to 2030.0 mm Hg