INSPECTION & HANDLING

.

STAT-probes should be carefully inspected for damage prior to installation. Report damage to your Freight Department,
or contact delivery carrier. Almost any means of handling can be utilized depending on the length and width of the
probes.  Probes may be handled while in any position; however, it is important not to drop or mishandle the probes such
that damage is done to the sensing holes, tubular members, signal connection fittings, end studs, or mounting plates.

ORIENTATION OF PROBES

.

Using the AIRFLOW directional arrow on the probe mounting flange to determine correct orientation, install STAT-
probes with sensing holes facing airflow.

INSTALLING STAT-probes

.

To achieve published performance standards, the location of STAT-probes in ductwork must comply with the

Minimum Requirements for Installation

 (Page 4).  Mounting hole sizes can be obtained using the dimensional

data shown on Page 3.

FASTENERS

. STAT-probe mounting plates and gaskets are predrilled for 1/4" mounting fasteners.  For ducts

inaccessible from the inside, Air Monitor recommends Type AB 1/4" thread-forming tapping screws [use a No. 4
(0.209) drill for pilot hole].  If the inside of the duct is accessible, Air Monitor recommends the use of 1/4-20
bolts, nuts, and lock washers (or flat washers and lock nuts).  Fasteners should be zinc coated carbon steel, or
better.

Gasket mounting surface should be clean and burr free.  Probes should be mounted perpendicular to matting
surfaces.  Fasteners need be tightened sufficiently to evenly compress gaskets to about 1/2 original thickness.

STAT-probe and STAT-probe/SS

- 2 -

Содержание STAT-probe

Страница 1: ...been the subject of misuse neglect accident damageormalfunctioncausedbyinterconnectionwithequipmentmanufacturedbyothers improper installation or storage or used in violation of instructions furnished by Seller nor does it extend to any product which has been repaired or altered by persons not expressly approved by Seller Nor does Seller warrant equipmentagainstnormaldeteriorationduetoenvironment n...

Страница 2: ... published performance standards the location of STAT probes in ductwork must comply with the Minimum Requirements for Installation Page 4 Mounting hole sizes can be obtained using the dimensional data shown on Page 3 FASTENERS STAT probe mounting plates and gaskets are predrilled for 1 4 mounting fasteners For ducts inaccessible from the inside Air Monitor recommends Type AB 1 4 thread forming ta...

Страница 3: ...TAT probe SS AIR TEMPERATURE The STAT probe made of 3003 extruded anodized aluminum is designed to operate in air systems with temperatures up to 400ºF The STAT probe SS made of Type 316 stainless steel is designed to operate in air systems with temperatures up to 1000ºF ...

Страница 4: ...n the packing list and clearly mark this number on the outside of each shipping container Costs associated with the return of equipment to Air Monitor Corporation are the customer s responsibility regardless whether the repair return is under warranty Once the Customer Service Department determines that the equipment repair is under warranty the item will be repaired and returned to the customer a...

Отзывы: