background image

INSTALLATION INSTRUCTIONS

CAUTION:

 

MAKE SURE POWER IS SWITCHED OFF AT 

SERVICE PANEL BEFORE STARTING INSTALLATION.

SECTION 1

Preparing the Exhaust Fan

1. 

Unpack fan from the carton and confirm that all pieces are present. In addition to the 

exhaust fan you should have:

 

 

1 - Grill

 

 

1 - Damper Assembly (attached)

 

 

4 - Mounting Rails

 

 

1 - Instruction/Safety Sheet   

2. 

Choose the location for your fan. To ensure the best air and sound performance, it 

is recommended that the length of ducting and the number of elbows be kept to a 

minimum, the radius of each elbow be as large as 

possible for the installation, and that insulated hard 

ducting be used. This fan will require at least 8" of 

clearance in the ceiling or wall, and will mount through 

drywall up to 3/4" thick. The fan mounts between 16” 

or 24” on center joists using the 4 provided mounting 

rails.

3. 

Select the most convenient electrical knockout and 

remove using a straight-blade screw driver 

(Figure 1).

4. 

No additional vibration deadening materials are needed 

for this fan.

SECTION 2

New Construction

1. 

Install the rails into the mounting channel on the housing. Center the mounting channel in 

the slots on the housing, then from inside the housing tighten the mounting channel screws 

so the channel is securely in place. Position the housing next to the joist. Line up housing so 

that it will be flush with the finished ceiling. Secure the ends of the rails with screws or nails 

(not included) to the joists and slide the housing into the final position 

(Figure 2).

SECTION 3

Existing Construction

1. 

Set housing in position between the joist and trace an outline onto the ceiling material 

(Figure 3).

 Set housing aside and cut opening, being careful not to cut or damage any 

electrical or other hidden utilities. Install the rails into the mounting channel on the 

housing. Center the mounting channel in the slots on the housing, then from inside 

the housing tighten the mounting channel screws so the channel is securely in place. 

Position the housing in the previously cut hole so that it is flush with the finished ceiling. 

Secure the ends of the rails to the joists 

(Figure 2).

www.airkinglimited.com

A210952009 Rev. Q 4-16

2 of 8

SECTION 4

Ducting

NOTE: 4" OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE.

CAUTION:

 

ALL DUCTING MUST COMPLY WITH LOCAL AND 

NATIONAL BUILDING CODES.

NOTE:

 The ducting from this fan to the outside of the building has a strong effect on the air 

flow, noise and energy use of the fan. Use the shortest, straightest duct routing possible 

for best performance, and avoid installing the fan with smaller ducts than recommended. 

Insulation around the ducts can reduce energy loss and inhibit mold growth. Fans installed 

with existing ducts may not achieve their rated air flow.
1. 

Connect the ducting to the fan’s duct collar 

(Figure 4).

 Secure in place using tape 

or screw clamp. Always duct the fan to the outside through a wall or roof cap. It is 

recommended that low restriction termination fittings be used.

2. 

Ensure duct joints and exterior penetrations are sealed with caulk or other similar 

material to create an air-tight path to minimize building heat loss or gain and to reduce 

the potential for condensation. Place/wrap insulation around duct and/or fan in order to 

minimize possible condensation buildup within the duct, as well as building heat loss or 

gain 

(Figure 5).

SECTION 5

Wiring

CAUTION:

 MAKE SURE POWER IS SWITCHED OFF AT 

SERVICE PANEL BEFORE STARTING INSTALLATION.

CAUTION:

 ALL ELECTRICAL CONNECTIONS MUST BE MADE 

IN ACCORDANCE WITH LOCAL CODES, ORDINANCES, OR NATIONAL 

ELECTRICAL CODE. IF YOU ARE UNFAMILIAR WITH METHODS OF INSTALLING ELECTRICAL 

WIRING, SECURE THE SERVICES OF A QUALIFIED ELECTRICIAN.

NOTE:

 This unit may include a side access panel for wiring that does not require the removal of 

the fan’s blower assembly. If you choose to wire the unit from the inside, you will need to remove 

the blower assembly and internal wiring compartment. Both methods are equally effective.

1a.  External Wire Compartment (Not included with all models): Remove the wire 

compartment cover screw and place cover in a secure place 

(Figure 6).

Figure 1

Figure 2

Housing

Joist

Mounting Rails

Ducting

Duct 

Collar

Figure 4

Figure 5

Insulation* 

(place around and 

over Fan Housing

Fan Housing

Power Cable*

Seal gaps 

around Housing

Round 

Duct*

Seal duct joints 

with tape

Round 

Elbows*

Wall Cap*

Roof Cap* 

(with built-in 

damper)

Keep duct 

runs short

*Purchase separately

or

Figure 3

Joist

Содержание AK50S

Страница 1: ...g equipment to prevent back drafting Follow the heating equipment manufacturer s guideline and safety standards such as those published by the National Fire Protection Association NFPA and the American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE and the local code authorities c When cutting or drilling into wall or ceiling do not damage electrical wiring and other hidde...

Страница 2: ... airkinglimited com A210952009 Rev Q 4 16 2 of 8 SECTION 4 Ducting NOTE 4 OR LARGER RIGID DUCT IS RECOMMENDED FOR BEST PERFORMANCE CAUTION ALL DUCTING MUST COMPLY WITH LOCAL AND NATIONAL BUILDING CODES NOTE The ducting from this fan to the outside of the building has a strong effect on the air flow noise and energy use of the fan Use the shortest straightest duct routing possible for best performa...

Страница 3: ...n to prevent air leakage from unconditioned spaces is recommended If gaps between unit housing and ceiling are great additional material backing rod ceiling material may be required NOTE This fan is rated for direct insulation contact Type IC and it is recommended that this fan be completely covered by insulation in order to reduce heat loss or gain to unconditioned space 2 If the fan s blower ass...

Страница 4: ...you specific legal rights You may also have other rights which vary from state to state and province to province Proof of purchase is required before a warranty claim will be accepted CUSTOMER SERVICE Toll Free 800 465 7300 Our Customer Service team is available to assist you with product questions service center locations and replacement parts They can be reached Monday through Friday 8am 4pm Eas...

Страница 5: ...abricant de l équipement de chauffage et les normes de sécurité telles que celles publiées par la National Fire Protection Association NFPA et de la American Society for Heating Refrigeration and Air Conditioning Engineers ASHRAE et de celles des autorités locales du code c Lors de coupe ou de perçage des murs et plafonds ne pas endommager le filage électrique et autres utilités cachées ATTENTION ...

Страница 6: ...E MEILLEURE PERFORMANCE ATTENTION TOUS LES CONDUITS DOIVENT ÊTRE CONFORMES AUX CODES DU BÂTIMENT LOCAUX ET NATIONAUX REMARQUE La canalisation de ce ventilateur à l extérieur du bâtiment a un effet important sur le flux d air le bruit et la consommation d énergie du ventilateur Utilisez la route de canalisation la plus courte et la plus droite possible pour une meilleure performance et évitez d ins...

Страница 7: ...riel supplémentaire tige de support matériel de plafond peut être nécessaire REMARQUE Ce ventilateur est conçu pour le contact d isolation directe type IC Il est aussi recommandé que ce ventilateur soit complètement recouvert par l isolation afin de réduire la perte de chaleur ou de gagner de l espace inconditionné 2 Si l assemblage de la soufflante du ventilateur a été enlevé durant le processus ...

Страница 8: ... CLIENTÈLE Sans frais 800 465 7300 Notre équipe de service à la clientèle est disponible pour vous aider avec des questions sur le produit les adresses des centres de service et les pièces de rechange Vous pouvez la rejoindre du lundi au vendredi de 8h 00 à 16h 00 HNE Veuillez avoir le numéro du modèle disponible ainsi que le genre et le style qui se trouvent sur l étiquette à l intérieur de votre...

Отзывы: