INSTALLATION
9. Secure the ballast to the mounting base.
With the ballast pressed against the mounting base, rotate the
ballast clockwise 90° to secure it to the base. When the ballast
is fully attached, the power cord will be aligned with the view
port hole. (See Figures 18 & 19)
10. Plug Haven Plus in.
Plug the power supply cord into a standard electric wall outlet.
Check lamp operation by looking through the view port hole.
NOTE:
The view port hole is made of glass and will not allow any UVC
rays to pass through. A blue glow should be seen in the duct.
TROUBLESHOOT
If blue glow is not seen, make sure the base is properly installed.
There is a proving switch located on the base that needs to be seated
properly onto the duct. Make sure that when base is mounted that
the plated washer on the switch is raised approximately
3/16
” and the
switch is fully engaged. (See Figure 20)
11. Seal all joints and seams.
With standard duct tape, seal any joints and seams near the
mounting location to reduce any direct viewing of UV light.
12. Place replacement reminder magnet in a safe spot.
Write the date of installation on the magnet and place it in a spot
that you will see often. Replace the UVC lamp once a year.
TURN CLOCKWISE
LOCKED POSITION
SAFETY SWITCH
SAFETY SWITCH
ENGAGED
SAFETY SWITCH
NOT
ENGAGED
FIGURE 20
TURN CLOCKWISE
LOCKED POSITION
SAFETY SWITCH
SAFETY SWITCH
ENGAGED
SAFETY SWITCH
NOT
ENGAGED
TURN CLOCKWISE
LOCKED POSITION
SAFETY SWITCH
SAFETY SWITCH
ENGAGED
SAFETY SWITCH
NOT
ENGAGED
FIGURE 18
FIGURE 19
WARNING: NEVER EXPOSE EYES OR SKIN TO UVC LIGHT FROM ANY SOURCE. LOOKING
DIRECTLY AT THE UVC LIGHT MAY CAUSE PERMANENT EYE DAMAGE OR BLINDNESS.
NEVER OPERATE THE AIR+HEALTH™ AIR PURIFYING SYSTEM OUT OF THE PLENUM.
AVOID TOUCHING THE GLASS PORTION OF THE LAMP WITH YOUR HANDS.