HEPA Filters (High Efficiency Particle Arrestors) 

This type of filter is generally fitted in front withdrawal frame. Filters will be held into the 
frame by retaining bars which can be removed to allow access to replace filters. 

Carbon Filters 

Carbon filters normally have an active life of about twelve (12) months, or more. It is 
advisable to remove a sample from the pack to return to manufacturer to determine the 
remaining working life, preferably after the first six (6) months & subsequent six (6) monthly 
intervals. 
 
NOTE! WHEN REPLACING ALL FILTERS ENSURE FILTER IS FACING CORRECT 
DIRECTION AS INDICATED BY AN AIRFLOW ARROW.  
 

ROUTINE MAINTENANCE SCHEDULE 

 

 

 

 

 
 

Monthly 

3 Monthly 

6 Monthly 

Annually 

Fan Shaft Bearings 

 

 

 

 

Motors 

 

 

 

 

Belts & Pulleys 

 

 

 

 

Elec. Heater Battery 

 

 

 

 

Coils 

 

 

 

 

Eliminators 

 

 

 

 

Dampers 

 

 

 

 

Panel & Bag Filters 

 

 

 

 

HEPA Filters 

 

 

 

 

Carbon Filters 

 

 

 

 

External Surfaces 

 

 

 

 

 

MAINTENANCE OF UNITS CONTAINING F GAS REFRIGERANTS. 
 

It is a legal requirement that all units containing F Gas refrigerants such as R407c, R410a are 
serviced on a regular basis and that leak tests are carried out. This should generally be carried 
out at least every six months and a service inspection sheet issued to the customer upon 
completion. Log books should be kept on site by the end user to prove that these works have 
been carried out. The responsibility of compliance is shared by the end user and the appointed 
maintenance engineers. 
 
Failure to comply with the F Gas regulations will result in invalidation of the warranty on the 
refrigeration system within the unit. 
 

INVALIDATION OF GUARANTEE 

 

 

 

 

 

 

The following misuses or maltreatment of AIR HANDLERS LIMITED equipment will 
render all guarantees, as set out on the Conditions of Sale, void. 
 

 

Failure to install, set up or put to work any part of the equipment as specified in AIR 
HANDLERS LIMITED Installation, Operation and Maintenance Instructions. 

 

Attempting to operate the motors and other electrical equipment with an electrical 
supply other than that designated on the motor nameplate, or failing to connect and 
protect such equipment in accordance with I.E.E. Regulations and local by-laws. 

 

Failure to notify AIR HANDLERS LIMITED of equipment damaged on receipt in 
writing within five (5) days. 

 

Failure to run equipment within the design specifications as notified at the time of 
order. 

Содержание Envirofresh Series

Страница 1: ...ANCE INSTRUCTIONS FOR SERIES ENVIROFRESH AIR HANDLING UNITS CONTRACT No PROJECT REF AIR HANDLERS LIMITED Alfred Proctor House Bute Street Weaste Salford M50 1DU TEL 0161 745 8888 FAX 0161 925 9900 mai...

Страница 2: ...electric motor s the procedure as laid down in this manual is fully carried out The procedure for removing and replacing timing wedge belts and filter media bags or panels are fully carried out as la...

Страница 3: ...also essential for service and maintenance purposes and for the removal of the motor s INSTALLATION All units must be installed in accordance with good engineering standards upright and levels on a p...

Страница 4: ...ed to prevent damp and ingress of dust or foreign bodies and held in a dry store Fan Shaft Bearings Refer to Bearing damage in Cautionary Notes Bearings fitted with shields should not be stored for pe...

Страница 5: ...ation drive belts should be checked for tension and re tensioned if required Maintenance At least every 12 months a major inspection of the fan section should be carried out as follows Isolate electri...

Страница 6: ...motors are shipped with sufficient grease for a long operating period if relubrication is needed using a low pressure hand operated grease gun pump in clean recommended grease until the new grease app...

Страница 7: ...et the lower marker ring at the deflection distance required in mm on the lower scale Set the upper marker ring against the bottom edge of the tube Place the belt tension indicator on top of the belt...

Страница 8: ...n bends of the coil Damage to fins can be corrected by use of a fin comb available from Air Handlers all coils should be installed level and upright unless otherwise specified Care must be taken to en...

Страница 9: ...um breakers must be installed between the coil and the trap inlet to ensure that the hydraulic head drain the coil when it is at atmospheric or sub atmospheric pressure The vacuum breaker should respo...

Страница 10: ...ot twisted by ductwork and that fixings do not penetrate cog housing of the damper which will affect the damper mechanism Ductwork must be independently supported and should not be left to hang from t...

Страница 11: ...rried out This should generally be carried out at least every six months and a service inspection sheet issued to the customer upon completion Log books should be kept on site by the end user to prove...

Страница 12: ...pproval of AIR HANDLERS LIMITED Damage caused to equipment on site through lack of adequate protection from the elements or misuse by other trades Failure to observe all normally accepted engineering...

Страница 13: ...S manifold and compare them with the commissioning sheet If there is any significant variation then the fault should be found and corrected Refer to the troubleshooting chart If on inspection of the r...

Страница 14: ...k isolator mains supply Check settings Inspect fireman s panel Check actuator operation and end switch making when open Check control switch fuses MCB s and control circuit wiring Inspect drive belts...

Страница 15: ...mpressor section Check operation and settings Check operation and settings of the indoor frost protection stat Check fan runs on to dissipate heat prior to unit shut down Replace if faulty and reset h...

Страница 16: ...d control circuit wiring Step energised on controller Check air flow failure switches Check delay timer operation check controller timer operation Change compressor Check winding resistance replace co...

Страница 17: ...or internal leak Icing coil Low on refrigerant Indoor check valve leaking Outdoor check valve not fully open Icing coil Low on refrigerant 4 port valve not fully engaged or internal leak Outdoor chec...

Страница 18: ...it is the installers responsibility to ensure correct lagging Installers Responsibility Installation Unless otherwise specified by ourselves this product is supplied with the intention to be incorpor...

Отзывы: