ommIssIonInG

Starting Up

Filling the Tank

Condition(s):

Tank flushed with fresh water.

Filling procedure:

DHW Tank:

1. 

Connect the cold water circuit to the distribu-

tion network outlet.

2. 

Make sure that the isolating valve of the cir-

cuit is open

3. 

Open a hot water draw-off tap at a high point 

in the system

4. 

Once the air is purged and the flow has sta-

bilised at the tap, close the tap.

Primary tank:

1. 

Fill the primary circuit through the primary cir-

cuit supply connection (inlet). 

2. 

Bleed the air from the primary tank and re-

peat  water  filling  until  you  reach  1,0  bar  to 

1,5 bar. Take care not to exceed 1,5 bar.

Follow-on Task(s):

 

î

Check that there are no leaks

 

î

Start the boiler as required. Refer to the 

Start-

up

 procedure opposite.

Always  fill  and  pressurise  the  inner 

tank  (DHW)  before  filling  the  outer 

(primary) tank. Failure to comply may 

damage the inner tank.

Condition(s):

Start-up procedure:

1. 

Turn on the heat generator connected to the  

tank.

2. 

Allow the tank to heat up and reach set tem-

perature.

3. 

Run water from a hot draw-off tap and adjust 

DHW thermostatic mixing valve to a suitable 

temperature (Minimum supply temperature 

60° on systems with a pumped return).

Follow-on Task(s):

Check that there are no leaks.

As  the  tank  is  connected  to  a  heat 

generator (e.g. a boiler), the DHW de-

mand  will  be  generated  through  the 

heat generator controller. Please refer 

to the heat generator technical manual 

for the correct start-up procedure.

i

Содержание SILOX S

Страница 1: ...h e a t i n g s y s t e m s EN installation and maintenance manual FOR THE INSTALLER AND THE USER 90 130 190 260 400 600 1000 L DOMESTIC HOT WATER STAINLESS STEEL TANKS I10_092 01 SILOX S SILOX S...

Страница 2: ...operation of the appliance and the hydraulic system as well as the safety devices that are provided Any instruction regarding periodic checks to be performed and possible anomaly to be reported All t...

Страница 3: ...ts 11 Recommendations for the Quality of Water Primary circuit 12 Hydraulic Connections 13 Commissioning 14 Filling the Tank 14 Starting Up 14 Maintenance 15 Safety Instructions and Recommendations 15...

Страница 4: ...r injuries or death Indicates an important instruction which if not followed could re sult in a hazardous situation that could cause damage to equip ment and or injuries Indicates an essential instruc...

Страница 5: ...or written consent of the manufacturer If components need to be replaced only genuine factory parts or compo nents approved by the manufacturer must be used When working on the appliance and the syste...

Страница 6: ...and hole 2 Thermal insulation 3 Drywell for temperature sensor 4 DHW inner storage tank in stainless steel 5 Steel primary outer tank 6 Primary connection return 7 Base cover 8 Inspection hole 9 Dip t...

Страница 7: ...170 182 182 182 192 336 D 575 980 777 1027 1512 1493 1926 Connections in SX90S SX130S SX190S SX260S SX400S SX600S SX1000S Cold water inlet M G 3 4 G 3 4 G 3 4 G 3 4 G 1 G 1 G 11 4 DHW outlet M G 3 4 G...

Страница 8: ...pty weight Kg 35 51 64 78 106 151 239 Standing heat loss W 45 50 58 63 99 103 113 Energy efficiency class B B B B C C C Hydraulic Performance SX90S SX130S SX190S SX260S SX400S SX600S SX1000S Peak Flow...

Страница 9: ...and temperatures of the primary circuit for DHW production from 10 C to 45 C Performance and pressure losses 86 Pressure losses between input and output connections of the primary circuit for differen...

Страница 10: ...the electrical circuit isolate the electri cal supply of the appliance through the external power cutting device fuse circuit breaker etc All connections must be carried out in accordance with curren...

Страница 11: ...appli ance power and the system size and the increase in temperature and pressure Using antifreeze in the primary circuit will reduce the heating performance The higher the concentration of antifreeze...

Страница 12: ...eds to be refilled frequently check for leaks in the primary circuit Inhibitors may be used according to stand ard EN 14868 An air separator on the appliance supply circuit combined with a dirt separa...

Страница 13: ...f tap DHW Outlet Isolating valve Cold water inlet Thermostatic mixing valve Pressure reducing valve Motorised spring return valve or manual valve From distribution network Make sure that your hydrauli...

Страница 14: ...d 1 5 bar Follow on Task s Check that there are no leaks Start the boiler as required Refer to the Start up procedure opposite Always fill and pressurise the inner tank DHW before filling the outer pr...

Страница 15: ...ne factory parts or parts approved by the manu facturer Replace any gaskets or seals present on the removed components before reinstallation unless otherwise speci ed in the procedures Operate manuall...

Страница 16: ...is sound Gradually introduce the descaling agent until the correct amount is added for the volume of water Run the pump and monitor the pH value the pro cess is complete when the pH stabilises at less...

Страница 17: ...an be extremely hot Use extreme care when draining a hot appliance Draining procedure Always drain depressurize the outer tank before draining the inner tank to prevent any deformation of the inner ta...

Страница 18: ...refer to the heat generator manual The isolating valves of the primary circuit are closed 2 Open the isolating valves to allow prima ry water to fill the outer tank Make sure that the DHW in ner tank...

Страница 19: ...uct Fiche AIC SILOX S Referring to Commission Delegated Regulation No 812 2013 Model Energy efficiency class Standing loss Volume SX90S B 45 W 80 l SX130S B 50 W 122 l SX190S B 58 W 187 l SX260S B 63...

Страница 20: ...AIC Europe B V Graafschap Hornelaan 163A NL 6001 AC Weert The Netherlands www myaic eu...

Отзывы: