I-41
Z-038791_EN • Rev A
P
roduct
I
nstallatIon
Calculation of the Chimney Length
The chimney length must be calculated using the
values in the tables below for both parallel and
concentric configurations.
1.
Compose your system.
2.
Add up the values from the tables below
(straight pipes and elbows), of all the com-
ponents used in the chimney system.
3.
Compare the resulting value with the maxi-
mum length value for your type of chimney
connection (parallel or concentric.)
Maximum Chimney Length (terminals incl.)
Parallel
(100/100)
Concentric
(100/150)
N 60 WH
70 m
25 m
N 80 WH
40 m
N 100 WH
25 m
N 120 WH
25 m
Equivalent Length of Chimney Components
90°
45°
1 m
Parallel connection
(N 60 to N120 WH)
3.7 m
2.3 m
1 m
Concentric connection
(N 60 to N120 WH
2.0 m
1.3 m
1 m
The resulting value must be lower than
the maximum value indicated in the ta
-
ble above for the considered appli
-
ance. Failure to comply can result in
severe injuries or death.
The chimney system must be engi-
neered by a qualified professional,
according to local standards and
regulations. The overall installation
resistance of each boiler should not
exceed the value indicated in the
combustion table (including maxi-
mum wind condition) measured at
the outlet of each boiler at maximum
Please contact your AIC representa-
tive for more information
Engineering the Chimney System
î
The flue system length must be
calculated so as to ensure a safe
performance of the system. See
“Calculation of the chimney
length” on the right.
î
Make sure to install the boiler with the short-
est length of combustion air and flue ducts.
î
When several boilers need to be connected
to a common duct, please contact your AIC
representative for more information.
î
For C43(x), C63(x) and
C83(x) chimney type-
connections, please
consider the follow-
ing dimensions of the
concentric connection
for the definition of the
components in your
chimney system.
i
Accessories
If required by local regulations, install
a condensate neutralisation system.
In that case, it may be necessary to
install the boiler on a base to get suf-
ficient downward flow. If flow is not
sufficient, install a condensate pump.
i
±0,45
1
-
+
0,5
+0,3
Int.
150
Int.
±0,5
101
100
Ext.
0,7
Ext. 149
-
56
±3
10
±5
56
±3