5.15 ELECTRONIC LEVEL CONTROLLED CONDENSATE DRAIN BEKOMAT 31
The electronic level controlled drain BEKOMAT has a special condensate management that makes sure that
condensate is drained safely without any unnecessary air-loss. This drain consists of a condensate accumulator
where a capacitive sensor continuously checking liquid level is placed: as soon as the accumulator is filled, the
sensor passes a signal to the electronic control and a diaphragm solenoid valve will open to discharge the
condensate. Right in time the discharge line will be closed again without wasting compressed air.
ATTENTION! These BEKOMAT condensate drains have been specially designed for the use in a
refrigerant dryer AHT. Any Installation in other compressed air treatment units or the exchange against a
different drain brand may lead to malfunction. Do not exceed the max. operating pressure (see type plate)!
MAKE
SURE
WHEN
THE
DRYER
STARTS
THE
UPSTREAM
VALVE
IS
OPEN.
CONTROL PANEL FOR BEKOMAT 31
AHT 20-100
TEST
Power
The control panel here illustrated allows checking of drain working.
Power-LED ON - drain ready to work / supplied
Test
: test button - discharge test (keep pushed for 2 seconds)
MEMBRANE FUNCTION OF BEKOMAT 31 AHT 20-100
TROUBLESHOOTING BEKOMAT 31 AHT 20-100
The detection of defects should be carried out by qualified personnel.
SYMPTOM
POSSIBLE CAUSE - SUGGESTED ACTION
No led lighting up.
Check for mains failure.
Verify the electric wiring (internal and/or external).
Check internal printed circuit board for possible damage.
Pressing of Test
button, but no
condensate discharge.
The service valve located before the drain is closed - open it.
The dryer is not under pressure - restore nominal condition.
Solenoid valve defective. Replace Service Unit (see para 5.17
MAINTENANCE
BEKOMAT).
The internal printed circuit board is damaged - replace the drain.
Condensate discharge
only when Test button
is pressed.
Too much internal dirt. Replace Service Unit (see para 5.17
MAINTENANCE
BEKOMAT).
Drain keeps blowing
off air.
Replace Service Unit (see para 5.17
MAINTENANCE BEKOMAT).
Drain in alarm
condition.
The service valve located before the drain is closed - open it.
The dryer is not under pressure - restore nominal condition.
Replace service unit (see para 5.17
MAINTENANCE BEKOMAT).
Содержание 20-350
Страница 29: ...7 1 1 AHT 20 50 AC 7 1 2 AHT 75 AC 7 1 3 AHT 100 150 AC ...
Страница 30: ...7 1 4 AHT 200 250 AC 7 1 5 AHT 300 350 AC ...
Страница 31: ...7 2 1 AHT 20 50 ...
Страница 32: ...7 2 2 AHT 75 ...
Страница 33: ...7 2 3 AHT 100 ...
Страница 34: ...7 2 4 AHT 150 ...
Страница 35: ...7 2 5 AHT 200 250 ...
Страница 36: ...7 2 6 AHT 300 350 ...
Страница 41: ...NOTE ...
Страница 42: ...NOTE ...
Страница 43: ...NOTE ...
Страница 44: ...GRAMAGLIA GO ...